AssistCall IP66 Call Plate
1 Product Overview
2 Installation
Document DViACCLW1001-03
The Assist Call ViAC-CLP-66 is a weatherproof call button, it is compatible with the
Lexicomm LX228 and Lexicomm Network range of panels and Assist Call
standalone 4 Zone and 1 zone controllers and the ViAC-RTK Remote kit.
This product can be used to replace a ViAC-CLP standard call button or it can be
used in place of a pull cord if agreed with all interested parties, note it only has
visual indication.
Typical applications are shower rooms, en-suite bathrooms and wet changing
areas.
This product has been tested to IP66 against dust particles and water jets when
installed appropriately in accordance with these instructions and with all seals
correctly positioned.
However, this product must not be immersed in
Please ensure that you read all this guide prior to commencing
1. The unit should be mounted on a clean, rigid vertical surface suitable to accept
screw fixings. The surface should be reasonably flat as unevenness could cause
product damage or affect operation.
2. Remove the product cover from the base by removing the 4 Allen screws
3. Remove the appropriate "cut out" suitable for your installation, ensuring that the
"cut out" hole is not distorted, is clean and free from burrs.
4. For side, top or rear entry the lowermost drain hole must be drilled out using a
5mm drill. ONLY one drain hole position must be drilled. For bottom entry a drain
hole MUST NOT be drilled in the rear box, but a a drain hole MUST be drilled at the
lowermost point of conduit run. For rear entry, remove rear knockout. For sealing
protection, a channel around the knockout is provided to accept a bead of sealant
(not supplied) when fixing to a mounting surface.
5. Mount the rear box using No 8 screws in all four, or at least two diagonal
positions on fixing centres shown. The fixing holes are slotted to enable some
rotation adjustment if required. Fit supplied bungs over all used fixing screw
positions to seal aperture recesses.
6. Make cable entry into rear of box as required. Only remove blank plugs for
required positions. Ensure adequate excess cable length for internal connections.
Install & seal all cable glands & conduit to manufacturer's instructions. Ensure the
gasket seal is properly fitted over front edge of rear box.
7. Connect the 2 cores to the Line + and 0 terminals there are 2 sets of 2-
Part/removable terminals they are not marked in or out, it does not matter which is
in or out, however polarity is important.
8.
If the device is the last device in the circuit, then the EOL resistor should be
fitted to the unused terminal if applicable (1 zone controllers do not have
monitored line circuits hence no EOL resistor).
9.
Refit the 4 screws
attaching
Product Manual
water.
the cover
assembly
to the
base.
installation.
Page 1 of 2

Advertisement

loading
Need help?

Need help?

Do you have a question about the AssistCall ViAC-CLP-66 and is the answer not in the manual?

Questions and answers

Summary of Contents for Vox Ignis AssistCall ViAC-CLP-66

  • Page 1 AssistCall IP66 Call Plate Product Manual 1 Product Overview The Assist Call ViAC-CLP-66 is a weatherproof call button, it is compatible with the Lexicomm LX228 and Lexicomm Network range of panels and Assist Call standalone 4 Zone and 1 zone controllers and the ViAC-RTK Remote kit. This product can be used to replace a ViAC-CLP standard call button or it can be used in place of a pull cord if agreed with all interested parties, note it only has visual indication.
  • Page 2 Vox Ignis Limited www.vox-ignis.com info@vox-ignis.com WEEE All information is believed to be correct at time of printing E&OE. Vox Ignis operate a policy of continuous improvement; always confirm specification details before purchase. Compliant Company Registration No: 8892407 info@vox-ignis.com Product Document DViACCLW1001-03...