AM2SE Protection Relay User Manual V1.4 Acrel CO.,LTD...
Page 2
DECLARATION All rights reserved. No part of this publication may be reproduced, stored in a retrieval system, or transmitted in any form by any means, electronic, mechanical photocopying, recording, or otherwise without prior permission of our company. The violator will bear the dependent legal responsibility. We reserve all the rights.
Main characteristic Protection functions The AM2SE relay has a modular design and it can be optimized to the line, transformer, PT protection applications in medium voltage distribution systems. Robust Hardware and Software ...
Acrel Co., Ltd. 2 Technical Characteristics 2.1 Rated Characteristics Version AM2SE Characteristics Power Supply Rated voltage AC/DC 110V or AC/DC 220V or DC48V or DC24V Range Rated voltage × (1±20%) Burden ≤10W ( DC ) PT Inputs Rated value AC 100V or PT rated secondary range 1V~120V...
Acrel Co., Ltd. Making capacity ≥ 1000W, L / R = 40ms Continuous current ≥ 5A Short duration carry current ≥ 30A for 200ms Breaking capacity ≥ 30W, L/R = 40ms 2.2 Protection Characteristics Characteristics Accuracy Resolution Disengaging ratio Voltage ±3%...
Page 9
Acrel Co., Ltd. Radiated radio frequency fields IEC-60255-26:2023 Electrostatic discharge IEC-60255-26:2023——6.1 Conducted radio frequency disturbance IEC-60255-26:2023——6.2-6.5 Fast transient bursts IEC-60255-26:2023——6.2-6.5 Slow damped oscillatory waves IEC-60255-26:2023——6.2-6.4 Surges IEC-60255-26:2023——6.2-6.4 Voltage dips and short interruptions test IEC-60255-26:2023——6.2 (AC or DC) Magnetic field at power frequency IEC-60255-26:2023——6.1...
Acrel Co., Ltd. 3 Use 3.1 Front Panel Introduction The AM2SE relay is equipped with a user friendly local panel which is shown in Figure 3.1 128*64 LCD screen Navigation buttonpad 6 LEDs Confirmation button Reset button button Fig.3.1 AM2SE Vertical & Horizontal surface 3.2 Push buttons...
Acrel Co., Ltd. Figure 3.2 (1): The operation interface without a single-line diagram. This can be modified in the configuration menu under the "Main Interface Single-Line Diagram" option. Figure 3.2 (2): The operation interface with a single-line diagram. The single-line diagram displays the on/off status of the circuit breaker.
Acrel Co., Ltd. button to return to the superior menu. Figure 3.6 shows the navigation diagram of the relay, which can be used to find relevant parameters quickly. Fig. 3.5 Main Menu Fig. 3.6 Navigation diagram 3.3.2 Configuration The "Conf" menu can set the LCD backlight time, as shown in Figure 3.7. After modification,...
Acrel Co., Ltd. Fig. 3.7 Backlight Time Setting Fig. 3.8 Configuration Save 3.3.3 Parameter The "Para" menu includes 3 sub-menus: Value View, Value Modify and Switch Group, as shown in Figure 3.9. A) Value View The "Value View" menu includes two sub-menus: "Selected" and "Running". There are 4 groups of valid value in the "Selected",which are 00, 01, 02, and 03 areas.
Acrel Co., Ltd. save the modification and return to the “Menu” .If press the button, relay will return to the “Menu”directly without saving the modification. The"Running" interface only shows the current running area of the relay, and no modification is made here.
Acrel Co., Ltd. digital input to "CB On". According to Appendix B, the code for “CB ON” can be found as 1079. Then the “Name05.C” should be modified to 00001079 in the "Modify". Next, the "CB On.C" in the "Modify" should be configured to 5. After the modification, it can be viewed in the digital inputs interface, as shown as figure 3.16.
Acrel Co., Ltd. Fig. 3.18 Error Record 3.3.7 Communication As shown in Figure 3.19, the "Comm" menu can set the communication address of relay and baud rate. Communication parameters can be configured based on the options in Table 3.2. After...
Acrel Co., Ltd. 3.3.10 Information The "Information" menu can display the basic information includes relay’s name、version、 check code、hardware、software、logic、logic version and so on, as shown in Figure 3.21. Fig. 3.20 Time Setting Fig. 3.21 Information...
Acrel Co., Ltd. 4 Dimension and Installation 4.1 Dimensions and Cut-out Dimension AM2SE-V (Vertical Ver.) Fig. 4.1 AM2SE-V Dimensions and cut-out dimensions Note: 1. Square cutout size is 150 x 68 mm. 2. Length unit is millimeter (mm).
Page 19
Acrel Co., Ltd. AM2SE-H (Horizontal Ver.) Fig. 4.2 AM2SE-H Dimensions and cut-out dimensions Note: 1. Square cutout size is 68 x 150 mm. 2. Length unit is millimeter (mm).
Insert the fixing brackets of the relay to secure it firmly to the cabinet panel, as shown in Fig. 4.4. Note: 1. For the AM2SE-V, the fixing brackets are located on the top and bottom of the relay.For the AM2SE-H, the fixing brackets are on the left and right sides of the relay.
Acrel Co., Ltd. 5.2 Typical application The following describe typical application diagrams. 3CTs and residual current, 3PTs have been showed in the diagrams. Fig. 5.2 Typical application diagram...
Page 23
Acrel Co., Ltd. Fig. 5.3 AM2SE function diagram...
Acrel Co., Ltd. 6 Product Maintanance The following table shows the common problems and treatment methods of the AM2SE during use. Table 6.1 Common problems and treatment methods Question Possible Cause Suggestion 1. Corresponding function is 1、 Set the corresponding protection enable Relay does not trip not enabled.
Acrel Co., Ltd. 过流一段定值 3I>>> 0.04~120 [ 3I>>> value ] 过流一段延时 3I>>>.T 0~60 [ 3I>>> delay time ] 过流二段投退 退出;投入 E.3I>> 0~1 Off;On [ Enable.3I>> ] 退出;投入 Off;On [ If enable 3I>>.U, voltage conditions should be considered for overcurrent 二段经低压...
Page 29
Acrel Co., Ltd. smallest of the three line voltages is less than U.Under and greater than U.Less, the overcurrent protection DO is prepare work. ] 过流三段定值 3I> 0.04~120 [ 3I> value ] 过流三段延时 3I>.T 0.5s 0~60 [ 3I> delay time ] 反时限过流投退...
Page 32
Acrel Co., Ltd. be blocked. ] [ Less than I.None 无流定值 I. None 0.2A 0.04~120 means that there is [Current none] no current ] 退出;投入 Off;On PT 断线闭锁投退 [ When PT break E. PT.B occurs, the relay will [ Enable PT break block]...
Page 36
Acrel Co., Ltd. "steal trip" can act auto-reclose.] 后加速过流投退 E. I>P 退出;投入 0~1 Off;On [ Enable post accelerating overcurrent ] 退出;投入 Off;On [ If enable I>P.U , voltage conditions should be considered for overcurrent 后加速经低压 protection. When the E. I>P.U 0~1...
Page 37
Acrel Co., Ltd. frequence function will be lockout.] 退出;投入 Off;On 滑差闭锁 [ When df/dt lower E.UnderFr.dHz. 0~1 than dHz.B, Under [ Enable UnderFr.dHz] frequence function will be lockout.] 低频减载定值 UnderFr. 49Hz 45~60 [ UnderFr. value ] 低频减载延时 UnderFr.T 0~60 [ UnderFr. delay time ] 滑差闭锁值...
Page 41
Acrel Co., Ltd. 负控保护配置 Ne.Con.C 0~8 [ Negative Control configuration ] 负控保护投退 退出;投入 E. Ne.Con 0~1 Off;On 负控保护 [ Enable Ne.Con.] Negative Control 负控保护方式 告警;跳闸 E. Ne.Con.M 0~1 Alarm;Trip [ Enable Ne.Con. Mode ] 负控保护延时 Ne.Con.T 0~999 [ Ne.Con. delay time ] 检修状态配置...
Page 42
Acrel Co., Ltd. as zero sequence CT] [ When there are 2CT, wheather zero sequence current is involved in the calculation of Ib.] 过量返回系数 Excess R.C 0.95 0.001~2 [ Excess Return Coefficient ] 欠量返回系数 Under R.C 1.05 0.001~2 [ Under Return Coefficient ]...
Page 44
Acrel Co., Ltd. 1QF 位置 2QF 位置 1QF Circuit Breaker On 1031 2QF Circuit Breaker On 1032 1QF On 2QF On 1 号主供跳位警报 2 号主供跳位警报 1QF Circuit Breaker Off Alarm 1033 2QF Circuit Breaker Off Alarm 1034 1QF Off A.
Page 45
Acrel Co., Ltd. 非保证负荷 2 非保证负荷 3 1057 1058 Non guarant load2 Non guarant load3 非保证负荷 4 非保证负荷 5 1059 1060 Non guarant load4 Non guarant load5 非保证负荷 6 非保证负荷 7 1061 1062 Non guarant load6 Non guarant load7 非保证负荷 8 非保证负荷...
Page 46
Acrel Co., Ltd. Isolation Handcart Work Position Isolation Handcart Test Position Iso.W.P Iso.T.P 隔离手车位置 急停信号 Isolation Handcart Position 1091 Emergency stop signal 1092 Iso.P Emergency stop sig. 计量断路器分位 计量断路器合位 Metering Circuit Breaker Off 1093 Metering Circuit Breaker On 1094 Meter.CB Off Meter.CB On...
Page 47
Acrel Co., Ltd. Upper Isolation On Upper Isolation Switch On Upper Iso.On Upper Iso.Switch On 手车工作位置 手车试验位置 Handcart Work Position 1117 Handcart Test Position 1118 Work Posi. Test Posi. 手动分闸 手动合闸 1119 1120 ManualTrip ManualClose 所用变工作位置 所用变试验位置 Transformer Handcart Work Position...
Page 48
Acrel Co., Ltd. Power Loss Circuit Breaker Temperature Alarm Cir.Temp.A I/II 段失压跳闸信号 油机并车屏联跳 Oil Engine Parallel Intertrip 1147 I/II Loss Voltage Trip Signal 1148 Oil.Eng.Par.Joint.T I/II LV.T Sig. I/II 段电压并列信号 进线侧电源失电 I/II Voltage Parallel Signal 1149 In-coming Power Loss 1150 I/II Vol.Par.Sig.
Page 53
Acrel Co., Ltd. Reclosing Pre.Plate 自投开关投入 Enable Automatic Switch 3041 AutomaticSwitch Input 信号量遥信 Signal 备用信号量遥信 1 备用信号量遥信 2 Spare Signal 1 4001 Spare Signal 2 4002 Spare Signal1 Spare Signal2 备用信号量遥信 3 备用信号量遥信 4 Spare Signal 3 4003 Spare Signal 4...
Page 54
Acrel Co., Ltd. 负控保护 运行状态 Load Control Protection 4025 4026 Running State Nega.Control.P 系统谐振信号 电压并列 4027 System Resonance Signal 4028 Voltage Parallel Sys.Resonance Sig. 系统接地信号 绝缘监察 System Ground Signal 4029 4030 Insulation Monitor Sys.Ground Sig. CT 二次过压 主变异常信号 Transformer Abnormal Signal...
Acrel Co., Ltd. Appendix C Relay Event AM 事件记录 AM Event Record 参数值 参数单位 事件代码 事件名称 参数名称 Parameter Parameter Event code Event name Parameter name values unit A 相电流 浮点数 Float B 相电流 浮点数 Float C 相电流 浮点数 Float 浮点数...
Page 56
Acrel Co., Ltd. Float 浮点数 Float 负序电压 Negative sequence 浮点数 voltage Float A 相二次谐波电流 浮点数 Ia Second Harmonic Float Ia_H2 B 相二次谐波电流 浮点数 Ib Second Harmonic Float Ib_H2 C 相二次谐波电流 浮点数 Ic Second Harmonic Float Ic_H2 A 相电流 浮点数 Float B 相电流...
Page 57
Acrel Co., Ltd. A 相电流 浮点数 启动时过流一段保护 Float [Motor Start Instantaneous B 相电流 浮点数 overcurrent] Float 3I>>>.S C 相电流 浮点数 Float A 相电流 浮点数 运行时过流一段保护 Float [Motor Run Instantaneous B 相电流 浮点数 overcurrent] Float 3I>>>.R C 相电流 浮点数 Float 时间...
Page 58
Acrel Co., Ltd. 浮点数 Float 负序电压 Negative sequence 浮点数 voltage Float 时间 浮点数 A 相电流 浮点数 Float B 相电流 浮点数 Float C 相电流 浮点数 C 相反时限过流保护 Float [Ic Inverse Definite Minimum 浮点数 Time overcurrent] Float Ic>InverseT. 浮点数 Float 浮点数 Float 负序电压...
Page 59
Acrel Co., Ltd. Definite Minimum Time overcurrent] 浮点数 I01>InverseT. Float I02 反时限 时间 浮点数 [I02 ground fault Inverse Float Definite Minimum Time overcurrent] 浮点数 I02>InverseT. Float A 相电流 浮点数 Float 后加速过流保护 [Post-accelerated overcurrent] B 相电流 浮点数 I>P.T Float C 相电流...
Page 60
Acrel Co., Ltd. 跳闸百分比 浮点数 Trip Percent Float 最大相电流 浮点数 Maximum current Float 热过载跳闸 正序电流 [Thermal overload Trip] Positive sequence 浮点数 OverHeat.T current Float 负序电流 Negative sequence 浮点数 current Float 堵转保护 最大相电流 浮点数 [Blocking Rotor Maximum current Float StallTrip] 启动时间过长保护...
Page 61
Acrel Co., Ltd. Unb.V.T Unb.V 不平衡 I 不平衡电流保护 浮点数 [Unbalance Current Trip] Unbalance Current Float Unb.I.T Unb.I 重瓦斯跳闸 [Severe Gas Trip] —— —— —— SevereGas.T 压力释放跳闸 [Pressure Release Trip] —— —— —— Pre.Re.T 超温跳闸 [High Temperature Trip] —— —— ——...
Page 67
Acrel Co., Ltd. [I Bus Over Voltage Alarm] I Bus OVP.A Ⅰ母零序过压告警 (AM5\AM4-U1) 零序电压 浮点数 [I Bus Residual Over Voltage] Residual Voltage Float Alarm I Bus U0.OVP.A 轻瓦斯告警 [Light Gas Alarm] LightGasA 高温告警 [Over Temperature Alarm] OverTemp.A 非电量 2 告警...
Page 68
Acrel Co., Ltd. Float (AM5\AM4-U2) [II Bus PT Break Alarm] 浮点数 UBC2 II Bus PT BreakAla. Float 浮点数 UCA2 Float 负序电压 Negative sequence 浮点数 voltage Float Ⅱ母过电压告警 最大线电压 (AM5\AM4-U2) 浮点数 Maximum voltage [II Bus Over Voltage Alarm] Float II Bus OVP.A Ⅱ母自产零序过压告警...
Page 79
Acrel Co., Ltd. 遥控并列 [Remote Parallel] —— —— —— Remote Juxtaposition 遥控解列 [Remote Disconnection] —— —— —— Remote Splitting A 相电流 浮点数 Float 母线充电保护 [Bus Charge Trip] B 相电流 浮点数 B.Cha.T Float C 相电流 浮点数 Float CT 二次过压跳闸 [Secondary CT Over Voltage ——...
Page 80
Acrel Co., Ltd. [High oil Alarm] High oil.A 均无压跳母联 [Loss of Voltage Trip Bus] No-Vol.T.B. 负序电流 浮点数 负序过流二段跳闸 [Negative sequence Float Time-limited overcurrent] 最大相电流 浮点数 I2>> Maximum Current Float 差动总启动标志 —— —— —— [Differential total start flag] 动作时间 浮点数 Action time Float A 相差流...
Page 81
Acrel Co., Ltd. A 相制动 浮点数 Restraint IA Float B 相制动 浮点数 Restraint IB Float C 相制动 浮点数 Restraint IC Float A 相差流 浮点数 Differential IA Float B 相差流 差流越限 浮点数 [Differential current overshoot] Differential IB Float C 相差流 浮点数...
Page 82
Acrel Co., Ltd. 动作时间 浮点数 Action time Float 正序电流 Positive sequence 浮点数 current Float 计时门槛 浮点数 长启动保护告警 [Starting time-out Alarm Timing threshold Float Long start protection alarm] 动作时间 浮点数 Action time Float 定值 浮点数 Fixed value Float 电流不平衡告警 延时 浮点数...
Page 83
Acrel Co., Ltd. Float 零序电压 浮点数 Residual Voltage Float 定值 浮点数 Fixed value Float 延时 浮点数 Delayed Float 浮点数 零序过压保护告警 Float [Residual Over Voltage Alarm] 浮点数 U0.OVP.A Float 浮点数 Float 零序电压 浮点数 Residual Voltage Float 定值 浮点数 Fixed value Float 延时...
Page 84
Acrel Co., Ltd. 定值 浮点数 Fixed value Float 延时 浮点数 Delayed Float 浮点数 负序过压保护告警 Float [Negative Over Voltage Alarm] 浮点数 U2.OVP.A Float 浮点数 Float 负序电压 浮点数 Negative Voltage Float 定值 浮点数 Fixed value Float 延时 浮点数 Delayed Float 浮点数 负序过压保护跳闸...
Page 85
Acrel Co., Ltd. 浮点数 Float 浮点数 Float 相序保护告警 浮点数 [Incorrect Phase Sequence Float Voltage Alarm] 零序电压 浮点数 Ph.Se.A Residual Voltage Float 正序电压 浮点数 Positive Voltage Float 负序电压 浮点数 Negative Voltage Float 平均线电压 浮点数 Average Voltage Float Uavg 首端 CT 断线告警...
Page 91
Acrel Co., Ltd. Ib_H2 C 相二次谐波电流 浮点数 Ic Second Harmonic Float Ic_H2 A 相二次谐波电流 浮点数 Ia Second Harmonic Float Ia_H2 C 相二次谐波 B 相二次谐波电流 浮点数 [Ic Second Harmonic Block] Ib Second Harmonic Float C.SH. Ib_H2 C 相二次谐波电流 浮点数 Ic Second Harmonic...
Acrel Co., Ltd. Appendix D AM5-FT Anti-pumping AM5-FT anti-pumping is module that cooperate with AM series protection relay to achieve anti-pumping function of circuit breaker. Anti-pumping is divided into two types: AC/DC110V and AC/DC220V. When ordering, it is assumed to consistent with power supply (anti-pumping cannot be used under DC48V and DC24V, and it is recommended to use circuit breaker anti-pumping function).