GDS XDI win-15J Quick Start Manual

Toxic/oxygen gas sensor – transmitter

Advertisement

Quick Links

XDI
win
–15/30J
(
)
TOXIC/OXYGEN GAS SENSOR – TRANSMITTER
Electrochemical cells – Oxygen/Toxic gases
Transmitter: PCB 337 Issue Ev01 | Software version: V2.4.0 ➝ | Single magnet setup
Reference documents
C1 144 Equipment Installation Guidelines
C1770 Wiring & Terminations for Sensors and Panels
G973 Gas Sensor Locations
C1548 Aspirated Sensor
Sensors
The positioning of sensors depends upon the type of gas to be
monitored and its density with respect to air. See G973
Heavier than air gases
(Carbon Dioxide, Hydrogen Sulphide) –
locate at 15 to 20 cm from floor level.
Lighter than air gases
(Ammonia, Hydrogen Cyanide) –
locate at 5 to 10cm from the ceiling.
All equipment should be mounted away from direct heat and in
accordance with its IP rating.
Cell replacement / transmitter calibration
New sensors are supplied ready to connect to the system with all
jumpers inserted. This procedure shows how to recalibrate as part of
a routine maintenance or cell replacement.
1. If bench testing the PCB see section E3
2. Using a digital mV meter measure across test pins TP2/3 and
adjust Zero pot RV2 (course adjust) until LED D9 goes green for
4mA (zero) = 4mV
3. Apply a known test gas to the sensor (e.g. 100ppm CO for
200ppm range) for 1 minute at a flow rate of 1 litre to give a
12mA = 12mV across test pins TP2/3, adjust gain pot RV4 for
correct mV reading.
4. For display and relay set up see sections B or E
Fig. 1 Transmitter
TP1
J2
ov
ADD
(W)
J12
J4
Address
SOUNDER
OPTION
MUTE
D2
D3
Fault/Inhibit
Amber LED
CONTRAST
J22
RV2
ZERO
VR1
Zero Pot
(4mA)
J23
TP10
J16
J13
J15
SENSOR CELL
Insert jumper J16
when using Oxygen Cells
win
(
TEST
J24
(P)
(Y)
TP2
J3
SO SI
J6
TP3
RELAYS
EOL
MPU
Toxic/Oxygen
FLT
Can Sensor
PCB 337
D5
CAN
DISPLAY
J17
D10
USB
J7
JTAG
J11
GAIN
J14
J19
GAIN
J18
D9
J5 J19
RV4
GAIN
Gas Status LED
Gain Pot (20mA)
J18, J20
)
Setting/adjusting using display board
push buttons or single magnet
On power up the unit will be inhibited for a 120 second warm
up period displayed as a countdown on the display (this may
be overridden by pressing 1).
Carry out procedure A. To access the menu press 2 (equipment
SN will be displayed) followed by the entry code 231, pressing
1 or 3 will allow travel through the menu and adjustment of
settings, pressing 2 enables access into the selected menu field
and on completion pressing 2 will confirm your selection.
Menu
1. Exit
2. Inhibit – relays and 4~20mA signal output to 2mA
3. Address – CANbus sensor address (Combi)
4. Zero/span (fine adjust)
5. Alarm levels set – valve/direction (rising/falling)
6. Exit
7.
Delay to alarm (relays) 0~255s
8. Relay off delay 0~255s
Default setting 0 seconds
9. Normally energised/de-energised relays
A
Note: Set LED status jumpers on the display PCB
(when used) to match relay settings.
JP3 = A1
JP4 = A2
E = Energised
D = De-energised (default)
10. LED/relay test
1 1. Exit
12. Set 4 and 20mA output – calibrate
13. Display gas reading decimal point setting
14. Gas type selection
15. Gas range select
16. Exit
17. Dead band and delay
Display dead band
Signal delay
18. Relay operation select – relay 1, 2, 3
19. Software version / product serial number
20. Select mA down scale fault trip level (direct 4~20mA input
signla). Default setting 2.5mA
J9 + J10
(select sink/source)
4-20mA
(mV = mA)
Power supply
24vDC
15 to 30Vdc 24v nominal
Initial power ON – 120s inhibit warm up period
4-20mA Input
Outputs
3 wire 4~20mA (Direct)/4 wire CANbus (Addressable)
S
Logging
GDS Terminal
Connection
(Micro USB B)
Requires
Options
Technical Sheet C1882 Issue Cv2
0.5%  5% scale
5  30 seconds
Intervals – variable time
Roll over/stop
Storage – 2,880 readings
USB A to USB micro B cable
(GDS part No. 160-511)
PC or laptop (dedicated)
GDS Terminal
(download from GDS website)
3 Relays
SPCO 3A (none inductive) @ 30vDC
www.gds–technologies.co.uk
Doc No. 194D28C
B
C

Advertisement

loading
Need help?

Need help?

Do you have a question about the XDI win-15J and is the answer not in the manual?