Summary of Contents for Beijer Electronics GT-3944
Page 1
User Manual GT-3944 Analog Input Module 4 differential analog input, 0 - 5 V / -5 - 5 V / 0 - 10 V / -10 - 10 V, 16 bit resolution, cage clamp, 10 pt removable terminal Doc ID: 82395...
Page 2
The information in this document is subject to change without notice and is provided as available at the time of printing. Beijer Electronics AB reserves the right to change any information without updating this publication. Beijer Electronics AB assumes no responsibility for any errors that may appear in this document.
10.1. Space Requirements ................20 10.2. Mount Module to DIN Rail ..............21 10.3. Mount Removable Terminal Block ............23 10.4. Connect Cables to Removable Terminal Block ..........24 10.5. Field Power and Data Pins ..............25 Beijer Electronics, Doc ID: 82395 2025-02...
About This Manual 1. About This Manual This manual contains information on the software and hardware features of the Beijer Electronics GT-3944 Analog Input Module. It provides in-depth specifications, guidance on installation, setup, and usage of the product. 1.1. Symbols Used in This Manual This publication includes Warning, Caution, Note and Important icons where appropriate, to point out safety-related, or other important information.
Before using this product, please read this manual and other relevant manuals carefully. Pay full attention to safety instructions! In no event will Beijer Electronics be responsible or liable for damages resulting from the use of this product. The images, examples and diagrams in this manual are included for illustrative purposes. Because of the many variables and requirements associated with any particular installation, Beijer Electronics cannot take responsibility or liability for actual use based on the examples and diagrams.
IP, EtherCAT, PROFINET, CC-Link IE Field, PROFIBUS, CANopen, DeviceNet, CC-Link, MODBUS/Serial etc. • Expansion Module - Expansion module types: Digital IO, Analog IO, and Special modules. • Messaging - The system uses two types of messaging: Service messaging and IO messaging. Beijer Electronics, Doc ID: 82395 2025-02...
Valid parameter data depends on the modules in use. For example, analog modules have settings of either 0-20 mA or 4-20 mA, and temperature modules have settings such as PT100, PT200, and PT500. The documentation for each module provides a description of the parameter data. 2025-02 Beijer Electronics, Doc ID: 82395...
Page 11
Field power On: LED Off < 0.5% (maximum input value) Field power On: LED On > 0.5% (maximum input value) Conversion time 1 ms / all channels Field calibration Not required Common type 1 common, field power 0 V is common (AGND) Beijer Electronics, Doc ID: 82395 2025-02...
[LED Off < 0.5% (Maximum Input Value)] - Normal operation Channel OFF [LED On > 0.5% (Maximum Input Value)] - Channel Green Field power error All channels repeat Green and OFF Field power is unconnected Beijer Electronics, Doc ID: 82395 2025-02...
14 bit Voltage 2.5 V 5.0 V 10.0 V Data(Hex) H0000 H0FFF H1FFF H3FFF 16 bit Voltage 2.5 V 5.0 V 10.0 V Data(Hex) H0000 H1FFF H3FFF H7FFF Voltage range: 0 - 5 V 2025-02 Beijer Electronics, Doc ID: 82395...
Page 15
1.25 V 2.5 V 5.0 V Data(Hex) H0000 H1FFF H3FFF H7FFF Voltage range: -10 - 10 V 14 bit Current -10 V -5 V 5.0 V 10.0 V Data(Hex) HE000 HF000 H0000 H0FFF H1FFF Beijer Electronics, Doc ID: 82395 2025-02...
Page 16
-5 V 5.0 V 10.0 V Data(Hex) HC000 HE000 H0000 H1FFF H3FFF Voltage range: -5 - 5 V 14 bit Current -5 V -2.5 V 2.5 V 5.0 V Data(Hex) HE000 HF000 H0000 H0FFF H1FFF 2025-02 Beijer Electronics, Doc ID: 82395...
Page 17
Data Value / Voltage 16 bit Current -5 V -2.5 V 2.5 V 5.0 V Data(Hex) HC000 HE000 H0000 H1FFF H3FFF Beijer Electronics, Doc ID: 82395 2025-02...
Installation position is valid vertical and horizontal. The drawings are illustrative and may be out of proportion. CAUTION NOT following the space requirements may result in damaging the product. 2025-02 Beijer Electronics, Doc ID: 82395...
• GT-5XXX • GT-7XXX GN-9XXX modules have three locking levers, one at the bottom and two on the side. For mounting instructions, refer to Mount GN-9XXX Module. Mount to DIN rail Dismount from DIN rail Beijer Electronics, Doc ID: 82395 2025-02...
Page 22
10.2.2. Mount GN-9XXX Module To mount or dismount a network adapter or programmable IO module with the product name GN-9XXX, for example GN-9251 or GN-9371, see the following instructions: Mount to DIN rail Dismount from DIN rail 2025-02 Beijer Electronics, Doc ID: 82395...
Hardware Setup 10.3. Mount Removable Terminal Block To mount or dismount a removable terminal block (RTB), see the instructions below. Mount a removable terminal block Dismount a removable terminal block Beijer Electronics, Doc ID: 82395 2025-02...
To connect/disconnect cables to/from the removable terminal block (RTB), see the instructions below. WARNING Always use the recommended supply voltage and frequency to prevent damage to the equipment and ensure optimal performance. Connect cable Disconnect cable 2025-02 Beijer Electronics, Doc ID: 82395...
Token output port of processor module Serial output Transmitter output port of processor module Serial input Receiver input port of processor module Reserved Reserved for bypass token Field GND Field ground Field VCC Field supply voltage (24 VDC) Beijer Electronics, Doc ID: 82395 2025-02...
Need help?
Do you have a question about the GT-3944 and is the answer not in the manual?
Questions and answers