Page 1
41 / 48 / 55 Split Air-to-Water Heat Pump Application Guide • Installation • Startup This manual must only be used by a qualified heating installer/service technician. Read all instructions, including this manual and all other information shipped with the boiler, before installing. Perform steps in the order given. Failure to comply could result in severe personal injury, death or substantial property damage.
HP Heat Pump – Application Guide Overview Configuration Steps / Walk-Through It is important to follow the below setup process to best configure your installation. General Piping: Verify all piping is configured and installed correctly. System Type: Verify system type to properly setup controls.
Page 4
HP Heat Pump – Application Guide This page intentionally left blank. Part Number 550-100-588/1224...
HP Heat Pump – Application Guide Section 1 Safety Hazard Definitions The following defined terms are used throughout this guide to bring attention to the presence of hazards of various risk levels or to important information concerning the life of the product. Indicates presence of hazards that will cause severe personal injury, death or substantial property damage.
HP Heat Pump – Application Guide Please Read Before Proceeding This guide provides system application information only. It must be used only as a supplement to the Eco HP Heat Pump manual and applicable code requirements. Before using this guide, refer to and follow all instructions in the HP IDU and ODU Manuals for initial installation.
General Piping Requirements Easy Up Manifold The Eco HP must always be piped in an isolation loop Weil-McLain offers an Easy-Up Manifold Kit that includes off of system distribution piping. Additionally, a heat trap near Eco HP piping and system secondary connection.
HP Heat Pump – Application Guide General Piping (continued) Fabricated Manifold If the WM Easy-Up Manifold is not used the following requirements must be met for an installer-built manifold: y A heat trap height of at least 2 inches for both the inlet and outlet. A Y-Strainer with 80 mesh screen on the inlet (Y-Strainer must be oriented where flow direction is down or horizontal) y The heat pump circulator can be place anywhere in the heat pump isolation loop provided its orientation complies with the circulator manufacturer’s installation guidelines.
HP Heat Pump – Application Guide General Piping (continued) Heat Pump/Boiler Piping Order HP Upstream of Boiler HP - ON System System Supply Return BOILER - ON Boiler Boiler Supply Return Supply Return HP - ON System System Supply BOILER - OFF Return Boiler Boiler...
HP Heat Pump – Application Guide System Type System Type A: WM Boiler w/ Unity 2 .0 & WM Heat Pump Figure 3 System Type A - Boiler (Master); Eco HP (Shadow) System Type A Boiler (Master); Heat Pump (Shadow) Unity 2.0 boilers connect up to 4 zone inputs and 4 configurable outputs* ECO HP Unity 2.0 Boiler...
HP Heat Pump – Application Guide System Type (continued) System Type B: WM Heat Pump & any Boiler with a Thermostat Input Figure 4 System Type B - Eco HP (Master); Boiler (Shadow) System Type B ECO HP (Master); Boiler (Shadow) Domestic - Priority Thermostat Interface Unit (Zone Panel)
HP Heat Pump – Application Guide System Type (continued) System Type C: HP Only and Multi-HP Figure 5 System Type C - Eco HP Solo System Type C ECO HP Solo Input 1 Thermostat Interface Unit (Zone Panel) ECO HP (Indoor Unit) Input 2 120V...
• System fluid (water or glycol mix) • Piping • Circulators Contact Weil-McLain for access to this tool as well as sizing and application support. The outdoor reset curves will including the following temperatures: • maximum water flow temperature •...
HP Heat Pump – Application Guide General Control Settings (HP, Boiler, TIU) (continued) FOR SERVICEMAN Mode Figure 6 Home Screen Figure 8 Entering serviceman menu Leftward Upward Press and hold 'Menu' (≡) and 'Rightward' (>) simultaneously Menu / Return ON / OFF for 3 seconds to enter the authorization page.
HP Heat Pump – Application Guide General Control Settings (HP, Boiler, TIU) (continued) Table 1 Heating Setting menu parameters Code State Default Minimum Maximum Unit Interval Enable or Disable the heating mode. Heating Mode* 0=NO, 1=YES t_T4_Fresh_H The refresh time of climate related curves in heating mode 0 .5 0 .5 0 .5...
HP Heat Pump – Application Guide General Control Settings (HP, Boiler, TIU) (continued) Room Thermostat Other Heat Source Figure 12 Room Thermostat Setting Figure 13 Heating and DHW Inputs may be paired with dry contacts only. 24Vac Thermostats require using the provided Thermostat Code State Interface Unit or a control device with end switches rated...
HP Heat Pump – Application Guide General Control Settings (HP, Boiler, TIU) (continued) Heat Pump Control Schematic Figure 14 Heat Pump Control Schematic High Voltage: Disconnect all power before servicing or installing this unit. Multiple power sources may be present. Failure to do so may cause property damage,personal injury,or death. 16010600A10031 2024.07.24 WARNING...
ODT and Target the usage of standard 24V thermostats with the WM ECO Temp mode. HP. Weil-Mclain offers a zone valve TIU (Taco ZVC404-5) and a zone circulator TIU (Taco SR503-5) AHD ODT Mode...
HP Heat Pump – Application Guide System Type A Application A1: Multi-zone space heating, DHW as zone If boiler will run concurrently with the heat pump, boiler must be downstream from heat pump to prevent high return water temperatures . Overview •...
HP Heat Pump – Application Guide System Type A (continued) Application A1: Multi-zone space heating, DHW as zone (continued) Application Piping Legend 15 . Return temperature sensor. 26 . Zone Valves. Boiler. Y-Strainer with 80 mesh screen. 16 . Supply temperature sensor. 27 .
HP Heat Pump – Application Guide System Type A (continued) Application A1: Multi-zone space heating, DHW as zone (continued) Application Wiring Figure 17 Application A1: Multi-zone space heating, DHW as zone Application Wiring BLACK WHITE To AHD 2 (Heating) To AHD 1 (DHW) C1 C1 C1 C1 C1 C1 C1...
Page 23
HP Heat Pump – Application Guide System Type A (continued) Application A1: Multi-zone space heating, DHW as zone (continued) Application Wiring (continued) Figure 18 Application A1: Multi-zone space heating, DHW as zone Application Wiring Zone Thermostat 4 Zone AHD 2 Thermostat 3 eating) Zone...
HP Heat Pump – Application Guide System Type A (continued) Application A1: Multi-zone space heating, DHW as zone (continued) Control Settings Boiler (Master) Configuration After entering the contractor menu, ensure the settings in the following sub-menus are set as noted. System Settings INPUT/OUTPUT 1 INPUT/OUTPUT 2...
Page 25
HP Heat Pump – Application Guide System Type A (continued) Application A1: Multi-zone space heating, DHW as zone (continued) Control Settings (continued) HP (Shadow) Configuration See pg XX-YY for basic settings and navigation Weather Temp . Settings T1SetH1 Per ECOCalc T1SetH2 Per ECOCalc T4H1...
HP Heat Pump – Application Guide System Type A (continued) Application A2: Multi-zone Space Heating, Boiler only DHW Overview • Two zones for space heating, zoned with circulators, through the WM Unity 2.0 controlled boiler. • DHW provided by ECO Tec Combi. •...
HP Heat Pump – Application Guide System Type A (continued) Application A2: Multi-zone Space Heating, Boiler only DHW (continued) Application Piping Legend 15 . Return temperature sensor. 26 . Zone Valves. Boiler. Y-Strainer with 80 mesh screen. 16 . Supply temperature sensor. 27 .
HP Heat Pump – Application Guide System Type A (continued) Application A2: Multi-zone Space Heating, Boiler only DHW (continued) Application Wiring Figure 20 Application A2: Multi-zone Space Heating, Boiler only DHW Application Wiring BLACK WHITE To AHD 2 (Heating) C1 C1 C1 C1 C1 C1 C1 class2 WHITE...
Page 29
HP Heat Pump – Application Guide System Type A (continued) Application A2: Multi-zone Space Heating, Boiler only DHW (continued) Application Wiring (continued) Figure 21 Application A2: Multi-zone Space Heating, Boiler only DHW Application Wiring Zone AHD 2 Thermostat 3 eating) Zone Thermostat 2 AHD 1...
HP Heat Pump – Application Guide System Type A (continued) Application A2: Multi-zone Space Heating, Boiler only DHW (continued) Control Settings Boiler (Master) Configuration After entering the contractor menu, ensure the settings in the following sub-menus are set as noted. System Settings INPUT/OUTPUT 2 INPUT/OUTPUT 3...
Page 31
HP Heat Pump – Application Guide System Type A (continued) Application A2: Multi-zone Space Heating, Boiler only DHW (continued) Control Settings (continued) HP (Shadow) Configuration See pg XX-YY for basic settings and navigation Weather Temp . Settings T1SetH1 Per ECOCalc T1SetH2 Per ECOCalc T4H1...
HP Heat Pump – Application Guide System Type B Application B1: Multi-zone space heating DHW as zone, boiler direct piped Overview • Two zones for space heating, zoned with circulators, through the TIU. • One zone for DHW, zoned with circulators, through the TIU. •...
HP Heat Pump – Application Guide System Type B (continued) Application B1: Multi-zone space heating DHW as zone, boiler direct piped (continued) Application Piping Legend 14 . Unions as needed for service. 26 . Zone Valves. Boiler. Y-Strainer with 80 mesh screen.
HP Heat Pump – Application Guide System Type B (continued) Application B1: Multi-zone space heating DHW as zone, boiler direct piped (continued) Application Wiring Figure 23 Application B1: Multi-zone space heating DHW as zone, boiler direct piped Application Wiring BLACK WHITE To TIU Main End Switch...
Page 35
HP Heat Pump – Application Guide System Type B (continued) Application B1: Multi-zone space heating DHW as zone, boiler direct piped (continued) Application Wiring (continued) Figure 24 Application B1: Multi-zone space heating DHW as zone, boiler direct piped Application Wiring (SR-503-5) rity 120Vac...
HP Heat Pump – Application Guide System Type B (continued) Application B1: Multi-zone space heating DHW as zone, boiler direct piped (continued) Control Settings HP (Master) Configuration See pg XX-YY for basic settings and navigation Weather Temp . Settings T1SetH1 Per ECOCalc T1SetH2 Per ECOCalc...
Page 37
HP Heat Pump – Application Guide This page intentionally left blank. Part Number 550-100-588/1224...
HP Heat Pump – Application Guide System Type B (continued) Application B2: Multi-zone space heating DHW as zone - Primary/ Secondary Overview • Two zones for space heating, zoned with circulators, through the TIU. • One zone for DHW, zoned with circulators, through the TIU. •...
HP Heat Pump – Application Guide System Type B (continued) Application B2: Multi-zone space heating DHW as zone - Primary/ Secondary (continued) Application Piping Legend 14 . Unions as needed for service. 26 . Zone Valves. Boiler. Y-Strainer with 80 mesh screen.
HP Heat Pump – Application Guide System Type B (continued) Application B2: Multi-zone space heating DHW as zone - Primary/ Secondary (continued) Application Wiring Figure 26 Application B2: Multi-zone space heating DHW as zone - Primary/Secondary Application Wiring BLACK WHITE To TIU Main End Switch (Heating)
Page 41
HP Heat Pump – Application Guide System Type B (continued) Application B2: Multi-zone space heating DHW as zone - Primary/ Secondary (continued) Application Wiring (continued) Figure 27 Application B2: Multi-zone space heating DHW as zone - Primary/Secondary Application Wiring o TIU Main End Switch (Heating) (SR-503-5)
HP Heat Pump – Application Guide System Type B (continued) Application B2: Multi-zone space heating DHW as zone - Primary/ Secondary (continued) Control Settings Boiler (Shadow) Configuration After entering the contractor menu, ensure the settings in the following sub-menus are set as noted. System Settings PRIORITY 2 System Type...
Page 43
HP Heat Pump – Application Guide This page intentionally left blank. Part Number 550-100-588/1224...
HP Heat Pump – Application Guide System Type B Application B3: Multi-zone Space Heating boiler only DHW Overview • Three zones for space heating, zoned with circulators, through the TIU. • One zone for DHW, direct piped with circulator, through boiler. •...
HP Heat Pump – Application Guide System Type B Application B3: Multi-zone Space Heating boiler only DHW (continued) Application Piping Legend 14 . Unions as needed for service. 26 . Zone Valves. Boiler. Y-Strainer with 80 mesh screen. 27 . Bypass pressure regulator 2 .
HP Heat Pump – Application Guide System Type B (continued) Application B3: Multi-zone Space Heating boiler only DHW (continued) Application Wiring Figure 29 Application B3: Multi-zone Space Heating boiler only DHW Application Wiring BLACK WHITE To TUI Main End Switch (Heating) C1 C1 C1 C1 C1 C1 C1...
Page 47
HP Heat Pump – Application Guide System Type B (continued) Application B3: Multi-zone Space Heating boiler only DHW (continued) Application Wiring (continued) Figure 30 Application B3: Multi-zone Space Heating boiler only DHW Application Wiring Priority On dipswitch must be set to OFF TUI Main nd Switch Heating)
HP Heat Pump – Application Guide System Type B (continued) Application B3: Multi-zone Space Heating boiler only DHW (continued) Control Settings Ultra Boiler (Shadow) Configuration After entering the contractor menu, ensure the settings in the following sub-menus are set as noted . System Settings PRIORITY 1 System Type...
Page 49
HP Heat Pump – Application Guide System Type B (continued) Application B3: Multi-zone Space Heating boiler only DHW (continued) Control Settings (continued) HP (Master) Configuration See pg XX-YY for basic settings and navigation Weather Temp . Settings T1SetH1 Per ECOCalc T1SetH2 Per ECOCalc T4H1...
HP Heat Pump – Application Guide System Type C Application C1: Multi-zone Space Heating Overview • Three zones for space heating, zoned with circulators, through the TIU. ECO HP Control Settings • See table on page 54 for heat pump control settings. •...
HP Heat Pump – Application Guide System Type C (continued) Application C1: Multi-zone Space Heating (continued) Application Piping Legend 9 . Air separator. 27 . Bypass pressure regulator Relief valve, supplied with 17 . HP Heat Pump boiler and heat pump, field 10 .
HP Heat Pump – Application Guide System Type C (continued) Application C1: Multi-zone Space Heating (continued) Application Wiring Figure 32 Application C1: Multi-zone Space Heating Application Wiring BLACK WHITE To TUI Priority End Switch (Heating) C1 C1 C1 C1 C1 C1 C1 class2 WHITE BLACK...
Page 53
HP Heat Pump – Application Guide System Type C (continued) Application C1: Multi-zone Space Heating (continued) Application Wiring (continued) Figure 33 Application C1: Multi-zone Space Heating Application Wiring Priority On dipswitch must be set to OFF ority (SR-503-5) 120Vac Input Zone Circ Zone Circ Zone Circ...
HP Heat Pump – Application Guide System Type C (continued) Application C1: Multi-zone Space Heating (continued) Control Settings HP (Master) Configuration See pg XX-YY for basic settings and navigation Weather Temp . Settings T1SetH1 Per ECOCalc T1SetH2 Per ECOCalc T4H1 Per ECOCalc T4H2 Per ECOCalc...
Page 55
HP Heat Pump – Application Guide This page intentionally left blank. Part Number 550-100-588/1224...
HP Heat Pump – Application Guide System Type C (continued) Application C2: Multi-zone Space Heating Overview • Multiple zones zones for space heating only, zoned with zone valves, end switches wired to the HP. ECO HP Control Settings • See table on page 59 for heat pump control settings. •...
HP Heat Pump – Application Guide System Type C (continued) Application C2: Multi-zone Space Heating (continued) Application Piping Legend 9 . Air separator. 27 . Bypass pressure regulator Relief valve, supplied with 17 . HP Heat Pump boiler and heat pump, field 10 .
HP Heat Pump – Application Guide System Type C (continued) Application C2: Multi-zone Space Heating (continued) Application Wiring Figure 35 Application C2: Multi-zone Space Heating Application Wiring BLACK WHITE Zone valve end switches C1 C1 C1 C1 C1 C1 C1 class2 If System Circ draws more System Circ...
HP Heat Pump – Application Guide System Type C (continued) Application C2: Multi-zone Space Heating (continued) Control Settings HP (Master) Configuration See pg XX-YY for basic settings and navigation Weather Temp . Settings T1SetH1 Per ECOCalc T1SetH2 Per ECOCalc T4H1 Per ECOCalc T4H2 Per ECOCalc...
HP Heat Pump – Application Guide System Type C (continued) Application C3: Multi-zone space heating DHW as zone Overview • Two zones for space heating, zoned with circulators, through the TIU. • One zone for DHW, direct piped with circulator, through the TIU. •...
HP Heat Pump – Application Guide System Type C (continued) Application C3: Multi-zone space heating DHW as zone (continued) Application Piping Legend 2 . Indirect water heater, if used 13 . Heat trap. 26 . Zone Valves. Y-Strainer with 80 mesh (domestic water piping not screen.
HP Heat Pump – Application Guide System Type C (continued) Application C3: Multi-zone space heating DHW as zone (continued) Application Wiring Figure 37 Application C3: Multi-zone space heating DHW as zone Application Wiring BLACK WHITE To TUI Main End Switch (Heating) To TUI Priority End Switch...
Page 63
HP Heat Pump – Application Guide System Type C (continued) Application C3: Multi-zone space heating DHW as zone (continued) Application Wiring (continued) Figure 38 Application C3: Multi-zone space heating DHW as zone Application Wiring I Main Switch ting) (SR-503-5) Priority Switch 120Vac Input...
HP Heat Pump – Application Guide System Type C (continued) Application C3: Multi-zone space heating DHW as zone (continued) Control Settings HP (Master) Configuration See pg XX-YY for basic settings and navigation Weather Temp . Settings T1SetH1 Per ECOCalc T1SetH2 Per ECOCalc T4H1 Per ECOCalc...
HP Heat Pump – Application Guide Section 4 Commissioning/Troubleshooting VERIFY PROPER OPERATION AFTER SERVICING Please reference the Eco HP IDU manual Hardness less than 7 grains and the relevant boiler manuals for specific 1 . Consult local water treatment companies for unusually startup instructions .
Purge Air from Water System for use in Weil-McLain heat pump. Do not apply these products or instructions for other applications. Local 1 . Connect a hose to the system purge valve. Route hose codes may require a back flow preventer or actual to an area where water can drain and be seen.
Page 67
Add additional inhibitor if necessary. Verify Flow Rate Through Eco 4 . See separate instructions or weil-mclain.com for 1 . Check the hydraulic configuration to find out the space suggested guidelines to determine how much inhibitor heating loops that can be closed by mechanical, to use.
HP Heat Pump – Application Guide General Commissioning Troubleshooting (continued) 2 . For system Type B applications This section provides useful information for diagnosing and correcting certain troubles which may occur in the a . Provide a thermostat call to test. The Eco unit.
HP Heat Pump – Application Guide Error Codes Error Code Description Notes Transducer module temperature too high protection. Verify circulator is operating and there Water flow failure (E8 appears 3 times) is no air in the system Phase sequence error (for 3phase models) Not applicable to the Eco Verify wiring connections are secure Communication error between the main control board of the hydraulic...
Page 70
HP Heat Pump – Application Guide Error Codes (continued) Error Code Description Notes H6 appears 10 times in 120min Low pressure protection (pressure < 0.6MPa for 3 times in one hour) Low pressure protection High pressure protection Compressor current protection Discharge temperature sensor Tp protection High temperature difference between water side heat exchanger water inlet and water outlet temperatures protection...
Page 71
HP Heat Pump – Application Guide Error Codes (continued) Symptom 2: The unit is turned on but the compressor is not starting (space heating or domestic water heating) POSSIBLE CAUSES CORRECTIVE ACTION In case of low water temperature, the system utilizes the AHS to reach the minimum water temperature first (54 °F).
Page 72
HP Heat Pump – Application Guide Error Codes (continued) Symptom 7: Heat mode can’t change to DHW mode immediately POSSIBLE CAUSES CORRECTIVE ACTION Check whether there is a problem with the DHW wiring and whether The heat pump does not receive the control signal DHW=ON the DHW=ON signal can be sent correctly.
HP Heat Pump – Application Guide EcoCalc Value Records Parameter Description Priority 1 Priority 2 Priority 3 WWSD Temp Max outdoor temperature heating will operate Outdoor Temperature Min outdoor temperature HP will operate Setpoint Target Crossover Temp Max Target Temperature HP will operate AHD Assign Contact AHD Contact used for Priority Order AHD contact will activate, 1st (contacts close immediately with call for heat), 2nd...