GDS M1 Quick Start Manual

Combustible lel gas detector

Advertisement

Quickstart Guide
Model M1 Combustible (LEL) Gas Detector

INSTALLATION

Declassify the area to non-hazardous prior to installation by
monitoring for hazardous gases. Orient the sensor housing so
the sensor head is aimed down and mount securely. Use
conduit and installation practices approved for the area's
classification. When properly installed the M1 is rated for Class
1, DIV 1 & 2 Gr. B, C, D.

M1 WIRING

M1 wiring terminates behind the front display assembly;
removed by loosening the two captive thumbscrews. The M1 is
a 3-wire transmitter with +POWER, +4-20mA and GROUND
terminals on TB2 of the I/O board (at right). M1 power may
range between 19 – 30 volts. The 4-20mA signal sources
output current into loads up to 750 ohms (at nominal 24 VDC
power). Sensor wires attach to TB1 and are typically connected
at the factory unless a 10-0193 remote sensor mounting option
is included. See the M1 manual for wiring to options such as
ALARMS, RS-485 Modbus or ISOLATED 4-20mA.

INITIAL INSTALLATION POTENTIOMETER SETUP

The following procedure is performed at the factory but should be checked again at initial start-up. Uncontrolled
variables such as the remote mounting distance of the sensor (if equipped with this option) and "tinkering" with
potentiometers or jumper positions may require attention. After installation, this procedure should only need
repeating upon replacement of the sensor.
Apply M1 power and confirm 2-volts across TB1-R & A sensor terminals (monitor at SENSOR's location if a 10-
0193 remote sensor mounting option is included). Use the VOLTS potentiometer R11 to set. Seal R11's
adjustment screw with a small dollop of RTV or epoxy to prevent an accidental over-voltage condition at the
sensor.
Wait at least one hour for the M1 to stabilize. Place the M1 in CAL-MODE, then UNITY MODE as described in
the next section. SEE NEXT SECTION BEFORE PROCEEDING!
WITH ZERO GAS ON THE SENSOR, adjust BALANCE potentiometer R2 for a 0 reading on the LCD readout
(still attached by ribbon cable). Using the GDS Corp. CAL CUP with barbed hose fitting, apply approximately ½
liter per minute of 50% LEL SPAN gas to the sensor and wait for the reading to stabilize.
DO NOT ADJUST MAGNETIC CONTROLS YET! The M1 must be in UNITY mode to complete this step.
Confirm the LCD reads from 35 – 65 then proceed to ROUTINE CALIBRATIONS. If outside this window, move
JP1's shorting strip left to increase and right to decrease the reading. Note: Shorting strips may also be
combined on JP1 to provide additional GAIN combinations. For example, shorting strips in both positions 3 & 4
provide higher readings than 3 or 4 alone, but lower than one strip in position 2. JP1 shorting strips are correctly
set when 50% LEL applied to a NEW sensor, in UNITY mode, provide an LCD reading of 35-65.
GDS Corp.
2513 Hwy 646 Santa Fe, Texas 77510
www.gdscorp.com
TB2
Pwr./Sig.
CATALYTIC BEAD SENSORS
(409) 927-2980
info@gdscorp.com
VOUT TEST POINT
VOUT
P1
RIBBON CABLE
TO CPU ASSY.
U2
R
C
TB1
U1
Sensor
Balance
VOLTS
1
2
3
4
U3
R2
R11
JP1
Set 2 volts
U5
across A&R
U4
M1/LEL I/O PCB FOR
(409) 927-4180 fax
A

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the M1 and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for GDS M1

  • Page 1 RTV or epoxy to prevent an accidental over-voltage condition at the sensor. Wait at least one hour for the M1 to stabilize. Place the M1 in CAL-MODE, then UNITY MODE as described in the next section. SEE NEXT SECTION BEFORE PROCEEDING! WITH ZERO GAS ON THE SENSOR, adjust BALANCE potentiometer R2 for a 0 reading on the LCD readout (still attached by ribbon cable).
  • Page 2 1). This allows viewing of the unconditioned signal from the I/O board’s bridge circuit on the LCD. However, remember negative readings may only be viewed in CAL-MODE. At all other times the M1 suppresses negative readings to 0 until –10% is exceeded causing a FAULT indication.

Table of Contents