Download Print this page

Copeland 814-3550 Quick Setup Manual

Wireless module system and e2
Hide thumbs Also See for 814-3550:

Advertisement

Quick Links

Wireless Module
System and E2
For a copy of the full Wireless User Manual (P/N 026-1734), go to
operation-manual-en-4845146.pdf
The Wireless Module System allows a quick and easy monitoring for a variety of Refrigeration and HVAC applications by connecting temperature
probes, product simulators, humidity probes or switches to the Wireless Module that transmits these signals to the Wireless Gateway. The Gateway
translates the signal into usable information to send to the building controller, E2 (version 4.08 or higher) or Supervisory Controller, where the data
can be logged into reports or used by algorithms to make control decisions. The Wireless Gateway can receive signals from up to 99 Modules. The
Wireless Module is flexible and configurable with up to three (3) analog or digital inputs that can be used for a variety of applications in
Refrigeration and HVAC, eliminating installation materials and costly labor-intensive wiring.
Installing the Wireless Module
Figure 1 - Wireless Module Board Inside Enclosure
If this is a User Selected Input Module (P/N 814-3600), you must set the
DIP switch setting based on the input being received from the sensor;
either 0 to 5V or NTC/Digital.
026-4255 R4
©2024 Copeland LP.
copeland.com/documents/026-1734-wireless-module-system-installation-
to download it or contact Copeland Technical Support at 833-409-7505.
QUICK SETUP GUIDE
814-3600 User selectable model:
• Set only one switch ON for each sensor pair
• Each pair can be set separately
Table 1 - DIP Switch Settings
0-5V Input:
• Humidity Sensor or Analog 0-5V Input
• Pin 1 ON
• Pin 2 OFF
NTC/Dig Input:
• Temp or Digital Sensor Input
• Pin 1 OFF
• Pin 2 ON
Setup and Commissioning of Module in E2
The Wireless Module must be associated with the Gateway through
the Commissioning process. With proper range planning, all Modules
can be commissioned to the Gateway prior to mounting. For complete
instructions on setup and commissioning of the Wireless Module, refer
to the Wireless User Manual (P/N 026-1734).
Steps to set up and commission the Wireless Module in E2:
1. Go to the Add Application screen to add required number of RF
Modules (Menu, 6, 1, F4: Lookup, 23. RF Module) then press
Enter.
2. Enter how many (99 max per Gateway) and press Enter.

Advertisement

loading
Need help?

Need help?

Do you have a question about the 814-3550 and is the answer not in the manual?

Questions and answers

Summary of Contents for Copeland 814-3550

  • Page 1 Copeland Technical Support at 833-409-7505. The Wireless Module System allows a quick and easy monitoring for a variety of Refrigeration and HVAC applications by connecting temperature probes, product simulators, humidity probes or switches to the Wireless Module that transmits these signals to the Wireless Gateway. The Gateway translates the signal into usable information to send to the building controller, E2 (version 4.08 or higher) or Supervisory Controller, where the data...
  • Page 2 Responsibility for proper selection, use and maintenance of any product remains solely with the purchaser and end-user. ©2024 Copeland is a trademark of Copeland LP.

This manual is also suitable for:

814-3560814-3570501-1121508-9101201-1160140-6801