SE Controls NV LogIQ Technical Information & Operating Instructions

Advertisement

Quick Links

Introduction
The NVLogiQ PSU is an adaptive Environmental Ventilation single zone
control panel and can be networked in multi zone projects.
It has the ability to operate on its own through manual switches, or it
can be connected to the BMS to manage the AOVs as required.
The NVLogiQ PSU can be installed into new and refurbished buildings
where there is a focus on indoor air quality and energy saving.
The physical size and appearance has been purposely designed to
enable surface mounting for new and refurbishment projects.
+44 (0)1543 443060
sales@secontrols.com
www.secontrols.com
NV LogIQ Power Supply
Technical Information & Operating Instructions
Application
The NV LogIQ Power Supply is a 24 Volt dc control
system designed for 2-wire 24V dc actuators in a
natural ventilation system.
Operating from a 230 V ac 2.0 A supply, the NV LogIQ
Power Supply can deliver 4.8 A (NPS00010002) for
short periods to motorised actuators.
The NV LogIQ Power Supply can be mounted locally
to the devices to be operated or in a centralised, plant
room location. Each NV LogIQ Power Supply can
operate independently or can be linked to others to
produce a networked control system.
.
.
Please keep these operating instructions for future reference and maintenance.
Subject to technical modifications. Diagram is not binding.

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the NV LogIQ and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for SE Controls NV LogIQ

  • Page 1 It has the ability to operate on its own through manual switches, or it Operating from a 230 V ac 2.0 A supply, the NV LogIQ can be connected to the BMS to manage the AOVs as required.
  • Page 2: Table Of Contents

    Contents General Information Switches 1.1. Packaging 4.1. Rotary Switch (SW2) 14-16 1.2. Preparation Quick Switch Settings 1.3. Location Circult Board Information 1.4. Fixing 5.1. External Control Board Indication 1.5. Disposal 5.2. Internal Control Board Indication 1.8. Contact Information 5.3. Error Codes 1.9.
  • Page 3: Important Notices

    Important Notices • The equipment has no • Failure to install the SE Controls accepts mains on/off switch and is device in accordance no liability for failure to comply with these intended for permanent with the manufacturer’s connection only. instructions will invalidate statements or the any warranties.
  • Page 4: General Information

    Care should be taken whilst the cover is removed to protect against damage to the internal electronic assemblies and light pipes. 1.3. Location The NV LogIQ Power Supply is intended for indoor use only. The unit is environmentally rated to ingress protection IP20 and should not be located where exposure to damp/moisture or significant amounts of dust is likely. In particular, do not mount the controller in extreme environments such as cold rooms/ovens and those areas classified as having potentially explosive atmospheres.
  • Page 5: Fixing

    1.4. Fixing Mark through the mounting holes (3 off) on the NV LogIQ Power Supply base plate assembly. It is important to drill pilot or fixing holes of the suitable size and employ plastic plugs or cavity fixings when necessary. To firmly secure the base plate, make use of pan head or countersunk screws that are of the appropriate size. R2.50 R4.70 251.2 Ø5 Figure 1 - Fixing Hole Locations Please keep these operating instructions for future reference and maintenance. +44 (0)1543 443060 Subject to technical modifications. Diagram is not binding. sales@secontrols.com www.secontrols.com...
  • Page 6: Disposal

    Disposal Do not dispose of electronic equipment with household or general commercial waste. For advice on disposal consult the local environmental officer, a recycling or waste management specialist or have them removed for correct disposal during regular planned preventive maintenance programs (contact SE Controls for details). 1.6. Contact Information For sales, technical support and maintenance please contact:...
  • Page 7: Specification

    Specification Part Number NPS00010002 Dimensions 280 x 190 x 55 mm (W x H x D Approx) Mass Approx 1.2 kg Supply Class 1 Supply 230 V ac 50/60 Hz from a fused unswitched spur Power Consumption Max 500 V A 100 - 120 V ac 3.5A Typical Output Voltage 200 - 240 V ac 2.0A...
  • Page 8: Connections

    Connections 3.1. Assembly and Mains Connection Wiring to the NV LogIQ Power Supply can be direct to the unit via the cable glands entry points. Alternatively for cosmetic flush/surface mount applications the wiring can be passed through the cavity located in the rear of the NV LogIQ Power Supply. It is recommended that the required number of cable entry glands are assessed and fitted at this point. Blanking plugs and 22 mm glands are provided for this purpose.
  • Page 9: Dyo/Dyc'- Open And Close Day/Day (Vfc) Input

    3.3. ‘DYO/DYC’ - Open and Close Day/Day (VFC) Input The ‘DYO’ & ‘DYC’ (Day to Day) functions are activated by means of an external volt free contact (VFC) signal (usually provided in the form of a momentary switch). An asserted input is used to manually open or close the connected actuator (via 24V dc actuator drive output connection).
  • Page 10: Hlt' - Halt (Vfc) Input

    (See SW2 – Position ‘1’ function mode). Conversely, an asserted (shorted) VFC input on the ‘ A /M’ inputs places the NV LogIQ Power Supply into‘ Auto’ mode, where any manual [DYC or DYC] Day to Day operation will not respond to user input, and, any running BMS lockout period is cancelled (i.e.
  • Page 11: Rns' - Rain Sensor

    SW2 – Position ‘3’ function mode. Under these conditions the NV LogIQ Power Supply will follow the BMS demand up to the set allowable open position during rain.
  • Page 12: Tp' - Thermister Input

    ‘TP’ - Thermister Input - Legacy Use Only If the NV LogIQ Power Supply is to be used in conjunction with the NV LogIQ Room controller(s), a single external temperature sensor must be fitted to one of the systems NV Power Supplies. The NV LogIQ Power Supply is designed to operate with the ‘Sontay TT-532-A’...
  • Page 13: Pep' And 'Ovp' - Power Input

    3.13. ‘PER’ and ‘OVP’ - Power Input The PER & 0VP are the connections points for the + 24 V dc power feed from the mains transformer. Please keep these operating instructions for future +44 (0)1543 443060 reference and maintenance. Subject to technical sales@secontrols.com modifications.
  • Page 14: Switches

    Switches 4.1. Rotary Switch (SW2) The Rotary switch (SW2) provides a selection method for the required operational settings or function monitor. The push button switch (SW1) is used to increment/change the selected value operational setting and reset any system errors (e.g. actuator over current) Switch Detail Push button –...
  • Page 15 Auxiliary relay mode (Note: the NVLINK zones settings must be matched between the wall controller and the NV LogIQ Power Supply) ‘psu’ Power Supply Status Mode – The auxiliary relay indicates the status of the power supply ((PSU > 18 V dc ) = Relay N/O) ‘bth’...
  • Page 16 BMS modes: demand level (0-100%). ‘OSL’ No BMS Input The BMS input demand is sent via NVLINK from an external source (such as an SE Controls NV Room Controller) 0-10V dc BMS Input NVLINK Mode Switch Pos ‘ A ’ - Temperature in ⁰C...
  • Page 17: Quick Switch Settings

    4.2. Quick Switch Settings The following chart can be used as a quick start guide for the switch settings that must be adjusted on the NVLogiQ Power Supply for a particular controller function. Day/Day Input BMS 0-10V Input Room Controller Mode Mode (OSLIINK) Input Mode...
  • Page 18: External Control Board Indication

    7 Segment display indicating the current setting for the selected function Segment LEDs parameter (See switch SW2 settings) Error Codes Any error conditions encountered by the NV LogIQ Power Supply are referenced on the seven segment display: Error Code Description 3 Amp Power Supply Current Limit Exceeded (Legacy)
  • Page 19: Hierarcy Of Functions

    Hierarcy of Functions 6.1. Hierarcy of Functions To avoid control conflicts, the control inputs are organised in a strict hierarchical priority order: • PIR (highest priority) • Maintenance - Open demand • Maintenance - Close demand • Rain Sensor • Day to day switch - Open demand (* if Auto/Manual input is in Manual mode) •...
  • Page 20: Connection Schematics

    Connection Schematics 7.1. Connection Schematics • The following sections are to be used for guidance only and are subject to change. • All external switch contacts are to be volt-free and capable of carrying 24 V dc at 10mA. • The maximum cable length for digital control input signals is 500 m. •...
  • Page 21 Lancaster House Wellington Crescent sales@secontrols.com Fradley Park, Lichfield www.secontrols.com Staffordshire WS13 8RZ Name & registered office: Loanguard Limited, Lancaster House, Wellington Crescent, Fradley Park, Lichfield, Staffordshire WS13 8RZ Company No.01468061 Vat No.377 5600 30 - SE Controls is a Registered Trademark...