Technical installation manual SPC-HEVX2 Vintage GCH air condensing unit The characteristics given in this technical sheet may change without prior notice, with the improvements that «FRIAX Industrie» always in- tends to make to its production. EN-NT-SPC-HEVX2-VTX-0125...
Page 2
Warning Read the manual carrefully before using the device and keep it for futur reference. This symbol indicates that the installation manual should be read carrefully. This symbol indicates that a technician must handle this equipment in referring to the installation manual. This symbol indicates that information are available, such as the manual operating instructions or installation manual.
Presentation Thank you for choosing a Friax cellar system to control the aging of your wines. Take the time to read this user manual. It will allow you to understand and master the operations to install and adjust your device.
Electrical connections SPC HEVX2 Voltage/Frequency 230V / 50Hz 230V / 50Hz Protection 3g1.5² cords 3g1.5² cords Power supply (provided) Link indoor 1x (5g1.5²) 1x (5g1.5²) unit ==> Outdoor unit 1 x (3 x1mm²) 1 x (3 x1mm²) (Not provided) 1 x (2 x0.5mm²) lg 20m Max 1 x (2 x0.5mm²) lg 20m Max Schematic diagram 12°C...
Dimensions Make sure you have sufficient clearance Your EVX2 evaporator uses its periphery along the wall to extract air. Allow at least 25 cm of space around the device so as not to obstruct the air flow and obtain optimal flow. For perfect diffusion, it is recommended to install the air conditioner high up;...
Fixing template WALL TEMPLATE For rear connection: Niveau The two refrigeration connections and the two electri- cal connections must pass through this hole. It will be necessary to drill the wall. Ø70mm Rear connection hole Fridge connections 2x Ø35mm Fixing the evaporator - Fix the device to the wall using screws suitable for the support (not supplied).
Installation of condensate drainage. - A sachet is supplied with your air conditioner, It includes 2 internal Ø 15 condensate pipes (1 x 40 mm 40mm Connections from inside the cellar. - Use the passages located at the bottom left for condensate drainage.
Fixing GCH Groups 30 to 48 Advice: -Raise the unit to avoid leaves and snow. -Favour open areas, out of the sun -Check the solidity of the supports. -Beware of noise for neighbours. Wall fixing Installation with KS2M kit (list of accessories) 133 mm 100 mm 100 mm...
Floor fixing The GCH unit can be placed on the floor using Rubber Foot (not supplied or sold by Friax) to avoid operating vibrations. Cover removal 1-Use a screwdriver to remove the nail from the rubber block. 2-Slide the cover in the direction of the arrow...
Refrigeration connection Be sure to read this carefully before installing your FRIAX equipment if the outdoor unit is above the evaporator. Make the connection to the piping (flare fittings). After connecting, evacuate the piping and the evaporator via the Schrader fittings located on the conden- sing unit valves.
Pipe preparation and flaring pipe in Compliant Improper 1-Cut the copper pipe correctly with a pipe cutter copper 90° (Fig1, 2). 2- Deburr gently while holding the pipe downwards to avoid introducing filings into the tube. (Fig.3) Fig.1 Fig.2 3-Remove the “FLARE” nuts attached to the device pipe in copper Flaring Tool slip them onto the pipes after removing all burrs.
Using the vacuum pump 1-Remove the charging port caps (Schrader) from the service valves of the gas lines and liquid lines of the outdoor unit (Fig8). 2-Connect the charging pipes to the schraders of the gas (Blue) and liquid (Red) side service ports. 3-Connect the charging hose (yellow) to the vacuum pump nozzle.
Handling of valves Once the vacuum is complete, 1- Fully open the control rods by turning them outwards but do not try to open them beyond the stop. (Start with the liquid side then the gas side). 2-Start the air conditioner and wait for a while, check the gas charge, the liquid indicator should not be bub- bling.
Installing the connectors 3 connectors are delivered to you in a bag in the evaporator box, for be connected to your cables following the assembly below. 1. Stripping length = 30 mm (2 poles), 37 mm (3 poles), 45 mm (4 and 5 poles) 2.
-Remove the protective film from the bodywork. - Place the bodywork and tighten the wing nuts by hand without forcing. - Put the colored magnetic front in place (Friax logo facing up). -During commissioning, you can remove this bodywork to check that your hy-...
Maintaining your cellar air conditioner The following maintenance operations, repeated every 6 months, will ensure that your air conditioner re- tains its optimum performance and lasts as long as you and your wine. Warning! Before any maintenance operations, turn off the device using the remote control then cut off the power sup- ply at the main circuit breaker to avoid any risk of electrocution.