Installation and operating instruction Gas condensing boiler WTC-GB 120 … 300-A User instructions ........................6 User guide ......................6 1.1.1 Symbols ......................... 6 1.1.2 Target group ......................6 Guarantee and Liability ..................7 Safety ............................8 Permissible application ..................8 When gas can be smelled .................
Page 4
Installation and operating instruction Gas condensing boiler WTC-GB 120 … 300-A Installation ..........................24 Requirements for the heating water ............. 24 5.1.1 Permissible water hardness ................24 5.1.2 Fill water quantity ....................25 5.1.3 Treatment of fill and top-up water ..............26 Hydraulic connection ..................
Page 5
Installation and operating instruction Gas condensing boiler WTC-GB 120 … 300-A Replacing electrodes ..................67 Removing and refitting burner tube .............. 68 Cleaning the heat exchanger ................. 71 Check flue gas pressure switch ..............72 10 Troubleshooting ........................73 10.1 Procedures for fault conditions ..............
Installation and operating instruction Gas condensing boiler WTC-GB 120 … 300-A 1 User instructions 1 User instructions These installation and operating instructions form part of the unit and must be kept Translation of original on site. operating instructions 1.1 User guide 1.1.1 Symbols Immediate danger with high risk.
▪ the installation of combustion chamber inserts, which impede full flame formation, ▪ repairs, which have been carried out incorrectly, ▪ the use of non original Weishaupt parts, ▪ unsuitable fuels, ▪ defects in the inlet lines, ▪...
Installation and operating instruction Gas condensing boiler WTC-GB 120 … 300-A 2 Safety 2 Safety 2.1 Permissible application The boiler is suitable for: ▪ Warm water heating circuits in closed systems according to DIN EN 12828 ▪ A flow rate of maximum: WTC 120 = 10.3 m WTC 170 = 14.2 m WTC 210 = 18.0 m...
Installation and operating instruction Gas condensing boiler WTC-GB 120 … 300-A 2 Safety 2.4.2 Electrical connection For all work carried out on live parts: ▪ Observe the accident prevention instructions BGV A3 and adhere to local direc- tives, ▪ tools in accordance with EN 60900 should be used. 2.4.3 Gas supply ▪...
Installation and operating instruction Gas condensing boiler WTC-GB 120 … 300-A 3 Product description 3.2.3 Safety devices Safety temperature limiter (eSTL) The fuel supply is shut off and the fan and the pump run-on are activated if the tem- perature on the eSTL exceeds a value of 95 °C ( W12 ). The boiler restarts automatically, if the temperature drops below the flow setpoint value for 1 minute.
Installation and operating instruction Gas condensing boiler WTC-GB 120 … 300-A 3 Product description 3.2.4 Program sequence Pre-purge At heat demand 1 the fan starts and dries to pre-purge speed 2. Ignition The fan drives down to ignition speed 3, ignition 4 switches on, the gas valves 5 open.
Installation and operating instruction Gas condensing boiler WTC-GB 120 … 300-A 3 Product description 3.3 Technical data WTC 120 / WTC 170 3.3.1 Approval data Gas Appliance Category 2ELL (DE, AT, CH) Type of installation CE-PIN CE-0063 BS 3948 SVGW 07-050-4 only in conjunction with a flue gas system in pressure class P1 or H1 to EN 14471.
Installation and operating instruction Gas condensing boiler WTC-GB 120 … 300-A 3 Product description 3.3.8 Flue gas system data WTC 120 WTC 170 Residual supply pressure at flue 163 Pa 166 Pa gas outlet Flue gas mass flow rate 10.3 … 51.1 g/s 12.1 …71.0 g/s Flue gas temperature at 80/60 °C 56 …...
Installation and operating instruction Gas condensing boiler WTC-GB 120 … 300-A 3 Product description 3.4 Technical data WTC 210 / WTC 250 / WTC 300 3.4.1 Approval data Gas Appliance Category 2ELL (DE, AT, CH) Type of installation CE-PIN CE-0063 BS 3948 SVGW 07-050-4 only in conjunction with a flue gas system in pressure class P1 or H1 to EN 14471.
Installation and operating instruction Gas condensing boiler WTC-GB 120 … 300-A 3 Product description 3.4.8 Flue gas system data WTC 210 WTC 250 WTC 300 Residual supply pressure at flue gas outlet 145 Pa 182 Pa 189 Pa Flue gas mass flow rate 19.5 …...
Installation and operating instruction Gas condensing boiler WTC-GB 120 … 300-A 4 Installation 4 Installation Only valid in Switzerland When installing and operating in Switzerland the regulations of SVGW, VKF, and local and Cantonal regulations must be observed. Remove front panel ▶...
Installation and operating instruction Gas condensing boiler WTC-GB 120 … 300-A 4 Installation Installation location The installation room must comply with local regulations. For must be fitted with an opening leading to atmosphere with a minimum cross section (see DVGW-TRGI, work sheet G 600).
Installation and operating instruction Gas condensing boiler WTC-GB 120 … 300-A 5 Installation 5 Installation 5.1 Requirements for the heating water In support of guideline VDI 2035 the following requirements are applicable for heating water. ▪ Untreated fill and top-up water must be of domestic water quality (colourless, clear and without any sedimentation), ▪...
Installation and operating instruction Gas condensing boiler WTC-GB 120 … 300-A 5 Installation WTC 210 / WTC 250 / WTC 300 WTC 210 WTC 250 WTC 300 1 Fill and top up water quantity in litres 2 Total hardness in °dH 5.1.2 Fill water quantity If information about the fill water quantity is not available, the following table can be used to estimate the quantity.
Installation and operating instruction Gas condensing boiler WTC-GB 120 … 300-A 5 Installation 5.1.3 Treatment of fill and top-up water De-ionisation (recommended by Weishaupt) ▶ De-ionise the fill and top-up water completely. (recommendation: mixed bed procedure) When the heating water has been entirely de-ionised, additional top-up water up to 10% of the system contents may be untreated.
Installation and operating instruction Gas condensing boiler WTC-GB 120 … 300-A 5 Installation 5.2 Hydraulic connection ▶ Flush the heating system with at least twice the total system content. ✓ Contaminants are removed. ▶ Connect the supply and the return (Recommendation: Use shut off valves). ▶...
Installation and operating instruction Gas condensing boiler WTC-GB 120 … 300-A 5 Installation 5.3 Condensate connection Danger of poisoning by escaping flue gas Flue gas can escape if the siphon is not filled. Inhalation leads to dizziness, nausea and eventually death. ▶...
Installation and operating instruction Gas condensing boiler WTC-GB 120 … 300-A 5 Installation 5.4 Gas supply Only an approved gas installer may carry out the gas side connection. Observe local regulations. The gas characteristics must match the data given on the name plate of the boiler. The condensing boiler is factory preset to Natural Gas E (G20).
Installation and operating instruction Gas condensing boiler WTC-GB 120 … 300-A 5 Installation 5.5 Routing of air/ flue gas circulation Air supply ducting The combustion air can be supplied: ▪ from the installation room (room air dependent operation), ▪ by connecting an external air inlet duct (room air independent operation). Flue gas system Local and building regulations must be observed when designing the flue gas ducting.
Installation and operating instruction Gas condensing boiler WTC-GB 120 … 300-A 5 Installation 5.6 Electrical installation Risk of electric shock Working on the unit when voltage is applied can lead to electric shock. ▶ Isolate unit from mains prior to carrying out work. ▶...
Installation and operating instruction Gas condensing boiler WTC-GB 120 … 300-A 5 Installation 5.6.1 Wiring diagram Observe the instructions for the electrical installation (see Ch. 5.6). The maximum total current of all external loads must not exceed 4.5 A. WCM - CPU µC - Unit eBUS Modul...
Installation and operating instruction Gas condensing boiler WTC-GB 120 … 300-A 5 Installation 5.6.2 Connection additional pump via output VA1 Observe the instructions for the electrical installation (see Ch. 5.6). ▶ Connect pump to wiring diagram. 230V MFA1 MFA2 eBUS L N PE 230 V/50 Hz 33-106...
Installation and operating instruction Gas condensing boiler WTC-GB 120 … 300-A 6 Operation 6.1.2 Display The display shows the current operating status and operating data. Symbols are shown or hidden depending on the system variation. When a remote control is connected (e. g. WCM-FS or WCM-EM) the symbols 9 …...
Installation and operating instruction Gas condensing boiler WTC-GB 120 … 300-A 6 Operation 6.2 End User Level In the end user level, various information can be called up and values can be changed. Symbols are shown or hidden depending on the system variation. When a remote control is connected (e.
Installation and operating instruction Gas condensing boiler WTC-GB 120 … 300-A 6 Operation 6.2.2 Settings End User Level ▶ Turn the dial knob. ✓ Tool bar appears. ▶ Turn the dial knob. ✓ Selection cursor alternates between the symbols. ▶ Press Enter button.
Installation and operating instruction Gas condensing boiler WTC-GB 120 … 300-A 6 Operation 6.3 Heating Engineer Level Activate heating engineer level ▶ Turn the dial knob. ✓ Tool bar appears. ▶ Turn the dial knob and set the selection cursor below the spanner symbol. ▶...
Installation and operating instruction Gas condensing boiler WTC-GB 120 … 300-A 6 Operation 6.3.1 Info level Display system values (i) ▶ Activate info level (see Ch. 6.3). ▶ Turn the dial knob. ✓ System values can be read. Depending on system variation, specific values are shown or hidden. Info system Unit...
Page 40
Installation and operating instruction Gas condensing boiler WTC-GB 120 … 300-A 6 Operation Info Sensors Unit i 37 Return temperature °C i 39 De-couple sensor temperature °C Info System info Unit i 42 Burner starts x 1000 i 43 Burner operating hours h x 100 i 44 Software version WCM-CPU...
Installation and operating instruction Gas condensing boiler WTC-GB 120 … 300-A 6 Operation 6.3.2 Parameter level Show parameter (P) ▶ Activate parameter level (see Ch. 6.3). ▶ Turn the dial knob. ✓ Parameters can be read. Depending on system variation, specific parameters are shown or hidden. Changing values ▶...
Page 42
Installation and operating instruction Gas condensing boiler WTC-GB 120 … 300-A 6 Operation Parame- Basic configuration Range of values Factory ters setting P 16 Function input H1 0 = Heating circuit release 1 = Heating circuit setback/normal 3 = Standby with frost protection 4 = Return signal flue gas damper (fixed, when P 11 = EA ) P 17 Function input H2...
Page 43
Installation and operating instruction Gas condensing boiler WTC-GB 120 … 300-A 6 Operation Parame- Circulation pump Range of values Factory ters setting P 40 Pump operation mode 0 = pump run-on heating 1 = pump continuous run P 41 Pump run-on time heat- 1 …...
Installation and operating instruction Gas condensing boiler WTC-GB 120 … 300-A 6 Operation 6.4 Manual start up ▶ Turn the dial knob. ✓ Tool bar appears. ▶ Set the selection cursor below the chimney sweep symbol. ▶ Press Enter button. ✓...
Installation and operating instruction Gas condensing boiler WTC-GB 120 … 300-A 6 Operation 6.5 Start manual configuration Manual configuration is used to match the settings with unit version. All sensors and actuators are re-entered during this process (see Ch. 7.2). ▶...
Installation and operating instruction Gas condensing boiler WTC-GB 120 … 300-A 6 Operation 6.6 Control options Constant flow temperature control No additional sensors or thermostats are required for this control. The flow temper- ature is controlled at the value set in the end user level (see Ch. 6.2.2). Weather compensation A remote control station (WCM-FS) and an external sensor (QAC 31) are required for weather compensated control.
Page 47
Installation and operating instruction Gas condensing boiler WTC-GB 120 … 300-A 6 Operation Temperature remote control 2 … 10 V ▶ Connect analogue setpoint signal 2 … 10 V to input N1 (see Ch. 5.6.1). ✓ Signal is interpreted as supply setpoint. Minimum flow temperature (P 30 ) 10 V Maximum flow temperature (P 31 )
Installation and operating instruction Gas condensing boiler WTC-GB 120 … 300-A 6 Operation 6.8 Boiler circuit pump 6.8.1 General information The unit can drive an external boiler circuit via outputs MFA 1, MFA 2 or VA1. The pump remains activated as long as heat requirement prevails. When no more heat is needed, the pump runs for the specified run-on time (NLZ) preset in parame- ter 41 .
Installation and operating instruction Gas condensing boiler WTC-GB 120 … 300-A 6 Operation 6.9 Frost protection Boiler frost protection Flow temperature < 8°C ▪ Burner is operated at minimum load. ▪ Outputs MFA and VA are active, if they have been parametered as heating circuit pump or feeder pump.
Installation and operating instruction Gas condensing boiler WTC-GB 120 … 300-A 6 Operation 6.10 Inputs and outputs Different applications can be realised with the freely selectable inputs and outputs. Output MFA and VA Output MFA is a non-isolated relay output. Output VA is potential free. All relay outputs can have a maximum loading of 3 A (AC1).
Page 51
Installation and operating instruction Gas condensing boiler WTC-GB 120 … 300-A 6 Operation Setting parameter 17 Description 3 = Burner lockout function If the input is closed, both the appliance and the pump switch off. Frost protection is not active. The display shows W24 , when the contact is closed.
Max run time flue gas damper 15 … 35 PWM setpoint pump inverse 0 / 1 – Factory setting. Parameter is safety relevant. Alterations are only permitted following consultation with the Weishaupt service de- partment. 52-106 83251702 • 1/2011-02 • La...
Max run time flue gas damper 15 … 35 PWM setpoint pump inverse 0 / 1 – Factory setting. Parameter is safety relevant. Alterations are only permitted following consultation with the Weishaupt service de- partment. 53-106 83251702 • 1/2011-02 • La...
Installation and operating instruction Gas condensing boiler WTC-GB 120 … 300-A 6 Operation 6.12 Chimney sweep function Activate chimney sweep function ▶ Turn the dial knob. ✓ Tool bar appears. ▶ Set the selection cursor below the chimney sweep symbol. ▶...
Installation and operating instruction Gas condensing boiler WTC-GB 120 … 300-A 7 Commissioning 7 Commissioning 7.1 Prerequisite Commissioning must only be carried out by qualified personnel. Only correctly carried out commissioning ensures the operational safety of the unit. ▶ Prior to commissioning check: ▪...
Installation and operating instruction Gas condensing boiler WTC-GB 120 … 300-A 7 Commissioning 7.1.1 Check soundness of gas valve train Soundness test ▶ Carry out soundness test: ▪ prior to commissioning, ▪ after all service and maintenance work. ▶ Switch off system. ▶...
Installation and operating instruction Gas condensing boiler WTC-GB 120 … 300-A 7 Commissioning 7.1.2 Check gas connection pressure The gas connection pressure must be within the following ranges: Natural Gas E/H 17.0 … 20 … 25.0 mbar Natural Gas LL 20.0 …...
Installation and operating instruction Gas condensing boiler WTC-GB 120 … 300-A 7 Commissioning 7.2 Adjusting the boiler ▶ During commissioning check: ▪ Maximum possible water throughput is ensured. ▪ Heat up is carried out with low flow temperatures and at low rating. ▪...
Page 59
Installation and operating instruction Gas condensing boiler WTC-GB 120 … 300-A 7 Commissioning 3. Adjust combustion The boiler is factory preset for operation with Natural gas E, H (G20). The O content must be checked and if necessary adjusted. WTC 120 Set O content at maximum rating ▶...
Page 60
Installation and operating instruction Gas condensing boiler WTC-GB 120 … 300-A 7 Commissioning WTC 170 / WTC 210 / WTC 250 / WTC 300 Set O content at maximum rating ▶ Open gas isolating valve. ▶ Manually drive rating to maximum (see Ch. 6.4). ▶...
Installation and operating instruction Gas condensing boiler WTC-GB 120 … 300-A 7 Commissioning 7.3 Calculate combustion heat rating Operating volume in m /h (gas throughput) Normal volume in m /h (gas throughput at 0 °C and 1013 mbar) Gas throughput determined at gas meter Time measured during gas throughput determination (V Conversion factor Gas temperature at meter in °C...
Installation and operating instruction Gas condensing boiler WTC-GB 120 … 300-A 8 Shutdown 8 Shutdown For breaks in operation: ▶ Switch off appliance. ▶ Close fuel shut off devices. ▶ If there is a risk of frost drain system. 62-106 83251702 •...
During the service, all system components with high wear and tear or with a specific life span should be replaced. Weishaupt recommends a service contract is entered into to ensure regular inspec- tions. Repair work on the following components must only be carried out by the component manufacturer or their approved agent: ▪...
Page 64
Installation and operating instruction Gas condensing boiler WTC-GB 120 … 300-A 9 Servicing Following servicing ▶ Check soundness of gas valve train (see Ch. 7.1.1). ▶ Check soundness of flue gas and condensate carrying components. ▶ Check tightness of water carrying components. ▶...
Installation and operating instruction Gas condensing boiler WTC-GB 120 … 300-A 9 Servicing 9.1 Safety components ▶ Vital safety components must be replaced as soon as they reach their predefined lifetime. The predefined lifetime is not the warranty time specified in the terms and conditions of delivery and payment.
Installation and operating instruction Gas condensing boiler WTC-GB 120 … 300-A 9 Servicing 9.3 Check differential pressure at air pressure switch Observe notes on servicing (see Ch. 9). ▶ Remove right side panel. ▶ Remove hoses from the test points 1 on the air pressure switch. ▶...
Installation and operating instruction Gas condensing boiler WTC-GB 120 … 300-A 9 Servicing 9.5 Removing and refitting burner tube Observe notes on servicing (see Ch. 9). Removal WTC 120 ▶ Close gas isolating valve. ▶ Remove electrodes (see Ch. 9.4). ▶...
Page 69
Installation and operating instruction Gas condensing boiler WTC-GB 120 … 300-A 9 Servicing Removal WTC 170 / WTC 210 / WTC 250 / WTC 300 ▶ Close gas isolating valve. ▶ Remove electrodes (see Ch. 9.4). ▶ Remove plugs for gas pressure switch 6, gas valve 5 and fan 2. ▶...
Page 70
Installation and operating instruction Gas condensing boiler WTC-GB 120 … 300-A 9 Servicing Cleaning the burner tube Clean burner tube if required: ▶ Clean the inside of the burner tube (if necessary use compressed air to blow through from outside to inside). ▶...
Installation and operating instruction Gas condensing boiler WTC-GB 120 … 300-A 9 Servicing 9.6 Cleaning the heat exchanger Observe notes on servicing (see Ch. 9). ▶ Remove left panel. ▶ Remove service covers from heat exchanger 1 and the condensate collector 4. ▶...
Installation and operating instruction Gas condensing boiler WTC-GB 120 … 300-A 9 Servicing 9.7 Check flue gas pressure switch Observe notes on servicing (see Ch. 9). ▶ Switch on main switch. ▶ Set boiler to Standby (see Ch. 6.2.2). If a remote control station is fitted, see op- erating instructions WCM-FS.
Installation and operating instruction Gas condensing boiler WTC-GB 120 … 300-A 10 Troubleshooting 10 Troubleshooting 10.1 Procedures for fault conditions Damage resulting from incorrect servicing The combustion plant could be damaged. ▶ Do not carry out more than 2 lockout resets successively. ▶...
Installation and operating instruction Gas condensing boiler WTC-GB 120 … 300-A 10 Troubleshooting 10.2 Fault history The last 6 faults and the system status at the time of the faults are recorded in the fault history. Display the fault ▶ Activate the fault level (see Ch.
Installation and operating instruction Gas condensing boiler WTC-GB 120 … 300-A 10 Troubleshooting 10.3 Rectifying faults 10.3.1 Warning codes Warning code Cause Rectification ▶ Temperature at eSTL > 95 °C Check the water flow. ▶ Temperature at supply sensor > 95 °C Check function of the pumps.
Page 76
Installation and operating instruction Gas condensing boiler WTC-GB 120 … 300-A 10 Troubleshooting Warning code Cause Rectification ▶ Communication to EM#3 is faulty Check address. ▶ Check the connection ▶ Replace the extension module. ▶ Communication to EM#4 is faulty Check address.
Installation and operating instruction Gas condensing boiler WTC-GB 120 … 300-A 10 Troubleshooting 10.3.2 Error codes Error code Cause Rectification ▶ Temperature at eSTL > 105 °C Check the water flow. ▶ Check function of the pumps. ▶ Vent boiler on the water side. ▶...
Page 78
Installation and operating instruction Gas condensing boiler WTC-GB 120 … 300-A 10 Troubleshooting Error code Cause Rectification ▶ Data record error burner Check the BCC connector and replace if nec- essary. ▶ Reset appliance, replace WCM-CPU on re- peat occurrence. ▶...
Installation and operating instruction Gas condensing boiler WTC-GB 120 … 300-A 10 Troubleshooting 10.3.3 Operating problems Observation Cause Rectification ▶ Burner does not operate in spite of Burner rapid cycle interlock ac- Wait for the cooling down. ▶ heat demand tivated Check sensor and replace if necessary.
Installation and operating instruction Gas condensing boiler WTC-GB 120 … 300-A 12 Technical documentation 12.4 Conversion table O2/CO2 content content in % dry in %v Natural Gas E Natural Gas LL Propane (max 11.7 % CO (max 11.5 % CO (max 13.7 % CO 10.5 10.3...
Installation and operating instruction Gas condensing boiler WTC-GB 120 … 300-A 14 Key word index Fan speed ..............15, 19 Fault conditions ..............73 Adjusting ................58 Fault history ................74 Adjustment ................23 Faults ..................73 Air inlet pipe .................10 Filling the water ..............27 Air pressure ................61 Flow limit .................
Page 106
Installation and operating instruction Gas condensing boiler WTC-GB 120 … 300-A 14 Key word index Temperature differential ............12 Temperature remote control ..........47 O2 content ........... 14, 18, 59, 60, 103 Throughput limit ............15, 19 Operating panel ............11, 34 Transport ..............
Page 108
Change of legal form from 22.11.2024: Max Weishaupt SE Change of legal form from 22.11.2024: Max Weishaupt SE www.weishaupt.de Max Weishaupt GmbH, D-88475 Schwendi Weishaupt (UK) Limited Neachells Lane, Willenhall, WV13 3RG www.weishaupt.co.uk Printed in Germany. All rights reserved. Product...
Need help?
Do you have a question about the WTC-GB 120-A and is the answer not in the manual?
Questions and answers