Page 1
Installation and operating manual GB/en Fire damper FKRS-EU according to Declaration of Performance DoP / FKRS-EU / DE/ 006 Read the instructions prior to performing any task!
Page 2
TROX GmbH Heinrich-Trox-Platz 47504 Neukirchen-Vluyn Germany Phone: +49(0)2845 202-0 Fax: +49 (0) 2845 202-265 Email: trox-de@troxgroup.de Internet: http://www.troxtechnik.com Installation and operating manual (translation of the original) A00000092709, 3, GB/en 03/2025 Valid from 01.07.2024 Fire damper FKRS-EU...
This operating and installation manual enables oper- the state of the art, and our expertise and experience of ating or service personnel to correctly install the TROX many years. product described below and to use it safely and effi- The manufacturer does not accept any liability for dam- ciently.
Page 4
Warning – danger zone. Potentially hazardous situation which, if not avoided, may result in property damage. ENVIRONMENT! Environmental pollution hazard. Tips and recommendations Useful tips and recommendations as well as informa- tion for efficient and fault-free operation. Fire damper FKRS-EU...
5.5.10 Dry mortarless installation remote from 2.2 FKRS-EU with fusible link ....... solid walls with installation kit WE2 2.3 FKRS-EU with spring return actuator ..13 (wall penetration) ........ 82 2.4 FKRS-EU with spring return actuator and 5.5.11 Installation remote from solid walls with smoke detector ........
Page 6
5.11.7 Mortar-based installation in hollow core 5.15.3 Fixing in conjunction with fire batt/fire ceiling ..........220 protection block bulkhead ....256 5.11.8 Mortar-based installation in ribbed 5.15.4 Fire damper remote from walls and ceiling ..........221 ceilings ..........Fire damper FKRS-EU...
Page 7
10.2 Replacing the fusible link ..... 270 10.3 Inspection and repair measures ..271 Decommissioning, removal and disposal . 273 11.1 Final decommissioning ......273 11.2 Removal ..........273 11.3 Disposal ..........273 Nomenclature ..........275 Revision history ........... 281 Index.............. 286 Fire damper FKRS-EU...
Operation of fire dampers is allowed only in compli- ance with installation regulations and the technical data in the installation and operating manual. Modifying the fire dampers or using replacement parts that have not been approved by TROX is not permitted. Fire damper FKRS-EU...
Trained personnel are individuals who have sufficient professional or technical training, knowledge and actual experience to enable them to carry out their assigned duties, understand any potential hazards related to the work under consideration, and recognise and avoid any risks involved. Fire damper FKRS-EU...
Data applies to uniform upstream and downstream conditions for the fire dampers. Non-condensing operation and without humidity ingress via the outdoor air intake. For explosion-proof constructions of the FKRS-EU, see additional operating manual. Leakage rate of the fire damper system tested at 300 Pa and 500 Pa negative pressure.
Page 11
Ä Chapter 5.1 ‘Overview of installation Notified body may vary The last two digits of the year in which the CE situations’ on page 26 marking was affixed Type Year of manufacture Order number Fire damper FKRS-EU...
Technical data FKRS-EU with fusible link 2.2 FKRS-EU with fusible link Dimensions and weights Fig. 2: FKRS-EU with fusible link Y Keep clear to provide access for operation A Installation side B Operating side Limit switch Connecting cable length/cross section 1 m / 3 ×...
Fig. 3: FKRS-EU with spring return actuator Y Keep clear to provide access for operation A Installation side B Operating side Ä 12 . Weight of FKRS-EU with fusible link + approx. 1.5 kg, see table Spring return actuator Construction 230 V...
Page 14
Technical data FKRS-EU with spring return actuator Dimensions and weights Fig. 4: FKRS-EU with spring return actuator (also suitable for Siemens bus system) Y Keep clear to provide access for operation A Installation side B Operating side Weight of FKRS-EU with fusible link + approx. 1 kg, see table Ä...
Page 15
Technical data FKRS-EU with spring return actuator FKRS-EU with Schischek explosion-proof spring return actuator The FKRS-EU can also be supplied with Schischek explosion-proof spring return actuator on request: ExMax-15-BF-TR RedMax-15-BF-TR For further information, see "Supplementary oper- ating manual for explosion-proof fire dampers Type FKRS-EU".
2.4 FKRS-EU with spring return actuator and smoke detector Dimensions and weights Fig. 5: FKRS-EU with spring return actuator and RM-O-M smoke detector, drawn in a circular duct (on site) Y Keep clear to provide access for operation A Installation side...
Page 17
FKRS-EU with spring return actuator and smoke de... Dimensions and weights Fig. 6: FKRS-EU with spring return actuator and RM-O-3-D smoke detector, drawn in a rectangular duct (on site) Y Keep clear to provide access for operation A Installation side B Operating side Fig.
FKRS-EU as an air transfer damper (FD) 2.5 FKRS-EU as an air transfer damper (FD) Dimensions and weights Fig. 8: FKRS-EU with fusible link and cover grilles as an air transfer damper (FD) Y Keep clear to provide access for operation A Installation side B Operating side Note: Air transfer dampers may require a general building inspectorate licence.
FKRS-EU as an air transfer damper (MFD) 2.6 FKRS-EU as an air transfer damper (MFD) Dimensions and weights Fig. 9: FKRS-EU with spring return actuator and duct smoke detector as an air transfer damper (MFD) Y Keep clear to provide access for operation A Installation side B Operating side Ä...
Store it in a dry place and remote from direct sun- light. Do not expose it to the effects of weather (even in its packaging). Do not store it below -40 °C or above 50 °C. Fire damper FKRS-EU...
(i.e. in the event of a fire), it must not be reopened. 4.2 FKRS-EU with fusible link Fig. 11: FKRS-EU with spring return actuator Casing Damper blade with ring seal Travel stop for CLOSED position...
Parts and function FKRS-EU with spring return actuator and smoke de... 4.4 FKRS-EU with spring return actuator and smoke detector Fig. 12: FKRS-EU with spring return actuator and smoke detector RM-O-M Casing Rectangular duct, customer supply Damper blade with ring seal 10.1...
Fig. 13: FKRS-EU and RM-O-M in circular duct FKRS-EU Circular duct, customer supplied Fig. 16: FKRS-EU as an air transfer damper (FD) 10.1 Spring return actuator 10.12 Smoke detector RM-O-M, fixed with bracket CRD...
Page 24
(72 °C) is reached. Smoke can, however, spread below this temperature. The air transfer damper consists of the FKRS-EU fire damper with thermal release mechanism 72 °C and cover grilles on both sides. It does not include a duct smoke detector.
The power supply is interrupted (closed current prin- ciple) The air transfer damper consists of the FKRS-EU fire damper with a thermal release mechanism 72 °C, cover grilles on both sides and a duct smoke detector. For more information on the installation and use as an air transfer damper (MFD) in Germany, see general type approval Z-6.50-2516.
The performance classes of the fire damper and the wall or ceiling may differ. The lower performance class determines the performance class of the overall system. Fire dampers with stainless steel casing (FKRS-EU-2/... version) have a performance class up to EI 90 S for all subsequent applications due to an update of EN 15882.
Page 27
The class of performance depends on the installation details E = Installation kit Thickness increased near the installation opening W = Coated board system Depending on local conditions T = Dry mortarless installation Up to EI 90 S with stainless steel casing Fire damper FKRS-EU...
Page 28
The class of performance depends on the installation details E = Installation kit Thickness increased near the installation opening W = Coated board system Depending on local conditions T = Dry mortarless installation Up to EI 90 S with stainless steel casing Fire damper FKRS-EU...
Page 29
The class of performance depends on the installation details E = Installation kit Thickness increased near the installation opening W = Coated board system Depending on local conditions T = Dry mortarless installation Up to EI 90 S with stainless steel casing Fire damper FKRS-EU...
Page 30
The class of performance depends on the installation details E = Installation kit Thickness increased near the installation opening W = Coated board system Depending on local conditions T = Dry mortarless installation Up to EI 90 S with stainless steel casing Fire damper FKRS-EU...
6 ‘Accessories’ on page 260 . mortar-based installation. When installing the FKRS-EU, the statics of the sup- Connecting duct and extension piece ...
Page 32
For information on the use of elastomer foams see Ä ‘Additional provision for use in Germany:’ on page 8 . The following applies to Great Britain: Fire damper FKRS-EU...
Page 33
You may choose a different arrangement as long as you comply with the general building inspectorate licence/ general type certification for the duct smoke detector. Fig. 20: FKRS-EU with spring return actuator and smoke detector (example RM-O-3-D) Y Keep clear for operation and maintenance...
Page 34
Installation General installation information Fig. 21: FKRS-EU with spring return actuator and duct smoke detector as an air transfer damper (MFD) Y Keep clear for operation and maintenance Fire damper FKRS-EU...
Page 35
Installation into separate installation openings With shortened cover plate Minimum distance depends on fire resistance rating and supporting construction. Distance between installation block(s) Supporting construction, Ä ‘Installation orientation (see installation details for fire resistance rating)’ on page 36 Fire damper FKRS-EU...
Page 36
E/A, B, D – F E/– Wooden panel elements In/combined with a wooden beam ceiling E/A, B, D – F E/– In historic wooden beam ceilings * The following applies to Germany: Installation requires a project-related type approval. Fire damper FKRS-EU...
Page 37
Larger mortar gaps do not have a negative effect on fire minimum/maximum clearance must be observed) protection and are, in our opinion, harmless. Equivalent mortars that meet the requirements of the above standards, gypsum mortar, or concrete Fire damper FKRS-EU...
Page 38
Use only sealant or coating that is suitable for the coated board system. Apply firestop coating to the mineral wool slabs, ridges, transitions and to any damage on the pre-coated mineral wool slabs; coating thickness ≥ 2.5 mm. Fire damper FKRS-EU...
Page 39
In addition to the listed fire batt systems, alternative fire batt systems with ablative coatings can be used if they FKRS-EU fulfil the following requirements: Non-flammable slab material, melting point ≥ 1000°C, minimum thickness 50 mm Fire damper FKRS-EU...
Page 40
Hilti soft penetration seal system (CFS-CT, CP 670 walls with metal support and sandwich panel walls. and CP 673), are permitted in the TROX combined pen- etration seal. The positions of the fire dampers, pipes and cables in the combined penetration seal are irrele- vant as long as the specified distances are maintained.
General installation information > Requirements for wall and ceiling systems 5.3.1 Requirements for wall and ceiling systems FKRS-EU fire dampers may be installed in wall and ceiling systems if these walls and ceilings have been erected in compliance with the relevant regulations, and if the information on the respective installation situation applies and the following requirements are met.
Page 42
The geometry of the metal pro- files can deviate from standard metal profiles. Use of the FKRS-EU in such walls is permitted Fig. 29: Distance from the FKRS-EU to other TROX fire if the wall construction has been approved by dampers in mortar-based installation the wall manufacturer.
Page 43
Self-supporting sandwich panels/layered boards (sheet steel ≥ 0.5 mm, both sides, mineral wool – Installation with the operating side (B) on the room end. filling, ≥ 1000°C, ≥ 115 kg/m – Wall thickness ≥ 100 mm to 200 mm. Fire damper FKRS-EU...
Page 44
– For further information, see "Additional documented on site. assembly instructions for asymmetrical shaft walls in fire dampers, type FKRS-EU". – Additional assembly instructions for room mod- ® ules according to the FireShield manufacturer's specifications.
Page 45
The use of fire dampers in walls and ceilings with slope is permitted if the fire damper remains completely in the inclination plane of the wall/ceiling. The position of the damper blade shaft is horizontal. Fig. 30: Installation in walls and ceilings with slope Fire damper FKRS-EU...
Fig. 32: Supply package and installation of installation block ER for dry mortarless installation FKRS-EU 2.18 Installation block ER with cover plate Dimensions of installation opening/cover plate [mm] Nominal size ÆDN ÆD1* ☐B Installation opening tolerance ±2 mm * Diameter of the core drill hole in solid walls and ceilings Fire damper FKRS-EU...
When using reveals, these are limited to a maximum of 25 mm or 2 × 12.5 mm. Fig. 33: Supply package and installation of installation kit TQ2 for dry mortarless installation FKRS-EU Half shell 2 2.11 Installation kit TQ2, consisting of: Connecting clamp (2 ×) Half shell 1 Intumescent seal (2 strips) Fire damper FKRS-EU...
Page 49
Installation of installation kit TQ2 Place half shells (2.11a) and (2.11b) of the installation kit (2.11) around the FKRS-EU so that the cover plate is flush with the bead. Fix the installation kit with two connecting clamps (2.11c) (any installation position of the FKRS-EU).
Fig. 34: Supply package and installation of installation kit WA2 for dry mortarless installation FKRS-EU Half shell 2 with Kerafix sealing tape Installation kit WA2, consisting of: Connecting clamp (2 ×) Half shell 1 with Kerafix sealing tape Fire damper FKRS-EU...
Page 51
Installation of installation kit WA2 Place the half shells (2.5a) and (2.5b) of the instal- lation kit (2.5) around the FKRS-EU so that it is flush with the bead (screw connections of the installation kit aligned towards the operating side).
Fig. 35: Scope of supply and assembly Installation kit WE2 for dry mortarless installation FKRS-EU Connecting clamp (2 ×) Installation kit WE2, consisting of: Sheet metal cover plate with Kerafix sealing tape Half shell 1 Drywall screw Half shell 2 Fire damper FKRS-EU...
Page 53
Installation kits > Installation kit WE2 Mounting installation kit WE2 Place the half shells (2.6a) and (2.6b) of the instal- lation kit (2.6) around the FKRS-EU so that it is flush with the bead (screw connections of the installation kit aligned towards the operating side).
Fig. 36: Supply package and installation of installation kit GL2 for dry mortarless installation FKRS-EU Half shell 2 2.12 Installation kit GL2, consisting of: Connecting clamp (2 ×) Half shell 1 Bracket Fire damper FKRS-EU...
Page 55
Cover (supplied by customer) Half shell 2 Fig. 38: Steel angle for dry mortarless installation with installation kit GL2 in lightweight partition wall if there is no rear fastening possibility 8.37 Steel bracket, supplied by customer Welded seam Fire damper FKRS-EU...
Page 56
ÆD Installation of installation kit GL2 Place the half shells (2.12a) and (2.12b) of the installation kit (2.12) around the FKRS-EU so that it is flush with the bead (screw connections of the installation kit aligned towards the operating side).
Half shell 2 with Kerafix sealing tape Assembly of installation kit GL2 Place the half shells (2.20a) and (2.20b) of the installation kit (2.20) around the FKRS-EU so that it is flush with the bead (screw connections of the installation kit aligned towards the operating side).
Page 58
Fig. 41: Mounting twin installation kit TS2 Place two assembled installation kits TS2 (2.20) with FKRS-EU next to each other as shown. Unscrew only one screw (2.20e) at a time from the actuator's side of the TS2 and screw it back on directly with a lug (2.20d).
Dry mortarless installation 40 – 600 10/40 – 600 with coated board system Observe the maximum permissible size of the coated board system! Distance between the installation blocks Depending on fire resistance rating Installation opening tolerance ± 4 mm Fire damper FKRS-EU...
Page 60
Installation Solid walls > General information Additional requirements: solid walls Solid wall, Ä on page 42 Ä Distances and installation orientation, ‘Dis- tances’ on page 35 Fire damper FKRS-EU...
Installation near the floor as in Mortar Filling of the perimeter gap with mortar and Solid wall a slanted smooth finish to at least 100 mm Solid ceiling/solid floor (optionally on one or two ends) – Up to EI 120 S Fire damper FKRS-EU...
Page 62
Mortar-based installation in solid wall - installation not flush with wall Fig. 45: Mortar-based installation in solid wall - installation not flush with wall FKRS-EU Solid wall Mortar, alternatively closing the perimeter gap Up to EI 120 S with mortar and sloping plaster finish 2.1* Mortar/cement mortar Fire damper FKRS-EU...
Page 63
Note for installation in gypsum wallboards with W = 80 to < 100 mm: Distance between two fire dampers ≥ 200 mm in separate installation openings at W ≥ 100 mm, distances Fig. 43 to Fig. 45 Fire damper FKRS-EU...
Page 64
The number of fire dampers in an installation opening is limited by their size (B × H for FK2-EU and/or Ænominal width for FKRS-EU) and the overall area of the fire dampers (1.2 m Other arrangements (side by side or on top of each other) are possible.
Page 65
Solid wall, Ä on page 42 Mortar-based installation in opening or cut hole Ä 31 ff General installation information, General information on mortar-based installation, Ä ‘Mortar-based installation’ on page 37 Fire damper FKRS-EU...
Solid walls > Mortar-based installation – multiple occupancy... 5.5.3 Mortar-based installation – multiple occupancy of one installation opening Fig. 48: Mortar-based installation – multiple occupancy of one installation opening FKRS-EU Solid wall (load-bearing structural element) Mortar Solid ceiling slab (load-bearing component) Fire damper FKRS-EU...
Page 67
Installation Solid walls > Mortar-based installation – multiple occupancy... Fig. 49: Mortar-based installation – multiple occupancy of one installation opening FKRS-EU Solid wall Mortar up to EI 90 S Fire damper FKRS-EU...
Page 68
opening is limited by their size (nominal width) and the overall area of the fire dampers (1.2 m ) (max- imum 10 FKRS-EU in single or double row arrange- ment) Distance to load-bearing structural elements ≥ 40 mm Maximum mortar bed width 225 mm;...
The following applies in Germany: For notes on the use of elastomeric foams Ä ‘Additional provision for use in Germany:’ on page 8 . required for nominal diameter ≥ 224 mm, alter- natively 6.19, 6.20 or 6.24 up to EI 90 S Fire damper FKRS-EU...
Page 70
42 Distance of 40 – 50 mm between the fire damper and load-bearing components 40 – 225 mm distance between two FKRS-EU fire dampers The difficult-to-access installation gap between the FKRS-EU and the wall/ceiling must be completely filled in the wall area.
Solid wall, on page 42 Distance from the fire damper to the top edge of the wall 40 – 225 mm Distance between two fire dampers ≥ 40 mm, perim- eter gap ≤ 225 mm Fire damper FKRS-EU...
Fixing by means of four wall plugs (M6) with fire safety suitability certificate, matched to the respective building material, is permissible, provided that all prevailing conditions of the wall plug proof are observed. Fire damper FKRS-EU...
Fig. 53: Dry mortarless installation into a solid wall, with installation kit TQ2 FKRS-EU Threaded rod as push-through installation or suit- 2.11 Installation kit TQ2 with cover plate able metal anchors approved by the building Solid wall authorities, min. M6 Up to EI 120 S Fire damper FKRS-EU...
Page 74
Fixing by means of four wall plugs (M6) with fire safety suitability certificate, matched to the respective building material, is permissible, provided that all prevailing conditions of the wall plug proof are observed. Fire damper FKRS-EU...
7.14 Reinforcing board, calcium silicate, thickness = 30 – 50 mm or mineral wool, ≥ 1000 °C, ≥ 140 kg/m³, thickness = 50 mm Extension piece/duct with shortened flush with the wall up to EI 90 S Fire damper FKRS-EU...
Page 76
(M8) with fire safety suitability certificate, matched to the respective building material, is permissible, provided that all prevailing conditions of the wall plug proof are observed. Note: Tighten the nuts hand-tight to approx. 5 Nm for fastening. Fire damper FKRS-EU...
MQ 41 × 3 mm or equivalent also possible ® Hilti drilled plate MQZ L13 or equivalent PROMATECT®-H strip d = 10 mm Hexagon nut M10 with washer 8.28 PROMATECT®-H strip d = 15 mm Up to EI 120 S Fire damper FKRS-EU...
Page 78
® drilled plate MQZ L13 or equivalent also possible Hexagon nut M10 with washer 6.13 Mineral wool, ≥ 1000 °C, ≥ 80 kg/m³, or gypsum Up to EI 120 S mortar to even out an uneven ceiling Fire damper FKRS-EU...
Page 79
Sheet steel duct with fire-rated cladding The cladding of the air duct and the suspensions are carried out in accordance with these instruc- tions, the additional assembly instructions for the installation kit WE2 and the specifications of the panel manufacturer Fire damper FKRS-EU...
Page 80
MQZ L13 or equivalent also possible Hexagon nut M10 with washer 6.13 Mineral wool, ≥ 1000 °C, ≥ 80 kg/m³, or gypsum Up to EI 120 S mortar to even out an uneven wall or ceiling Fire damper FKRS-EU...
Page 81
31 ff General information on installation with installation Ä kit WE2, on page 38 Note: For more installation details and for components to be provided by the customer, see the additional WE2 installation manual. Fire damper FKRS-EU...
The cladding of the air duct and the suspensions are carried out in accordance with these instruc- tions, the additional assembly instructions for the installation kit WE2 and the specifications of the panel manufacturer Suspension system (by others) consisting of: Fire damper FKRS-EU...
Page 83
Sheet steel duct with fire-rated cladding The cladding of the air duct and the suspensions are carried out in accordance with these instruc- tions, the additional assembly instructions for the installation kit WE2 and the specifications of the panel manufacturer Fire damper FKRS-EU...
Page 84
Sheet steel duct with fire-rated cladding The cladding of the air duct and the suspensions are carried out in accordance with these instruc- tions, the additional assembly instructions for the installation kit WE2 and the specifications of the panel manufacturer Fire damper FKRS-EU...
Page 85
Sheet steel duct with fire-rated cladding The cladding of the air duct and the suspensions are carried out in accordance with these instruc- tions, the additional assembly instructions for the installation kit WE2 and the specifications of the panel manufacturer Fire damper FKRS-EU...
Page 86
31 ff General information on installation with installation kit WE2, Ä on page 38 Note: For more installation details and for components to be provided by the customer, see the additional WE2 installation manual. Fire damper FKRS-EU...
Solid wall circumferentially glued 6.29* Mineral wool PAROC Hvac Fire Mat BlackCoat Sheet steel duct (≥ 80 kg/m Please check in advance whether the PAROC material is available in your market region. Up to EI 60 S Fire damper FKRS-EU...
Page 88
Ä on page 38 Distance between two fire dampers ≥ 400 mm Distance to load-bearing/adjacent components ≥ 200 mm Suspend the fire damper and air duct according to the mineral wool manufacturer's specifications Fire damper FKRS-EU...
Installation side 100 – 315 EI 60 S – – 100 – 200 EI 90 S – – 224 – 315 EI 90 S – 100 – 200 EI 120 S – 224 – 315 EI 120 S Fire damper FKRS-EU...
Page 90
Installation near the floor as in Ä 91 mechanism; inspection openings must remain – See table accessible Note: The fire resistance properties of depend on the nominal width and 6.10*. Fire damper FKRS-EU...
Page 91
Suspension and fixing, Ä Chapter 5.15 ‘Fixing the fire damper’ on page 255 General installation information, Ä 5.3 ‘General installation information’ on page 31 ff General information on installation with fire batt, Ä on page 38 Fire damper FKRS-EU...
Dry mortarless installation with fire batt in solid wall - multiple occupancy of an installation opening Fig. 67: Dry mortarless installation with fire batt in solid wall - multiple occupancy of an installation opening FKRS-EU Solid wall (load-bearing structural element) Mortar Solid ceiling slab (load-bearing component) Fire damper FKRS-EU...
Page 93
Mineral wool > 1000 °C, > 80 kg/m³, 6.19, 6.20 or 6.24 as an alternative Ä Table on page 94 thickness = 20 mm, panel material around the see table perimeter, leave out the actuator and release mechanism; inspection openings must remain accessible Fire damper FKRS-EU...
Page 94
opening is limited by their size (nominal width) and the overall area of the fire dampers (1.2 m ) (max- imum 10 FKRS-EU in single or double row arrange- ment) Distance to load-bearing structural elements ≥ 40 mm Fire batt systems, installation details, dis- ...
Lightweight partition wall with metal support or Mortar steel support structure, cladding on both sides Ä Coated board system with firestop coating Perimeter gap, on page 37 Distance between the fire dampers, Ä ‘Dis- tances’ on page 35 Fire damper FKRS-EU...
Page 96
Observe the maximum permissible size of the soft bulkhead! Reveal optional or according to installation detail Depending on fire resistance rating (max. 2 × 12.5 mm / 1 × 25 mm) Installation opening tolerance ± 4 mm Fire damper FKRS-EU...
Page 97
Installation Lightweight partition walls > General information Lightweight partition wall with metal support and cladding on both sides Fig. 70: Lightweight partition wall with metal support and cladding on both sides; for picture caption, see Fig. 71 Fire damper FKRS-EU...
Page 98
B Mineral wool, depending on wall construction Installation opening ☐A UW section Opening in the metal support structure ☐A1 7.1a UW section, either cut in and bent, or cut off (without reveals: ☐A = ☐A1) CW section Fire damper FKRS-EU...
Page 99
Fig. 72: Metal stud frame for a compartment wall, single and double stud system Drywall screw UW section Hexagon head screw M6 CW section Carriage bolt L ≤ 50 mm with washer and nut UA section Steel rivet Installation opening according to installation 5.14 Angle bracket details Fire damper FKRS-EU...
Page 100
(clear installation opening ≤ 475 mm) between the standard studs and reinforce the installation opening with a circum- ferential metal profile. On both sides, screw metal sections over the cladding, spaced approx. 100 mm apart. Fire damper FKRS-EU...
Installation near the floor as in Solid ceiling/solid floor – Up to EI 120 S Mineral wool, depending on wall construction Up to EI 60 S 6.11 Insulating strips (depending on wall construction) EI 30 S – EI 120 S 7.10 Reveal Fire damper FKRS-EU...
Page 102
Installation near the floor as in Mineral wool, depending on wall construction EI 30 S – 6.11 Insulating strips (depending on wall construction) EI 120 S UA section EI 30 S – EI 120 S 7.10 Reveal Fire damper FKRS-EU...
Page 103
Optional/depending on wall construction Solid ceiling/solid floor Fixing to at least two metal post profiles Mineral wool, depending on wall construction Installation near the floor as in UW section EI 120 S 7.10 Reveal Fire damper FKRS-EU...
Page 104
Up to EI 90 S for s2 = 10 – 225 mm Mineral wool, depending on wall construction Up to EI 60 S 7.10 Reveal EI 30 S 7.13 Cladding EI 30 S – EI 120 S Fire damper FKRS-EU...
Page 105
Mineral wool, depending on wall construction Fig. 74 Up to EI 120 S Note: Illustration is an example. The distance from the ceiling depends on the flexible ceiling joint, the expected ceiling subsidence and the specifications of the wall manufacturer. Fire damper FKRS-EU...
Page 106
Installation Lightweight partition walls > Mortar-based installation Mortar-based installation into a lightweight partition wall, FKRS-EU and FK2-EU, combined Fig. 78: Mortar-based installation into a lightweight partition wall, FKRS-EU and FK2-EU, combined FKRS-EU Mineral wool, depending on wall construction FK2-EU up to B × H ≤ 800 × 400 mm 7.10...
Page 107
Lightweight partition wall or fire wall, Ä on page 42 Ä 5.3 ‘General General installation information, installation information’ on page 31 ff General information on mortar-based installation, Ä ‘Mortar-based installation’ on page 37 Fire damper FKRS-EU...
Lightweight partition walls > Mortar-based installation – multiple occupancy... 5.6.3 Mortar-based installation – multiple occupancy of one installation opening Fig. 79: Mortar-based installation – multiple occupancy of one installation opening FKRS-EU Solid wall (load-bearing structural element) Mortar Solid ceiling slab (load-bearing component) Fire damper FKRS-EU...
Page 109
Lightweight partition wall with metal support or According to installation details Fig. 73 and steel support structure, cladding on both sides Fig. 74 Compartment wall or safety partition wall with up to EI 90 S metal stud, clad on both sides Fire damper FKRS-EU...
Page 110
opening is limited by their size (nominal width) and the overall area of the fire dampers (1.2 m ) (max- imum 10 FKRS-EU in single or double row arrange- ment) Distance to load-bearing structural elements ≥ 40 mm The mortar bed width must not exceed 225 mm, ...
Chamfer the outer layer of the cladding all round on both sides and completely fill the surrounding gap on both sides with joint filler to the depth of the cladding. Connection of the air duct via flexible connectors (recommendation). Fire damper FKRS-EU...
Air duct/extension piece Mineral wool, ≥ 1000 °C, ≥ 40 kg/m³ Optional Mineral wool, depending on wall construction – Up to EI 120 S 6.11 Insulating strips (depending on wall construction) UW section UA section Fire damper FKRS-EU...
Page 113
Optional Mineral wool, ≥ 1000 °C, ≥ 40 kg/m³ Up to EI 120 S Mineral wool, depending on wall construction Up to EI 60 S UW section EI 30 S – Steel support structure (box section) Fire damper FKRS-EU...
Page 114
Mineral wool, depending on wall construction Cover plate shortened by others 6.11 Insulating strips (depending on wall construction) – EI 30 S 6.13 Mineral wool strips A1, alternatively gypsum EI 30 S – EI 120 S mortar UW section Fire damper FKRS-EU...
Page 115
Dry wall screw, min. 10 mm screwed into the Installation near the floor as in metal stud frame Fixing to at least two metal post profiles Mineral wool, depending on wall construction Up to EI 120 S UW section Fire damper FKRS-EU...
Page 116
Distance between two fire dampers ≥ 200 mm (Installation of each fire damper in separate opening) General installation information, Ä 5.3 ‘General installation information’ on page 31 ff General information on installation with installation Ä kit TQ2, on page 38 Fire damper FKRS-EU...
PROMATECT ® -H, d = 10 mm tions, the additional assembly instructions for the Sheet steel duct with fire-rated cladding * installation kit WE2 and the specifications of the panel manufacturer up to EI 90 S Fire damper FKRS-EU...
Page 118
Sheet steel duct with fire-rated cladding The cladding of the air duct and the suspensions are carried out in accordance with these instruc- tions, the additional assembly instructions for the installation kit WE2 and the specifications of the panel manufacturer Fire damper FKRS-EU...
Page 119
Hilti mounting rail MQ 41 × 3 mm or equivalent compensating unevenness Hilti ® drilled plate MQZ L13 or equivalent PROMATECT ® -H, d = 10 mm Hexagon nut M10 with washer up to EI 90 S Fire damper FKRS-EU...
Page 120
® mounting rail MQ 41 × 3 mm or equivalent compensating unevenness ® Hilti drilled plate MQZ L13 or equivalent ® PROMATECT -H, d = 10 mm Hexagon nut M10 with washer up to EI 90 S Fire damper FKRS-EU...
Page 121
31 ff General information on installation with installation Ä kit WE2, on page 38 Note: For more installation details and for components to be provided by the customer, see the additional WE2 installation manual. Fire damper FKRS-EU...
Fire wall or safety partition wall with metal sup- circumferentially glued port structure, cladding on both sides Sheet steel duct Mineral wool, depending on wall construction Please check in advance whether the PAROC material is available in your market region. up to EI 60 S Fire damper FKRS-EU...
Page 123
Ä wool, on page 38 Distance between two fire dampers ≥ 400 mm Distance to load-bearing/adjacent components ≥ 200 mm Suspend the fire damper and air duct according to the mineral wool manufacturer's specifications Fire damper FKRS-EU...
Chamfer the outer layer of the cladding all round on both sides and completely fill the surrounding gap on both sides with filler to the depth of the cladding. Screw metal sections onto both sides over the cladding, spaced approx. 100 mm apart. Fire damper FKRS-EU...
EI 90 S Note: Do not make any screw connections in the hatched area. Fire damper FKRS-EU...
Page 126
Solid ceiling slab 6.13 Mineral wool strips A1, filler as an alternative 6.27 Z brackets both sides, 90 × 140 × 1.5 mm up to EI 90 S Note: Do not make any screw connections in the hatched area. Fire damper FKRS-EU...
Page 127
EI 90 S Note: Do not make any screw connections in the hatched area. Fire damper FKRS-EU...
Page 128
Solid ceiling slab 6.13 Mineral wool strips A1, filler as an alternative 6.27 Z brackets both sides, 90 × 140 × 1.5 mm up to EI 90 S Note: Do not make any screw connections in the hatched area. Fire damper FKRS-EU...
Page 129
Solid ceiling slab CW section 7.22 Ceiling joint section up to EI 90 S Note: Do not make any screw connections in the hatched area. Fire damper FKRS-EU...
Page 130
Solid ceiling slab CW section 7.22 Ceiling joint section up to EI 90 S Note: Do not make any screw connections in the hatched area. Fire damper FKRS-EU...
Page 131
(≤ 5 mm) above the installa- tion kit to even out ceiling unevenness. Note: Installation is carried out in accordance with the additional assembly instructions for flexible ceiling joint supplied. Installation details for installation in compartment walls on request. Fire damper FKRS-EU...
Page 132
Mineral wool ≥ 1000 °C, ≥ 100 kg/m Compartment wall or safety partition wall with 8.37 Steel bracket, supplied by customer metal stud, clad on both sides up to EI 90 S Fire damper FKRS-EU...
Page 133
If necessary, provide mineral fibre strips A1, alterna- tively levelling material (≤ 5 mm) above the installa- tion kit to even out ceiling unevenness. Note: Installation is carried out in accordance with the additional assembly instructions for flexible ceiling joint supplied. Fire damper FKRS-EU...
7.13 Cladding release mechanism; inspection openings must 7.14 Reinforcing board of the same material as the remain accessible wall 6.19, 6.20 or 6.24 as an alternative Installation near the floor as in Ä 135 – See table Fire damper FKRS-EU...
Page 135
– 224 – 315 EI 90 S – 100 – 200 EI 120 S – 224 – 315 EI 120 S 100 – 315 EI 60 S – – 100 – 315 EI 30 S – – Fire damper FKRS-EU...
Page 136
Fig. 102: Dry mortarless installation into a lightweight partition wall, with a fire batt, flange to flange, illustration shows side by side installation (applies also to installation of dampers on top of each other) FKRS-EU 6.20 Pipe collar (can be ordered separately) Fire damper FKRS-EU...
Page 137
EI 30 S – – 10 – 600 * For a distance of 10 mm, mineral wool ≥ 1000 °C, ≥ 80 kg/m with d = 10 mm and width nominal width/2 shall be provided between the fire dampers. Fire damper FKRS-EU...
Page 138
Compartment wall or safety partition wall with required metal stud, clad on both sides Installation near the floor as in Solid ceiling/solid floor – F120 Mineral wool, depending on wall construction – 6.11 Insulation strips F 30 – F 120 Fire damper FKRS-EU...
Page 139
Suspension and fixing, Ä Chapter 5.15 ‘Fixing the fire damper’ on page 255 General installation information, Ä 5.3 ‘General installation information’ on page 31 ff General information on installation with fire batt, Ä on page 38 Fire damper FKRS-EU...
Dry mortarless installation with fire batt in lightweight partition wall – Multiple occupancy of an installation opening Fig. 104: Dry mortarless installation with fire batt in lightweight partition wall – Multiple occupancy of an installation opening FKRS-EU Solid wall (load-bearing structural element) Mortar Solid ceiling slab (load-bearing component) Fire damper FKRS-EU...
Page 141
6.19, 6.20 or 6.24 as an alternative 6.19 Mineral wool > 1000 °C, > 80 kg/m³, see table Ä Table on page 142 thickness = 20 mm, leave out the actuator and release mechanism; inspection openings must remain accessible Fire damper FKRS-EU...
Page 142
The number of fire dampers in an installation opening is limited by their size (nominal width) and the overall area of the fire dampers (1.2 m ) (max- imum 10 FKRS-EU in single or double row arrange- ment) Fire damper FKRS-EU...
☐A = ÆDN + max. 1200 Dry mortarless installation 40 – 600 10/40 – 600 with coated board system Observe the maximum permissible size of the coated board system! Depending on fire resistance rating Installation opening tolerance ± 4 mm Fire damper FKRS-EU...
Page 144
Mineral wool, depending on wall construction min. 60 × 80 mm Timber stud, min. 60 × 80 mm ☐A Clear installation opening 7.11 Reveals, double layer, with staggered joints Opening in timber support structure, ☐A1 ☐A1 = ☐A + (4 × reveals) Fire damper FKRS-EU...
Page 145
Clear installation opening ☐A Opening in the half-timbered construction, ☐A1 ☐A1 = ☐A + (4 × reveals) Additional requirements: lightweight partition walls with timber stud/half-timbered construction Timber stud wall/half-timbered construction, Ä on page 43 Fire damper FKRS-EU...
60 × 60 mm with F60 Up to EI 60 S 7.10 Reveals (fire-resistant) EI 30 S 7.11 Reveals, double layer, with staggered joints EI 30 to EI 120 S 7.12 Reveals, wood sheet, at least 600 kg/³ Fire damper FKRS-EU...
Page 147
Reveals, double layer, with staggered joints Up to EI 90 S for s2 = 10 – 225 mm 7.12 Reveals, wood sheet, at least 600 kg/³ Up to EI 60 S 7.13 Cladding EI 30 S EI 30 to EI 120 S Fire damper FKRS-EU...
Page 148
Lightweight partition walls with timber support ... > Mortar-based installation Mortar-based installation into a lightweight partition wall with timber support structure, FKRS-EU and FK2- EU, combined Fig. 111: Mortar-based installation into a lightweight partition wall with timber support structure, FKRS-EU and FK2-EU, combined FKRS-EU Timber stud, min.
Page 149
≥ 1000 °C, ≥ 50 kg/m³, or masonry, aerated con- EI 30 S crete, lightweight concrete, reinforced concrete or EI 30 to EI 120 S puddle clay) Half-timbered construction 7.11 Reveal, fire-resistant, double layer with stag- gered joints Fire damper FKRS-EU...
Page 150
Up to EI 90 S for s2 = 10 – 225 mm crete, lightweight concrete, reinforced concrete or EI 30 S puddle clay) EI 30 to EI 120 S Half-timbered construction 7.11 Reveal, fire-resistant, double layer with stag- gered joints Fire damper FKRS-EU...
Page 151
Lightweight partition walls with timber support ... > Mortar-based installation Mortar-based installation into a lightweight partition wall with half-timbered construction, FKRS-EU and FK2-EU, combined Fig. 114: Mortar-based installation into a lightweight partition wall with half-timbered construction, FKRS-EU and FK2-EU, combined FKRS-EU Infill (cavities completely filled with mineral wool FK2-EU up to B ×...
Page 152
Timber stud wall/half-timbered construction, Ä on page 43 Ä 5.3 ‘General General installation information, installation information’ on page 31 ff General information on mortar-based installation, Ä ‘Mortar-based installation’ on page 37 Fire damper FKRS-EU...
Mortar-based installation into a lightweight partition wall with timber support structure Fig. 115: Mortar-based installation in lightweight partition wall with timber stud – Multiple occupancy of an installation opening FKRS-EU Solid wall (load-bearing structural element) Mortar Solid ceiling slab (load-bearing component) Fire damper FKRS-EU...
Page 154
Reveal, fire-resistant, double layer with stag- Timber stud wall (including timber panel construc- gered joints tion), clad on both sides 7.17 Framed openings, timber stud/noggings Mineral wool, depending on wall construction min. 60 × 80 mm up to EI 90 S Fire damper FKRS-EU...
Page 155
Half-timbered wall, clad on both sides gered joints Infill (cavities completely filled with mineral wool up to EI 90 S ≥ 1000 °C, ≥ 50 kg/m³, or masonry, aerated con- crete, lightweight concrete, reinforced concrete or puddle clay) Fire damper FKRS-EU...
Page 156
opening is limited by their size (nominal width) and the overall area of the fire dampers (1.2 m ) (max- imum 10 FKRS-EU in single or double row arrange- ment) Distance to load-bearing structural elements ≥ 40 mm...
Timber stud, min. 60 × 80 mm or EI 30 S min. 60 × 60 mm with F60 EI 30 to EI 120 S 7.10 Reveals (fire-resistant) 7.11 Reveals, double layer, with staggered joints 7.12 Reveals, wood sheet, at least 600 kg/³ Fire damper FKRS-EU...
Page 158
Distance between two fire dampers ≥ 200 mm (Installation of each fire damper in separate opening) Ä 5.3 ‘General General installation information, installation information’ on page 31 ff General information on installation with installation Ä kit TQ2, on page 38 Fire damper FKRS-EU...
Mineral wool, depending on wall construction Sheet steel duct 6.29* Mineral wool PAROC HVAC Fire Mat 80BLC Please check in advance whether the PAROC (80 kg/m³) material is available in your market region. Up to EI 60 S Fire damper FKRS-EU...
Page 160
Please check in advance whether the PAROC or puddle clay) material is available in your market region. 6.29* Mineral wool PAROC Hvac Fire Mat BlackCoat Up to EI 60 S (≥ 80 kg/m Fire damper FKRS-EU...
Page 161
(≥ 80 kg/m material is available in your market region. 6.30* Reinforcing board made of mineral wool Up to EI 60 S PAROC HVAC Fire Mat BlackCoat (≥ 80 kg/m circumferentially glued Timber stud, min. 60 × 80 mm Fire damper FKRS-EU...
Page 162
Ä wool, on page 38 Distance between two fire dampers ≥ 400 mm Distance to load-bearing/adjacent components ≥ 200 mm Suspend the fire damper and air duct according to the mineral wool manufacturer's specifications Fire damper FKRS-EU...
The following applies in Germany: For notes on Ä the use of elastomeric foams ‘Additional provision for use in Germany:’ on page 8 . Timber stud, min. 60 × 80 mm or min. 60 × 60 mm with F60 Fire damper FKRS-EU...
Page 164
100 – 200 EI 120 S – 224 – 315 EI 120 S 100 – 315 EI 60 S – – 100 – 315 EI 30 S – – 100 – 315 EI 30 S – – Fire damper FKRS-EU...
Page 165
Installation Lightweight partition walls with timber support ... > Dry mortarless installation with fire batt Dry mortarless installation into a lightweight partition wall, with a fire batt, with timber support structure, "flange to flange Fire damper FKRS-EU...
Page 166
(applies also to installation of dampers on top of each other) FKRS-EU 7.10 Reveals (fire-resistant) Coated board system with firestop coating 7.11 Reveals, double layer, with staggered joints Fire damper FKRS-EU...
Page 167
EI 30 S – – 10 – 600 * For a distance of 10 mm, mineral wool ≥ 1000 °C, ≥ 80 kg/m with d = 10 mm and width nominal width/2 shall be provided between the fire dampers. Fire damper FKRS-EU...
Page 168
6.20 Pipe collar (can be ordered separately) 6.24 Elastomeric foam (flame-resistant, non-dripping) The following applies in Germany: For notes on Ä the use of elastomeric foams ‘Additional provision for use in Germany:’ on page 8 . Fire damper FKRS-EU...
Page 169
Installation side 100 – 200 EI 90 S – – 224 – 315 EI 90 S – 100 – 200 EI 120 S – 224 – 315 EI 120 S 100 – 315 EI 30 S – – Fire damper FKRS-EU...
Page 170
(applies also to installation of dampers on top of each other) FKRS-EU 6.24 Elastomeric foam (flame-resistant, non-drip- Coated board system with firestop coating ping) Half-timbered wall, clad on both sides Solid ceiling/solid floor Fire damper FKRS-EU...
Page 171
Ä Chapter 5.15 ‘Fixing the Suspension and fixing, fire damper’ on page 255 Ä 5.3 ‘General General installation information, installation information’ on page 31 ff General information on installation with fire batt, Ä on page 38 Fire damper FKRS-EU...
Dry mortarless installation into a lightweight partition wall with timber support structure, with a fire batt Fig. 128: Dry mortarless installation with fire batt in lightweight partition wall with timber studs – Multiple occupancy of an installation opening FKRS-EU Solid wall (load-bearing structural element) Mortar Solid ceiling slab (load-bearing component) Fire damper FKRS-EU...
Page 173
Framed openings, wooden beams 6.20 Pipe collar (can be ordered separately) min. 60 × 80 mm or min. 60 × 60 mm for F60 6.19, 6.20 or 6.24 as an alternative Ä Table on page 174 see table Fire damper FKRS-EU...
Page 174
EI 30 S – – 10 – 600 * For a distance of 10 mm, mineral wool ≥ 1000 °C, ≥ 80 kg/m with d = 10 mm and width nominal width/2 shall be provided between the fire dampers. Fire damper FKRS-EU...
Page 175
= 20 mm, leave out the actuator and wall release mechanism; inspection openings must 6.19, 6.20 or 6.24 as an alternative Ä Table on page 176 remain accessible see table 6.20 Pipe collar (can be ordered separately) Fire damper FKRS-EU...
Page 176
opening is limited by their size (nominal width) and the overall area of the fire dampers (1.2 m ) (max- imum 10 FKRS-EU in single or double row arrange- ment) Distance to load-bearing structural elements ≥ 40 mm...
≥ 200 with coated board system Observe the maximum permissible size of the coated board system! Installation opening tolerance ± 4 mm Additional requirements: solid wood walls Ä Solid wood wall or CLT wall, on page 43 Fire damper FKRS-EU...
Reinforcing board of the same material 3.11 Solid wood wall/CLT wall (required if W < 100 mm) Solid ceiling slab/solid floor Optional 5.13 Wood screw or pin Installation near the floor as in 7.10 Trim panel – Up to EI 90 S Fire damper FKRS-EU...
Page 179
Ä Solid wood wall or CLT wall, on page 43 General installation information, Ä 5.3 ‘General installation information’ on page 31 ff General information on mortar-based installation, Ä ‘Mortar-based installation’ on page 37 Fire damper FKRS-EU...
≥ 200 mm distance between two fire dampers in separate installation openings Ä 5.3 ‘General General installation information, installation information’ on page 31 ff General information on installation with installation Ä kit TQ2, on page 38 Fire damper FKRS-EU...
Solid wood wall/cross-laminated timber wall circumferentially glued 6.29* Mineral wool PAROC Hvac Fire Mat BlackCoat Sheet steel duct (≥ 80 kg/m Please check in advance whether the PAROC material is available in your market region. Up to EI 60 S Fire damper FKRS-EU...
Page 182
Ä wool, on page 38 Distance between two fire dampers ≥ 400 mm Distance to load-bearing/adjacent components ≥ 200 mm Suspend the fire damper and air duct according to the mineral wool manufacturer's specifications Fire damper FKRS-EU...
Page 183
Reinforcing board of the same material as the mechanism; inspection openings must remain wall accessible 6.19, 6.20 or 6.24 as an alternative 6.20 Pipe collar (to be ordered separately) Installation near the floor as in – Up to EI 90 S Fire damper FKRS-EU...
Page 184
≥ 200 mm distance between two fire dampers in separate installation openings Ä 5.3 ‘General General installation information, installation information’ on page 31 ff General information on installation with fire batt, Ä on page 38 Fire damper FKRS-EU...
≥ 200 with TQ2 ☐A = ÆDN + max. 1200 Dry mortarless installation 40 – 600 ≥ 200 with coated board system Observe the maximum permissible size of the coated board system! Installation opening tolerance ± 4 mm Fire damper FKRS-EU...
Page 186
UW section, either cut in and bent, or cut off Installation near the ceiling analogous to B CW section Mortar-based installation only 7.10 Reveals, according to installation details Clear installation opening ☐A ☐A1 Opening in the metal support structure (without reveals: ☐A = ☐A1) Fire damper FKRS-EU...
Page 187
(clear installation opening ≤ 475 mm) between two standard vertical studs, attach the reinforcing board and brace the instal- lation opening with a circumferential metal sec- tion. Screw metal sections over the cladding, spaced approx. 100 mm apart. Fire damper FKRS-EU...
Installation near the floor as in UW section – up to EI 90 S Steel support structure (box section) EI 30 S – 7.10 Reveal Up to EI 60 S EI 30 S – EI 90 S Fire damper FKRS-EU...
Page 189
Cladding, single-layer, inside UW section Drywall screw 7.14 Reinforcing board of the same material as the Mineral wool, depending on wall construction wall UW section Optional Steel support structure (box section) – up to EI 90 S Fire damper FKRS-EU...
Page 190
Solid ceiling/solid floor Air duct/extension piece Drywall screw Optional 5.21 Screw/dowel Installation near the floor as in UW section EI 30 S – Metal section according to wall manufacturer EI 30 S – EI 90 S Fire damper FKRS-EU...
Page 191
The number of fire dampers in an installation opening is limited by their size (B × H for FK2-EU and/or Ænominal width for FKRS-EU) and the overall area of the fire dampers (1.2 m Other arrangements (side by side or on top of each other) are possible. Details are available upon request.
Page 192
Shaft wall, Ä on page 43 Ä 5.3 ‘General General installation information, installation information’ on page 31 ff General information on mortar-based installation, Ä ‘Mortar-based installation’ on page 37 Fire damper FKRS-EU...
7.13 Cladding Shaft wall with metal stud, clad on one side 7.13.1 Cladding, single-layer, inside UW section 3.10 Wall without adequate fire resistance rating 7.14 Reinforcing board of the same material as the Solid ceiling/solid floor wall Fire damper FKRS-EU...
Page 194
Distance between two fire dampers ≥ 200 mm (Installation of each fire damper in separate opening) Ä 5.3 ‘General General installation information, installation information’ on page 31 ff General information on installation with installation kit TQ2, Ä on page 38 Fire damper FKRS-EU...
Create Promatect strips (8.3). Push the fire damper into the wall opening and fix it with threaded rods (5.4) and Promatect strips (8.3). Note: Tighten the nuts hand-tight to approx. 5 Nm for fastening. Apply fire-resistant cladding (7.19). Fire damper FKRS-EU...
≥ 200 mm distance between two fire dampers in separate installation openings General installation information, Ä 5.3 ‘General installation information’ on page 31 ff General information on installation with fire batt, Ä on page 38 Fire damper FKRS-EU...
Installation type Installation opening [mm] Distance [mm] ÆDN + max. 450 Mortar-based installation ≤ 225 ≥ 200 Dry mortarless installation ☐A = ÆDN + 110 central installation ≥ 200 with TQ2 Installation opening tolerance ± 4 mm Fire damper FKRS-EU...
Page 198
Fig. 149: Shaft wall without metal support structure and cladding on one side Shaft wall Metal section/steel bracket according to wall Shaft wall, installation near the floor manufacturer Shaft wall, installation near the ceiling 7.10 Reveals, according to installation details Solid ceiling slab / solid floor 7.13 Cladding Fire damper FKRS-EU...
Page 199
Fig. 149 After cladding the wall, create a square wall opening with reinforcing strips and brace it with a perimeter metal section. Screw metal sections over the clad- ding, spaced approx. 100 mm apart. Fire damper FKRS-EU...
Distance between two fire dampers ≥ 200 mm (Installation of each fire damper in separate opening) General installation information, Ä 5.3 ‘General installation information’ on page 31 ff General information on mortar-based installation, Ä ‘Mortar-based installation’ on page 37 Fire damper FKRS-EU...
≥ 55 mm distance between the fire damper and load-bearing components General installation information, Ä 5.3 ‘General installation information’ on page 31 ff General information on installation with installation Ä kit TQ2, on page 38 Fire damper FKRS-EU...
Create Promatect strips (8.3). Push the fire damper into the wall opening and fix it with threaded rods (5.4) and Promatect strips (8.3). Note: Tighten the nuts hand-tight to approx. 5 Nm for fastening. Apply fire-resistant cladding (7.19). Fire damper FKRS-EU...
Observe the maximum permissible size of the coated board system! Distance between the installation blocks Installation into separate installation openings x = 45 mm up to EI 120 S / x = 10 mm up to EI 90 S Fire damper FKRS-EU...
Page 204
(by customer). Compensation measures, especially with regard to large installation openings (such as for multiple installation), must be determined on a case-to-case basis (by customer). Fire damper FKRS-EU...
Fig. 154: Mortar-based installation into a solid ceiling slab, suspended or upright FKRS-EU Up to EI 120 S Mortar Up to EI 90 S Reinforced concrete Up to EI 120 S Solid ceiling slab (thickness increased at Up to EI 90 S Fire damper FKRS-EU...
Page 206
Fig. 155: Mortar-based installation into a solid ceiling slab with screed and footfall sound insulation, suspended or upright FKRS-EU 6.22 Screed Mortar 6.23 Footstep sound insulation Reinforced concrete – Up to EI 120 S Solid ceiling slab Fire damper FKRS-EU...
Page 207
Fig. 156: Mortar-based installation into solid ceiling slab, "flange to flange", upright and suspended (also applicable for blending into the screed according to Fig. 154 ) FKRS-EU 45 mm up to EI 120 S Mortar 10 mm up to EI 90 S – Up to EI 120 S Fire damper FKRS-EU...
Page 208
Installation Solid ceiling slabs > Mortar-based installation Solid ceiling slab (thickness increased at Fire damper FKRS-EU...
Page 209
The number of fire dampers in an installation opening is limited by their size (B × H for FK2-EU and/or Ænominal width for FKRS-EU) and the overall area of the fire dampers (1.2 m Other arrangements (side by side or on top of each other) are possible. Details are available upon request.
Page 210
Ä ‘Mortar-based installation’ on page 37 Note: Structural and fire resistance properties of the ceiling construction, including the attachment to the con- crete or any required reinforcement, have to be eval- uated and ensured by others. Fire damper FKRS-EU...
Solid ceiling slabs > Mortar-based installation – multiple occupancy... 5.11.3 Mortar-based installation – multiple occupancy of one installation opening Fig. 158: Mortar-based installation – multiple occupancy of one installation opening FKRS-EU 2.1 Mortar 3.1 Solid wall (load-bearing structural element) Fire damper FKRS-EU...
Page 212
opening is limited by their size (nominal width) and the overall area of the fire dampers (1.2 m ) (max- imum 10 FKRS-EU in single or double row arrange- ment) Distance to load-bearing structural elements ≥ 40 mm...
Fig. 160: Mortar-based installation with concrete base into a solid ceiling slab, upright Steel fabric, Æ ≥ 8 mm, mesh aperture 150 mm, FKRS-EU 5.22 Concrete base or equivalent, for number of fixing points: 4 Solid ceiling slab Air duct/extension piece Up to EI 120 S Fire damper FKRS-EU...
Page 214
Mortar-based installation with concrete base into a solid ceiling slab, upright, combined, FKRS-EU and FK2-EU Fig. 161: Mortar-based installation with concrete base into a solid ceiling slab, upright, combined, FKRS-EU and FK2-EU Steel fabric, Æ ≥ 8 mm, mesh aperture 150 mm, FKRS-EU 5.22...
Page 215
Concrete bases with H ≤ 150 mm do not require reinforcement Ä 5.3 ‘General General installation information, installation information’ on page 31 ff Fire damper FKRS-EU...
Solid ceiling slabs > Mortar-based installation into a concrete base... 5.11.5 Mortar-based installation into a concrete base – multiple installation opening into one installation opening Fig. 162: Mortar-based installation – multiple occupancy of one installation opening FKRS-EU 2.1 Mortar 3.1 Solid wall (load-bearing structural element) Fire damper FKRS-EU...
Page 217
Fig. 163: Mortar-based installation with concrete base into a solid ceiling slab, upright, multiple installation Steel fabric, Æ ≥ 8 mm, mesh aperture 150 mm, FKRS-EU 5.22 Concrete base or equivalent, for number of fixing points see Ä 215 Solid ceiling slab table Air duct/extension piece up to EI 90 S Fire damper FKRS-EU...
Page 218
opening is limited by their size (nominal width) and the overall area of the fire dampers (1.2 m ) (max- imum 10 FKRS-EU in single or double row arrange- ment) Distance to load-bearing structural elements ≥ 40 mm Minimum number of fixing points in the ceiling slab ...
General information on mortar-based installation, Ä ‘Mortar-based installation’ on page 37 After creating the installation opening, the adjacent cavities must be partially sealed (to the thickness of the ceiling) by at least 100 mm all round. Fire damper FKRS-EU...
General information on mortar-based installation, Ä ‘Mortar-based installation’ on page 37 After creating the installation opening, the adjacent cavities must be partially sealed (to the thickness of the ceiling) by at least 100 mm all round. Fire damper FKRS-EU...
Concrete bases with H ≤ 150 mm do not require reinforcement ≥ 40 mm distance between the fire damper and load-bearing components ≥ 45 mm distance between two fire dampers Ä 5.3 ‘General General installation information, installation information’ on page 31 ff Fire damper FKRS-EU...
load-bearing components ≥ 45 mm distance between two fire dampers Ä 5.3 ‘General General installation information, installation information’ on page 31 ff General information on mortar-based installation, Ä ‘Mortar-based installation’ on page 37 Fire damper FKRS-EU...
Ä Wooden beam ceiling, on page 44 ≥ 40 mm distance between the fire damper and load-bearing components ≥ 45 mm distance between two fire dampers Fire damper FKRS-EU...
Ä Solid wood ceiling, on page 44 ≥ 40 mm distance between the fire damper and load-bearing components ≥ 45 mm distance between two fire dampers Fire damper FKRS-EU...
(Cadolto system) Ä Modular ceiling, (Cadolto system), on page 45 ≥ 40 mm distance between the fire damper and load-bearing components ≥ 45 mm distance between two fire dampers Fire damper FKRS-EU...
Aluminium bracket ≥ 130 × 80 × 6 mm Air duct/extension piece Mineral wool, A1, ≥ 1000 °C, 140 mm thick Up to EI 90 S 6.23 Footfall sound insulation Note on lightweight ceiling: Ceiling construction according to ADK module room specifications. Fire damper FKRS-EU...
Page 227
(7.19) and screw angle bracket to the steel section. Set fire damper in concrete [1] or pour concrete base [2] and then mortar the gap between fire damper and concrete base. Provide reinforcement according to structural requirements. Fire damper FKRS-EU...
Fig. 172: Dry mortarless installation with installation block ER in solid ceiling slab, upright and suspended FKRS-EU Wallplug with fire protection suitability certifi- 2.18 Installation block ER with cover plate cate, alternatively push through installation Solid ceiling slab Up to EI 90 S – Fire damper FKRS-EU...
Page 229
Fix the cover plate with four threaded rods (push through installation) or with at least four M6 screws. For solid walls and solid ceiling slabs, suitable steel wall plugs with building inspectorate approval that have been adapted to the respective building material must be used. Fire damper FKRS-EU...
Threaded rod as push-through installation with panel, thickness ≥ 12.5 mm) washers and nuts or wall plug with fire safety suit- Extension piece/duct with , shortened, flush ability certificate with the ceiling Up to EI 90 S Up to EI 60 S Fire damper FKRS-EU...
Page 231
Note: Tighten the nuts hand-tight to approx. 5 Nm for fastening. : Fire protection cladding (7.19) with the installa- tion kit WA2 at a distance of ≤ 100 mm. Fire damper FKRS-EU...
MQZ L13 or equivalent bolts (supplied by the customer) with suitability Hexagon nut M10 with washer certificate that are suitable for the wall or ceiling up to EI 90 S can also be used; push-through installation is also possible Fire damper FKRS-EU...
Page 233
The cladding of the air duct and the suspensions are carried out in accordance with these instruc- tions, the additional assembly instructions for the installation kit WE2 and the specifications of the panel manufacturer Suspension system (by others) consisting of: Fire damper FKRS-EU...
Page 234
MQ 41 × 3 mm or equivalent 5.17 HUS-6 anchor Æ 6 mm × 80 mm ® Hilti ® Hilti drilled plate MQZ L13 or equivalent Hexagon nut M10 with washer up to EI 90 S Fire damper FKRS-EU...
Page 235
The cladding of the air duct and the suspensions are carried out in accordance with these instruc- tions, the additional assembly instructions for the installation kit WE2 and the specifications of the panel manufacturer up to EI 90 S Fire damper FKRS-EU...
Page 236
31 ff General information on installation with installation Ä kit WE2, on page 38 Note: For more installation details and for components to be provided by the customer, see the additional WE2 installation manual. Fire damper FKRS-EU...
+ 10 – 40 mm. Centred installation of the fire damper in the con- crete base with reinforcement. For installation in Germany, please note: Use in Fireshield with a combined penetration seal requires individual type-approval. Fire damper FKRS-EU...
Solid ceiling slab Fire resistance rating Coating Detail [mm] Operating side Installation side 100 – 315 EI 90 S – 100 – 315 EI 120 S Fire damper FKRS-EU...
Page 239
Solid ceiling slab Fire resistance rating Coating Detail [mm] Operating side Installation side 100 – 315 EI 90 S – 100 – 315 EI 120 S Fire damper FKRS-EU...
Page 240
Ä Chapter 5.15 ‘Fixing the Suspension and fixing, fire damper’ on page 255 Ä 5.3 ‘General General installation information, installation information’ on page 31 ff General information on installation with fire batt, Ä on page 38 Fire damper FKRS-EU...
≥ 200 mm distance between two fire dampers in separate installation openings Ä 5.3 ‘General General installation information, installation information’ on page 31 ff General information on mortar-based installation, Ä ‘Mortar-based installation’ on page 37 Fire damper FKRS-EU...
≥ 200 mm distance between two fire dampers in separate installation openings General installation information, Ä 5.3 ‘General installation information’ on page 31 ff General information on installation with installation Ä kit TQ2, on page 38 Fire damper FKRS-EU...
Acrylic fire protection sealant Solid wood ceiling up to EI 90 S 5.3e Chipboard screw min. 5 × 70 mm (on site) Installation opening Nominal size [mm] ÆDN [mm] Width [mm] Height [mm] Installation opening tolerance ±5 mm Fire damper FKRS-EU...
Page 244
5 × 120 mm (5.3g, provided by customer) Seal the gap between the ceiling opening and the TS2 twin installation kit on both sides with acrylic fire protection sealant (8.21, e.g. HILTI CFS-S ACR, supplied by customer). Fire damper FKRS-EU...
≥ 200 mm distance between two fire dampers in separate installation openings Ä 5.3 ‘General General installation information, installation information’ on page 31 ff General information on mortar-based installation, Ä ‘Mortar-based installation’ on page 37 Fire damper FKRS-EU...
≥ 200 mm distance between two fire dampers in separate installation openings Ä 5.3 ‘General General installation information, installation information’ on page 31 ff General information on installation with installation Ä kit TQ2, on page 38 Fire damper FKRS-EU...
(reduce distances between wooden beams to the up to EI 90 S size of the installation opening) Up to EI 60 S 7.17 Framed openings, wooden beam/glued lami- EI 30 S nated timber min. 100 × 80 mm Fire damper FKRS-EU...
Page 248
Wood sheet, at least 600 kg/m³ up to EI 90 S 7.16 Wooden beam/gluelam at least 100 × 80 mm Up to EI 60 S (reduce distances between wooden beams to the EI 30 S size of the installation opening) Fire damper FKRS-EU...
Page 249
(7.28) at intervals of approx. 100 mm. Note: Structural and fire resistance properties of the ceiling construction, including the attachment to the con- crete or any required reinforcement, have to be eval- uated and ensured by others. Fire damper FKRS-EU...
Reveal, same construction as 7.19 nated timber min. 100 × 80 mm 7.15 Wood sheet, at least 600 kg/m³ 7.19 Fire protection cladding, e.g. GKF, (ceiling- dependent) up to EI 90 S Up to EI 60 S EI 30 S Fire damper FKRS-EU...
Page 251
Reveal, same construction as 7.19 nated timber min. 100 × 80 mm 7.15 Wood sheet, at least 600 kg/m³ 7.19 Fire protection cladding, e.g. GKF, (ceiling- dependent) up to EI 90 S Up to EI 60 S EI 30 S Fire damper FKRS-EU...
Page 252
The mounting screws must be selected so that they reach at least 50 mm into the wooden beams. With decoupled cladding and suspended installa- tion, the installation kit must be connected to the ceiling construction in a load-bearing manner. Fire damper FKRS-EU...
6.26 Cement plaster* Air duct/extension piece 6.28 Ceiling filling* The illustration is an example; other ceiling con- 7.10 Reveals (fire-rated plasterboard or wood sheet) structions may be possible depending on make and local conditions EI 30 S Fire damper FKRS-EU...
Page 254
Ä ‘Mortar-based installation’ on page 37 Note: Structural and fire resistance properties of the ceiling construction, including the attachment to the con- crete or any required reinforcement, have to be eval- uated and ensured by others. Fire damper FKRS-EU...
16 air transfer damper (FD)’ on page 18 Ä Chapter 2.6 ‘FKRS-EU as an air transfer damper (MFD)’ on page 19 . In addition to the fixing systems described in this manual, you may also use fixing systems that have been approved by accredited testing institutes.
> 1.5 m require fire- resistant insulation. The FKRS-EU is attached to the wall via the soft bulkhead. The connected air ducts must be fastened independently of the fire damper. The pipes may be connected on both sides with or without flexible connectors.
Page 257
DANGER! Danger of falling off! Do not step onto the fire batt! The fire batt cannot carry any loads. Adequate means, e.g. a permanent barrier, must be installed to prevent people from stepping onto the fire batt. Fire damper FKRS-EU...
Page 258
Anchor bolt Hilti ® HUS-6 or equivalent 5.19 L-bracket according to EN 10056-1, 20 × 20 × 3 mm galvanised, painted or similar. 5.20 L-bracket according to EN 10056-1, 35 × 35 × 4 mm galvanised, painted or similar. Fire damper FKRS-EU...
Installation Fixing the fire damper > Fire damper remote from walls and ceilings 5.15.4 Fire damper remote from walls and ceilings Fig. 197: FKRS-EU in a cladded duct FKRS-EU Threaded rod M10 Solid wall Hilti ® mounting rail MQ 41 × 3 mm or equivalent Lightweight partition wall with metal support struc- ®...
This ensures quick structure (wall or ceiling slab). They must not be and easy connection to the TROX AS-i bus system. fixed to the fire damper. For connection to the terminals, shorten the connecting cable.
Based on this, additional meas- ures such as cleaning in the event of heavy soiling (e.g. dust contamination in extract air systems) can maintain the functionality of the system. Fire damper FKRS-EU...
The handle (1.6) swivels automatically in the direction of the arrow. The damper blade is closed and the handle (1.6) shows that the damper blade is closed. Fig. 205: Damper blade position indicator Damper blade is closed Damper blade is open Fire damper FKRS-EU...
Fig. 207: Damper blade position indicator Release the button (1). Damper blade is closed ð Power is supplied again, and the damper Damper blade is open blade opens. Check if the damper blade is OPEN, check run- time. Fire damper FKRS-EU...
Page 265
Turn the crank handle in the direction of the arrow (2) until just before the travel stop. Then quickly rotate the crank handle by approx. 90° towards the 'lock' position. ð The actuator locks, the damper blade remains in the OPEN position. Remove the crank handle. Fire damper FKRS-EU...
Release the button (1). ð Power is supplied again, and the damper blade opens. Fig. 212: Damper blade position indicator Check if the damper blade is OPEN, check run Damper blade is closed time. Damper blade is open Fire damper FKRS-EU...
Page 267
Turn the crank handle in the direction of the arrow (2) to just short of the travel stop and hold it. Set the interlock (3) to "Lock " ð The damper blade remains in the OPEN posi- tion. Remove the crank handle. Fire damper FKRS-EU...
CLOSED fire dampers Fire dampers which close while the ventilation system is running must be inspected before they are opened again in order to ensure their correct function Ä ‘Inspection’ on page 269 . Fire damper FKRS-EU...
262 . by expert qualified personnel or the manufacturer. Only original replacement parts are to be used. A functional Ä 8.1 ‘General test is required after any repair work information’ on page 262 . Fire damper FKRS-EU...
While doing so, slightly press down the fasten with screws (10.17). tab (1.6) of the handle. ð Carry out functional test. Fig. 217: Replacing the fusible link 10.15 Fusible link holder 10.18 Fusible link 10.20 Spring Fire damper FKRS-EU...
Function OK Fire damper closes when triggered manually or when smoke is detected Fire damper opens after reset – Determine and eliminate the cause of the fault – Repair or replace duct smoke detector Fire damper FKRS-EU...
Page 272
(remote controlled). The system owner can then set the intervals for local tests. C = as required Item to be checked Required condition – Remedial action if necessary Fire damper FKRS-EU...
In case of doubt, contact your local authorities or a specialist disposal company. Note: The fire damper has to be dismantled for dis- posal. If no disposal or return agreements with TROX GmbH are in place, we recommend disposing of the materials as follows: Fire damper FKRS-EU...
Page 274
Decommissioning, removal and disposal Disposal Disposal information Fig. 219: FKRS-EU with fusible link or spring return actuator Pos. Component Material/waste code Type of disposal Casing Metal Scrap metal recycling. Damper blade EAK 17 09 04 – mixed con- Take such materials to construction waste struction and demolition waste and inert waste landfills (class 1 landfill).
Installation kit WA / WA2 3.12 Sandwich panel wall Installation kit WE / WE2 3.13 Facing formwork with metal stud Installation kit WV 3.14 Solid wall made of gypsum wallboard Installation kit E1 / E2 / E3 / EW Fire damper FKRS-EU...
Page 276
Screw or rivet, galvanised steel (see respec- construction, mineral wool filling if required tive installation detail) Mineral wool (tamping wool), loose, ≥ 150 Dowels with suitability certificate for fire kg/m³, e.g. Rockwool RL resistance Coated board system Metal anchor M8 – M12 Fire damper FKRS-EU...
Page 277
6.32 Fire-rated plasterboard strip d = 20 mm 7.13a Cladding, fire-resistant 6.33 Fire-rated plasterboard strip d = 15 mm 7.13b Cladding wooden composite board, min. 600 6.34 Gyproc FireLine 15 mm kg/m³ 6.35 Gyproc CoreBoard 19 mm Fire damper FKRS-EU...
Page 278
Steel bracket Hilti mounting rail MQ 41 × 3, or equivalent 8.38 OWA adhesive Hilti perforated plate MQZ L13, or equivalent 8.39 Support, consisting of spiral duct and 2 × flanged collars Hilti perforated strips LB26, or equivalent Fire damper FKRS-EU...
Page 279
Thermal release unit FT. Nc-72- duo 9.12 Clamping ring 9.13 Stiffening angle Seq. Designation 9.14 Connecting subframe Additions 9.15 T piece 11.1 Cable tray 9.16 Cover grille (Q grille) 11.2 Cable bundle 9.17 Sheet steel smoke extract duct 11.3 Pipe penetration Fire damper FKRS-EU...
Page 280
Cooking area, e.g. hob, grill, deep fryer 11.10 Cooker hood 11.11 Extract air fan 11.12 Attic 11.13 Extract air duct 11.14 Fire-resistant shaft * Please check in advance whether the PAROC material is available in your market region. Fire damper FKRS-EU...
Page 282
2023-12-01 PB General information: – Declaration of Performance increased from DoP / FKRS-EU / DE / 005 to DoP / FKRS-EU / DE / 006 – Addition EN 15882 to the standardisation principles, as a result: - Specification of the performance class for FKRS-EU with stainless...
Page 283
The use of FKRS-EU in walls with such profiles is permitted if the wall construction has been tested by the wall manufacturer.
Page 284
– FKRS-EU with spring return actuator and smoke detector – FKRS-EU with fusible link and cover grilles as an air transfer damper (FD) – FKRS-EU with spring return actuator and duct smoke detector as an air transfer damper (MFD) Structure and function - New attachments: ...
Page 285
Revision history Version Date Author Remark/amendment – M375DE7 Version 5 –> A00000092709 Version 1 Fire damper FKRS-EU...
Need help?
Do you have a question about the FKRS-EU and is the answer not in the manual?
Questions and answers