Download Print this page
GE NCUC 5S Series Installation Instructions Manual
GE NCUC 5S Series Installation Instructions Manual

GE NCUC 5S Series Installation Instructions Manual

R-454b indoor vertical upflow coils

Advertisement

Quick Links

INSTALLATION INSTRUCTIONS
This manual must be left with the homeowner for future reference
Refrigerant Detection System Control (27A05) must be
ordered . RDS system requires 3 VA additional loading
on low voltage transformer.
Improper installation, adjustment, alteration, service
or maintenance can cause property damage, personal
injury or loss of life. Installation and service must be
performed by a licensed professional HVAC installer or
equivalent, service agency, or the gas supplier.
The Clean Air Act of 1990 bans the intentional venting of
refrigerant (CFCs, HCFCs and HFCs) as of July 1, 1992.
Approved methods of recovery, recycling or reclaiming
must be followed. Fines and/or incarceration may be
levied for noncompliance.
As with any mechanical equipment, contact with sharp
sheet metal edges can result in personal injury. Take
care while handling this equipment and wear gloves and
protective clothing.
The installation guidelines in this document are based on
Appliance Park
Louisville, KY 40225
508450G01 / 31-5000969
Releasing Air Charge .....................................................3
Installation .....................................................................3
Refrigerant Line Connections ........................................5
Blower Speed Selection ................................................9
Maintenance ................................................................10
Decommissioning ........................................................ 11
The NCUC*5S coil includes an externally equalized
factory-installed R-454B check/expansion valve and a
factory-installed R-454B refrigerant leak detection sensor.
The coil drain pan has a maximum service temperature
of 500°F. The drain pan must be at least 2" away from a
exchanger. Closer spacing may damage the drain pan
and cause a leak.
handlers and line sets.
These instructions are intended as a general guide and
do not supersede local or national codes in any way.
Authorities who have jurisdiction should be consulted
before installation.
Special procedures are required for
cleaning the aluminum coil in this unit. See page 10 in this
instruction for information.
Package 1 of 1 contains:
1 - Line set joint sleeve kit
Liquid line sleeve (1)
Suction line sleeve (1)
Band clamps (3)
Suction line insulation tape (1)
Check the components for shipping damage; if found,
immediately contact the last carrier.
NOTE - This unit NCUC*5S is a PARTIAL UNIT AIR CON-
DITIONER, complying with PARTIAL UNIT requirements
of this Standard, and must only be connected to other
sponding PARTIAL UNIT requirements of this Standard,
UL 60335-2-40/CSA C22.2 No. 60335-2-40, or UL 1995/
CSA C22.2 No 236.
Partial units shall only be connected to an appliance
suitable for the same refrigerant.
Issue 2431
(P) 508450G01
Page 1 of 12

Advertisement

loading
Need help?

Need help?

Do you have a question about the NCUC 5S Series and is the answer not in the manual?

Questions and answers

Summary of Contents for GE NCUC 5S Series

  • Page 1 INSTALLATION INSTRUCTIONS This manual must be left with the homeowner for future reference Releasing Air Charge .............3 Installation ..............3 Refrigerant Line Connections ........5 Blower Speed Selection ..........9 Maintenance ..............10 Decommissioning ............11 The NCUC*5S coil includes an externally equalized factory-installed R-454B check/expansion valve and a factory-installed R-454B refrigerant leak detection sensor.
  • Page 2 • Do not use means to accelerate the defrosting pro- Leak Detection System installed. Unit must be powered except for service. cess or to clean, other than those recommended by the manufacturer. • The appliance shall be stored in a room without con- tinuously operating ignition sources (for example: For duct connected appliances, false ceilings or drop ceilings may be used as a return air plenum if a...
  • Page 3 the charging area. • No person carrying out work in relation to a refrigerating To prevent serious injury or death: system which involves exposing any pipe work shall 1. Lock-out/tag-out before performing maintenance. use any sources of ignition in such a manner that it may 2.
  • Page 4 that could compromise safety, then no electrical supply shall be connected to the circuit until it is satisfactorily be achieved by breaking the vacuum in the system dealt with. If the fault cannot be corrected immediately but it is necessary to continue operation, an adequate the working pressure is achieved, then venting to temporary solution shall be used that is reported to the owner of the equipment, so all parties are advised.
  • Page 5 2 - Determine the refrigerant suction line size. For If replacement parts are necessary, order kit 69J46. The end of the larger line set joint sleeve accordingly to kit includes: • 10 - Brass nuts for liquid line assemblies • •...
  • Page 6 NOTE - When installing refrigerant lines longer than 50 various parts of the system. Make sure that cylinders feet, see the GE Refrigerant Piping Design and Fab- are situated on the scales before recovery takes place. rication Guidelines, or contact GE Technical Support Start the recovery machine and operate in accordance Product Applications for assistance.
  • Page 7 and the relevant waste transfer note arranged. Do not 1 - Using the insulation provided, wrap the section of mix refrigerants in recovery units and especially not in the suction line next to the coil cabinet. Start at cylinders. the coil piping panel and wrap the suction line with tape for approximately 7 inches.
  • Page 8 Connect the main drain and route drain tubing downward to drain line or sump. Do not connect drain to a closed waste plugged with the provided cap. The following practices are recommended to ensure better condensate removal: • be smaller than both drain connections at drain pan.
  • Page 9 and the duct. Drill holes away from refrigerant piping. TEST HOLES avoid unit damage. LEFT-HAND AIR DISCHARGE (TOP VIEW) AIR FLOW Proper air volume must be provided over the evaporator coil. Select a blower motor speed tap that will provide 400 ± 50 CFM per 12,000 Btuh of cooling capacity (wet coil).
  • Page 10 4 - Spray the coil at a vertical angle of 30 to 45 degrees with a constant stream of water at moderate pressure. A pressure washer with a fan nozzle will work best. Do not spray the coil from a horizontal direction.
  • Page 11 the furnace at all times. refrigerant can be removed from various parts of the system. • The furnace heat exchanger, components, duct system, f) Make sure that cylinder is situated on the scales before and evaporator coils must be thoroughly cleaned recovery takes place.
  • Page 12 It is recommended to check the state of the sensor every six months, at the beginning of each cooling and heating season. • debris. • Check that the sensor cable is in good condition. • DO NOT use abrasive cleaning solutions or detergents to clean sensor opening.