CTC Union EcoAir 400 Installation And Maintenance Manual
CTC Union EcoAir 400 Installation And Maintenance Manual

CTC Union EcoAir 400 Installation And Maintenance Manual

Air/water heat pump
Hide thumbs Also See for EcoAir 400:

Advertisement

Quick Links

Installation and Maintenance Manual
CTC EcoAir 400
Model 406 / 408 / 410 / 415 / 420
Air/water heat pump
Translation of the original instructions.
Keep for future use.
Read carefully before use.
162 605 32-3 CR00983 2025-03-04

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the EcoAir 400 and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for CTC Union EcoAir 400

  • Page 1 Installation and Maintenance Manual CTC EcoAir 400 Model 406 / 408 / 410 / 415 / 420 Air/water heat pump Translation of the original instructions. Keep for future use. Read carefully before use. 162 605 32-3 CR00983 2025-03-04...
  • Page 2: Table Of Contents

    Alarm output ................24 Positioning ..................5 Heat pump connections ............24 Recycling ..................5 Series connection of the CTC EcoAir 400 ....... 25 After commissioning ..............5 Connecting the control system ..........27 Connecting the control system ..........32 Safety instructions ...............6...
  • Page 3: Congratulations On Buying Your New Product

    Congratulations on buying your new product! The complete air source heat pump The CTC EcoAir 400 is an outdoor air source heat pump which moves heat from the outside air and delivers it to the heating circuit of the building. The CTC EcoAir 400 works with outside air temperatures down to -22°C.
  • Page 4: Checklist

    Checklist The checklist must always be completed by the installation engineer • If a service is performed, you may be required to provide this document. • Installation must always be done according to the installation and maintenance instructions. • Installation must always be carried out in a professional manner. Following installation, the unit must be inspected and functional checks performed as indicated below: Pipe installation...
  • Page 5: Important To Remember

    Important to remember! Check the following points in particular at the time of delivery and installation: Transportation Recycling • Transport the heat pump to the installation • The packaging must be deposited at a recycling location before removing the packaging. Move the station or with the installation engineer for product using one of the following means: correct waste management.
  • Page 6: Safety Instructions

    Safety instructions The installation should be preceded by an omnipolar safety switch according to overvoltage category III, which ensures disconnection from all electric power sources. Turn off the power with an omnipolar switch before doing any work on the product. The product must be connected to protective earth.
  • Page 7: Connection Alternative Ctc Ecoair 400

    Connection alternative CTC EcoAir 400 The illustration below shows the different connection alternatives available for the CTC EcoAir 400 In some cases, a CTC Converter or CTC Basic display may be needed, see the chapter “Electrical installation/Connecting the control system”.
  • Page 8: Technical Data

    Technical data 400V 3N~ EcoAir 406-408 General data Article number 585600001 585600002 HP-Keymark 012-056 012-057 Weight (gross) / Weight (net) 164 / 145 169 / 150 Dimensions (DxWxH), package excluded 545 x 1245 x 1080 Heating capacity 9.12 / 7.83 / 6.02/ Heating capacity max: 7.24 / 6.22 / 4.69/ 3.87 / 2.84...
  • Page 9: 400V 3N~ Ecoair 410-420

    (R407C, fl uorinated greenhouse gases GWP 1774) - equivalent 3.902 31±0,7 Max operating pressure, low pressure side (PS) 18.8 Seasonal coeffi cient of performance data SCOP for cold climate W35 (EN14825) SCOP for average climate W35 (EN14825) SCOP for warm climate W35 (EN14825) Max starting current measured at 100 mΩ...
  • Page 10: 230V 1N~ Ecoair 406-410

    Flow qw minimum: A7/W35 at defrost 0.39 Air fl ow: max Pressure drop across evaporator at max airfl ow Refrigerant system Refrigerant quantity (R407C, fl uorinated greenhouse gases GWP 1774) - equivalent 6.032 4.790 6.209 31±0,7 Pressure limiter, high pressure Low pressure sensor -1.0...18.8 Max operating pressure, high pressure side (PS)
  • Page 11 10.3 Ω 0.392 23.2 23.5 Dimension power cable Warm side Maximum operation pressure (PS) Water volume (V) liter Safety valve Maximum operating temperature (TS) °C Maximum operating temperature, condenser °C 2.35 Water volume, condenser liter 1.88 2.82 Flow qw nominal: A7/W35, Δt=5K 0.39 0.21 0.27...
  • Page 12: Component Location

    Component location...
  • Page 13 Ändring Ändr. av Kontr. av Ny artikel till ny produkt åsen förseglas Ventil kul filter G1" DN25 Kondensavlopp Plastpåse 210x325x40 Benämning Kommentar Ämnes nr Ersätter art. nr Compressor Ersättes av art. nr 4-way valve Defrosting sensor in evaporator Bipack EA614 Benämning Grupp Bipack...
  • Page 14: Dimensions Diagram

    Dimensions diagram Top view CTC EcoAir 406, 408 CTC EcoAir 410-420 1155 1285 1375 1245 1080 1180 Ø28 Ø28...
  • Page 15: Refrigerant System

    Refrigerant system Evaporator Defrosting sensor (B16) Suction gas sensor (B22) Low pressure sensor (B101) Compressor Hot gas sensor (B21) High pressure switch High pressure sensor (B100) 4-way valve Condenser Primary flow sensor (B1). Heating mode Defrosting mode Return sensor (B7) Drying filter Schrader Expansion valve...
  • Page 16: Installation

    Delivery includes: should be maintained. • 1 x Heat pump CTC EcoAir 400 The installation must be carried out in accordance with current MCS standards. Refer to MIS 3005 and • Packaged component (see chapter titled associated building regs Part L,F &...
  • Page 17: Location Of The Heat Pump

    Location of the heat pump • CTC EcoAir 400 is normally placed against an outside wall. These guidelines must be • The distance between wall and product is recommended to be at least followed in order for your 250 mm (EcoAir 610M / 614M) and 400 mm (EcoAir 622M) respectively,...
  • Page 18: Preparation And Drainage

    Preparation and drainage The heat pump should be positioned so that the house cannot be damaged and the condensation water can easily drain into the ground. The base must be of concrete blocks or similar, resting on crushed stones or gravel. •...
  • Page 19: Condensation Water

    Condensation water • The condensation tray is built into the heat pump and is used to divert most of the condensation water. The tray can be connected to a suitable drain. Connection diameter: 42 mm. • A heating cable (available as an accessory) should be placed in the pipe to prevent refreezing.
  • Page 20: Pipe Installation

    For longer pipes, the (>25 °C) for reliable installer should calculate the pump and pipe dimensions needed to handle the minimum recommended flow for the CTC EcoAir 400 defrosting functionality: concerned. EcoAir 420 180 L •...
  • Page 21: Example Pipe Connection

    Internal connection With internal connection, the flow through the circulation pump is controlled by the controller in the CTC EcoAir 400. The control system for the CTC EcoAir 400 monitors and ensures that the unit is working within its operating range.
  • Page 22: External Connection

    8.3.2 External connection With external connection, a circulation pump is installed so that the right flow through the heat pump can be guaranteed. The flow is set at 50 RPS. Set the right temperature differential by adjusting the speed of the circulation pump.
  • Page 23: Control/Supply

    The circulation pump (not speed-controlled) must be connected to the CTC EcoAir 400. Operating range The control system for the CTC EcoAir 400 monitors and ensures that the unit is working within its operating range. primary flow temp out temp...
  • Page 24: Electrical Installation

    Electric installation 400V 3N~ Supply, black connector CTC EcoAir 400 must be connected to 400V 3N~ 50Hz and protective earth. The minimum group fuse size is specified in “Technical data”. The 2 m long power supply cable is pre-connected to the product.
  • Page 25: Series Connection Of The Ctc Ecoair 400

    Series connection of the CTC EcoAir 400 9.6.1 Series connected heat pump connections In a series connection, dip switch 2 must be set to the “OFF” position on all heat pumps except the last one, which should be set to “ON”.
  • Page 26 Heat pumps in series connection The last heat pump connected in series CTC Basic Display B A G Sc B A G Sc Connect each cable to the next heat pump in the series connection here. Remove the jumper (PE), connect the screen to the next heat pump here.
  • Page 27: Connecting The Control System

    Connecting the control system Define number of heat pumps 9.7.1 Define the heat pumps in the controlling product’s display under: "Advanced/Defin/Heat pump". Set the heat pumps contained in the system to position "On". Example of a system with 3 heat pumps. 9.7.2 Numbering CTC EcoAir to HP2 Applies to control launched in October 2020...
  • Page 28 5. The heat pump is now numbered (HP2). When you press OK, (HP1 and HP2)* disappears and the row "Current address/New address" will go dark. *In this example, we have assumed that the heat pump is called HP1, which is the factory default. If the heat pump has already been renumbered, then select this number instead.
  • Page 29 When all heat pumps are numbered and energised, they should be displayed when you press the heat pump symbol in the menu “Operation data”. If any heat pump does not appear in the menu (communication with the heat pump fails) It may be because it has not been numbered as described above.
  • Page 30 9.7.4 Numbering CTC EcoAir as A2 Applies to older controls with 2 connectors on the back of the display. 1 RJ-45 and 1 RJ-12 for the CTC EcoZenith i550 Pro and CTC EcoLogic Pro/Family. RJ-12 RJ-45 1. System disconnected from power. 2.
  • Page 31 6. The heat pump is now numbered (A2). 7. To number the other heat pumps: Energise the control and the next heat pump to be numbered to heat pump 3 (A3). 8. Wait approx 2 minutes until the heat pump is visible in the Operation operational information.
  • Page 32: Connecting The Control System

    CTC EcoZenith i555 Pro, the CTC Basic Display accessory can be used to address be set to terminated the various heat pumps A1, A2, A3, and so on. All CTC EcoAir 400 units are position. factory-set addressed to A1. For connection, refer to the CTC Basic Display manual.
  • Page 33: Connection Option

    Converter accessory must be used as an interpreter to control the CTC EcoAir from 2006 onwards. 400. See the manual for the CTC Converter for connecting this. CTC EcoZenith CTC EcoEl CTC EcoLogic RS485 TX RS485 RX COM TX COM RX CTC Converter CTC EcoAir 400...
  • Page 34 The earlier version needed a Converter to control the heat pump. CTC EcoZenith CTC EcoLogic RS485 TX RS485 RX COM TX COM RX CTC Converter When connected in series, the last CTC EcoAir 400 must be set to the terminated position. CTC EcoAir 400 CTC EcoAir...
  • Page 35 CTC EcoZenith RS485 TX RS485 TX RS485 TX RS485 RX RS485 RX RS485 RX COM TX COM TX COM TX COM RX COM RX COM RX CTC Converter CTC Converter CTC Converter CTC EcoAir 400 CTC EcoAir 400 CTC EcoAir 400...
  • Page 36: Wiring Diagram 400V 3N

    Wiring diagram 400V 3N~ 586145...
  • Page 37: Wiring Diagram 230V 1N

    9.10 Wiring diagram 230V 1N~ 586260...
  • Page 38: Parts List

    9.11 Parts list Relay/main card Soft-start card with motor protection and contactor function Primary flow sensor Type 2 NTC/NTC 22 Return sensor Type 2 NTC/NTC 22 Outdoor sensor Type 1 NTC/NTC 22 Defrosting sensor Type 1 NTC/NTC 22 Fan sensor Type 1 NTC/NTC 22 Type 3 NTC/NTC 50 Discharge sensor...
  • Page 39: Sensor Data

    9.12 Sensor Data Sensor Type 2 NTC Sensor Type 3 NTC Sensor Type 1 NTC Temperature °C Temperature °C Temperature °C Resistance kΩ Resistance kΩ Resistance kΩ 5.37 0.67 0.22 0.78 6.18 0.25 7.13 0.908 0.28 0.32 1.06 8.26 0.37 1.25 9.59 1.47...
  • Page 40 Givare 22kΩ, framledning/ retur 2,5m Givare 22kΩ, framledning/ retur 2,5m Givare 22kΩ, framledning/ retur 2,5m Givare 22kΩ, framledning/ retur 2,5m Givare 48kΩ, Hetgas är ungefär lika med den nyare Givare 48kΩ, Hetgas är ungefär lika med den nyare Carel 50kΩ ( kallas NTC 50) denna givare skulle Carel 50kΩ...
  • Page 41: First Start

    10. First start Check that the boiler and system are full of water and have been bled. Check that all connections are tight. Check that sensors and the charge pump are connected to the power source. Energise the heat pump by switching on the operating switch (the main switch).
  • Page 42: Operation And Maintenance

    The condensation tray is located at the bottom on the back of CTC EcoAir 400. By lifting the handle and pulling it out, you can clean and inspect the condensation tray. You can buy a heating cable as an accessory and connect it to the EcoAir 400.
  • Page 43: Troubleshooting

    12. Troubleshooting The CTC EcoAir is designed to provide reliable operation and high levels of comfort, and to have a long service life. Various tips are given below which may be helpful and guide you in the event of an operational malfunction. If a fault occurs, you should always contact the installer who installed your unit.
  • Page 48 CTC AB Box 309 SE-341 26 Ljungby info@ctc.se +46 372 88 000 www.ctc.se...