ASJ series Residual Current Operated Relay Installation and Operation Manual V2.1 Acrel Co., Ltd.
Page 2
Declaration Please read this instruction carefully before using this product. All pictures, logos and symbols involved are owned by Acrel Co., Ltd. All or part of the content shall not be reproduced publicly without written authorization by non-company personnel. Please read the instructions and precautions in this operation manual carefully before using this series of products.
ASJ series residual current operated relay 1 Introduction ASJ series residual current operated relay can be combined with low voltage circuit breaker or low voltage contactor to form a residual current protection device, which is mainly used for the TT and TN system distribution lines with AC 50Hz and rated voltage of 690V and below.
A-type residual current measurement; Current percentage light column display; Rated residual operating current can be measured; ASJ20-LD1A Limit non-driving time can be set; Two sets of relay output (settable)note 1; With local and remote "test" and "reset" functions. Notes: 1. The function of setting for relay means that you can set the initialization and the output state of relay by yourself through the code dialing on the panel;...
Page 7
ASJ10 appearance dimensions ASJ10 installation dimensions The appearance and installation dimensions of ASJ10L-LD1A are shown in the figure below. (Unit: 35.5 4566 ASJ10L-LD1A appearance dimensions ASJ10L-LD1A installation dimensions The appearance and installation hole dimensions of the ASJ20 series are shown in the figure below. (Unit: mm) ASJ20 appearance dimensions ASJ20 opening dimensions...
Notes: 5.ASJ20 housing plus wiring terminals, the depth from panel to terminals is 106mm. 4.2 Installation Instructions 4.2.1 Installation Steps The ASJ10 series instrument is mounted on a guide rail, using a standard 35mm guide rail, as shown in the following figure. ASJ20 series instrument installation method is panel installation, both sides of the buckle extrusion fixed, the specific operation is as follows: (1) On the switchboard, choose the appropriate place to cut the 45*45mm...
Function Run light Work often light, communication light flashing Red indicator light, it lights when the leakage current Alarm light reaches the alarm value Acrel ASJ10 Disconnected Red indicator light, it lights when the external Alarm1 alarm light transformer is disconnected...
In programming mode, used to return to previous menu or mode In SOE page of operation mode, it is used to view the fault records; Td/- key In programming mode, it is used to enter next menu or subtract 1 from the value In SOE page of operation mode, it is used to view the fault records;...
Page 12
Reference value of leakage current of wires laid in pipes for 220/380V single-phase and three-phase lines (unit: mA/km) Wire cross-sectional area (mm Insulation material Rubber Leakage current reference value of motor Rated power of motor 18.5 (kW) Leakage current in normal operation 0.15 0.18 0.29 0.38 0.50 0.57 0.65 0.72 0.87 1.00 1.09 1.22 1.48 (mA)
The ASJ cannot be adopted. If the PEN line is not grounded repeatedly, when the shell is charged, the incoming and outgoing current of the transformer is equal, and the ASJ is not TN-C activated. If the PEN line is repeatedly system grounded, part of the single-phase current will flow into the repeated grounding.
Page 15
L-190*35(PB) 250~400 L-230*45(PB) 450~600 L-300*60(PB) 600~1000 Overall dimensions Hole size Installation dimensions Reference current (mm) (mm) (mm) Product model L-400*120(PB) 1000~1250 L-500*150(PB) 1500~2000 Explain: The current transformer with corresponding specifications should be selected according to the rated current of the circuit and the thickness of the wire. (If you have special requirements on the shape and range of the transformer, contact us) 11 / 19...
7 Programming Menu Chapters 7 and 8 apply only to ASJ10L-LD1A. First Menu Second Menu Third Menu Descriptions Addr 1~247 none Address setting 1200, 2400, 4800, none bAUd Communication Baud rate setting 9600, 19200, 38400 Select a modified bit modified bit Rated residual operating current setting AL.Pr Select a modified bit...
and Td/- key are used to switch channels between the second level menu, then press PROG key, use Td/+ key and Td/- key to modify the specific value. When you're done, press PROG or RESET to return. After the modification is completed, press RESET key to exit. Before exiting, you should choose whether to save or not.
Page 19
Running Long Press PROG PASS Press Td/- to modify, Press Td/+ to modify number, password confirm, press PROG Addr 0030mA 0030mA Press PROG Press Td/- Press Td/+ or Td/- Press Td/+ Press RESET Press PROG 50mA 0050mA Press RESET SAvE Press PROG Running (3)Set the limit non-driving time to 60ms.
Low byte Register High byte High byte data Low byte Number of registers Low byte Low byte Low byte check code High byte check code High byte 8.2.2 Function code 10H: Write the registers The function code 10H allows the user to change the contents of multiple registers, which can write the time and date in this meter.
40~44 28H~2CH Reserved UINT16*5 Alarm 10~30000mA UINT16 setting value Actual alarm 0-30000mA UINT16 value 30H High Year alarm time - year First UINT16 30H Low Month alarm time - month 31H High alarm time - day UINT16 31H Low Hour alarm time –...