AIR CONDITIONER (SPLIT TYPE) Installation Manual Outdoor Unit Model name: For commercial use RAV-GP1101AT8-E RAV-GP1101AT8J-E RAV-GP1401AT8-E1 RAV-GP1401AT8J-E1 RAV-GP1601AT8-E RAV-GP1601AT8J-E English...
Original instruction Contents ADOPTION OF R32 REFRIGERANT This air conditioner adopts the HFC refrigerant (R32) which does not destroy the ozone layer. PRECAUTIONS FOR SAFETY ....... . 5 This outdoor unit is designed exclusively for use with R32 refrigerant.
Thank you for purchasing this Toshiba air conditioner. Qualified • The qualified service person is a person who installs, repairs, maintains, relocates and Please read carefully through these instructions including important information which complies with the “Machinery service removes the air conditioners made by Carrier Japan Corporation. He or she has been trained Directive”...
Definition of Protective Gear These safety cautions describe important matters concerning safety to prevent injury to users or other people and damages to property. Please read through this manual after understanding the contents below (meanings of When the air conditioner is to be transported, installed, maintained, repaired or removed, wear protective gloves and indications), and be sure to follow the description.
Warning Indications on the Air Conditioner Unit This mark is for R32 refrigerant only. Refrigerant type is written on nameplate of CAUTION outdoor unit. CAUTION WARNING In case that refrigerant type is R32, this unit uses a flammable refrigerant. (Risk of fire) If refrigerant leaks and comes in contact with fire or heating part, it will create Do not touch the aluminum...
PRECAUTIONS FOR SAFETY • Before carrying out the installation, maintenance, repair or removal work, be sure to set the circuit breaker to the OFF position. Otherwise, electric shocks may result. The manufacturer shall not assume any liability for the damage caused •...
About the refrigerant Selection of installation location • This product contains fluorinated greenhouse gases. • If you install the unit in a small room, take appropriate measures to • Do not vent gases to the atmosphere. prevent the refrigerant from exceeding the limit concentration even if it •...
• Follow the instructions in the Installation Manual to install the air Electrical wiring conditioner. Failure to follow these instructions may cause the product • Only a qualified installer(*1) or qualified service person(*1) is allowed to fall down or topple over or give rise to noise, vibration, water to carry out the electrical work of the air conditioner.
Page 9
Test run Explanations given to user • Before operating the air conditioner after having completed the work, • Upon completion of the installation work, tell the user where the circuit check that the electrical parts box cover of the indoor unit and service breaker is located.
Page 10
To disconnect the appliance from main power supply CAUTION • This appliance must be connected to the main power supply by means This air conditioner adopts the HFC refrigerant (R32) which does of a switch with a contact separation of at least 3 mm. not destroy the ozone layer Do not wash air conditioners with pressure washers.
ACCESSORY PARTS INSTALLATION OF R32 REFRIGERANT AIR CONDITIONER Part name Q’ty Shape Usage CAUTION Hand this directly to the customer. (For other languages that do not appear in this Installation manual R32 refrigerant air conditioner installation Installation Manual, please refer to the enclosed •...
Installation Location Earthing • A location where high-frequency equipment (including Consider the wind direction during the inverter equipment, private power generator, medical operational season of the air conditioner, and equipment, and communication equipment) is used install the unit so that the discharge port is set WARNING WARNING (Installation in such a location may cause malfunction...
Page 14
Necessary Space for Installation (Unit: mm) Serial unit installation * When the outdoor temperature is high, the cooling capability may be decreased because of an equipment protection operation. Single unit installation When there is an obstacle on the When there are obstacles on the When there is an obstacle on the back side back and top sides...
REFRIGERANT PIPING Installation of Outdoor Unit Set the out margin of the anchor bolt to 15 mm or less. • Before installation, check the strength and horizontalness of the base so that abnormal sounds 15 or less do not emanate. ...
Refrigerant Piping Connection Projection margin in flaring: B (Unit: mm) Supplied protective bush CAUTION Take note of these 4 important points below for piping work Rigid (Clutch type) Keep dust and moisture away from inside the connecting pipes. Outer dia. of R32 or R410A Conventional Supplied passage hole guard material...
Page 17
Tightening of Connecting Part Refrigerant Pipe Length CAUTION Align the centers of the connecting pipes and fully Single tighten the flare nut with your fingers. Then fix the • Do not put the crescent wrench on the cap or cover. nut with a wrench as shown in the figure and tighten Allowable pipe length (m) Height difference (Indoor-outdoor H) (m)
AIR PURGING Vacuum pump Use the vacuum pump, vacuum pump adapter, and gauge manifold correctly referring to the manuals supplied with each tool before using them. Check that the vacuum pump oil is filled up to the specified As shown in the figure, connect the charge hose after line of the oil gauge.
Replenishing Refrigerant Charging additional refrigerant Groove position This model is a 30 m chargeless type that does not need Figure of Single Figure of Simultaneous twin Figure of Simultaneous triple to have its refrigerant replenished for refrigerant pipes up Indoor Unit Indoor Unit Indoor Unit...
To Fix the Fluorinated Gas leak inspection Fill in the label as follows: Greenhouse Gases Label Indoor unit inspection locations Use a leak detector manufactured specially for HFC refrigerant (piping connections) (R32, R410A, R134a, etc.) to perform the R32 gas leak inspection. This product contains fluorinated greenhouse gases.
ELECTRICAL WORK Wiring between Indoor Unit and Outdoor Unit The dashed lines show on-site wiring. Outdoor unit Indoor unit • Remove the service panel, and the terminal cover. Wired remote controller WARNING • A conduit pipe can be installed through the hole for Input power wiring.
How to wire Wiring diagram Connect the connecting wire to the terminal as * For details on the remote controller wiring/installation, refer to the Installation Manual enclosed with the remote identified with their respective numbers on the controller. terminal block of the indoor and outdoor units. H07 RN-F or 60245 IEC 66 (1.5 mm or more) Single system...
EARTHING Stripping length power cord and connecting wire Indoor/outdoor Power supply wire connecting wire Earth Earth 1 2 3 L1 L2 L3 N screw screw WARNING Be sure to connect the earth wire. (Grounding work) Incomplete earthing may cause an electric shock. (mm) Earth line Earth line...
ANNUAL MAINTENANCE • The existing pipe must have a wall thickness equal to or larger than the following thicknesses. Reference outside Wall thickness (mm) Material diameter (mm) – For an air conditioning system that is operated on a regular basis, cleaning and maintenance of the indoor/outdoor units are strongly recommended.
TROUBLESHOOTING APPENDIX [1] Existing piping You can perform fault diagnosis of the outdoor unit with the LEDs on the P.C. board of the outdoor unit in addition to * Pipe diameter and thickness (mm) using the check codes displayed on the wired remote controller of the indoor unit. Reference Use the LEDs and check codes for various checks.
Page 26
Connect the indoor/outdoor units to the existing pipe. • Use a flare nut attached to the main unit for the In the concurrent twin system, when TOSHIBA has indoor/outdoor units. (Do not use the flare nut of the specified that branching pipe is to be used, it can be existing pipe.)
Page 27
[2] Minimum floor area: Amin (m Total Floor Wall Ceiling refrigerant standing mounted mounted Piping length quantity* unit unit unit M (kg) 58.00 6.44 4.31 2.64 59.80 6.64 4.45 2.68 61.63 6.85 4.58 2.72 63.48 7.05 4.72 2.76 65.36 7.26 4.86 67.27 7.47...
Generic Denomination: Air Conditioner Product information of ecodesign requirements. (Regulation (EU) 2016/2281) http://ecodesign.toshiba-airconditioning.eu/en Model/type: RAV-GP1101AT8-E, RAV-GP1401AT8-E1, RAV-GP1601AT8-E RAV-GP1101AT8J-E, RAV-GP1401AT8J-E1, RAV-GP1601AT8J-E Commercial name: Super Digital Inverter Series Air Conditioner Complies with the provisions of the “Machinery Directive” (Directive 2006/42/EC) and the regulations transposing...
Generic Denomination: Air Conditioner Total amount of refrigerant (kg) ≤ Concentration limit (kg/m Model/type: RAV-GP1101AT8-E, RAV-GP1401AT8-E1, RAV-GP1601AT8-E Min. volume of the indoor unit installed room (m RAV-GP1101AT8J-E, RAV-GP1401AT8J-E1, RAV-GP1601AT8J-E Refrigerant Concentration Limit shall be in accordance with local regulations. Commercial name:...