Table of Contents INTRODUCTION ABBREVIATIONS GENERAL DESCRIPTION 3.1. PROTECTIVE COVER 3.2. LED SET THE COM LOOP ADDRESS 4.1. AUTO ADDRESSING 4.2. MANUAL ADDRESSING SET THE MODE 5.1. COMPATIBILITY TABLE ROUTINE TESTING REPLACE THE GLASS ELEMENT MOUNTING INSTALLATION AND WIRING TECHNICAL DATA APPROVALS...
4433 ADDRESSABLE MANUAL CALL POINT WITH ISOLATOR - FIRE ALARM SOLUTIONS TECHNICAL DESCRIPTION 1. INTRODUCTION This document describes the addressable manual call point with isolator, type number 4433. The document contains information about the product and instructions on how to mount and connect it.
4433 ADDRESSABLE MANUAL CALL POINT WITH ISOLATOR - FIRE ALARM SOLUTIONS TECHNICAL DESCRIPTION 3. GENERAL DESCRIPTION The addressable manual call point with isolator is used for immediate manual actuation of a fire alarm. To operate the manual call point the glass element is pressed until it is broken. This will generate a fire alarm in the CIE.
4. SET THE COM LOOP ADDRESS 4.1. AUTO ADDRESSING The 4433 supports automatic addressing via EBLWin. For more information, see Planning instructions for the system, version 2.4.x or later. 4.2. MANUAL ADDRESSING Each COM loop unit has to have a unique COM loop address (001-253).
4433 ADDRESSABLE MANUAL CALL POINT WITH ISOLATOR - FIRE ALARM SOLUTIONS TECHNICAL DESCRIPTION 6. ROUTINE TESTING a) Insert the test key into the hole in the front cover. The glass position will change, indicating that the manual call point is oper- ated.
8. MOUNTING The addressable manual call point must be mounted on the wall. Screws are not supplied. (Measure in mm) a) Mount the red back box on the wall. There is provision for rear cable entry. In case of open wiring (surface mounted back box), cable holes can be drilled into the top or bottom of the back box (max diameter 20 mm).
4433 ADDRESSABLE MANUAL CALL POINT WITH ISOLATOR - FIRE ALARM SOLUTIONS TECHNICAL DESCRIPTION 9. INSTALLATION AND WIRING Screen wire termination is not provided. COM-Loop Wire size (Min) Ø 0.8 mm (0.5 mm²) Wire size (Max) Ø 1.6 mm (2 mm²)
10. TECHNICAL DATA All current consumptions are valid by nominal voltage and by 25 °C. Voltage: Allowed 12 – 30V DC Normal 24V DC Current: Quiescent 1.6 mA Active 2.7 mA Address range 001-253 Address setting With address setting tool Short circuit isolator Internal battery Material...
4433 ADDRESSABLE MANUAL CALL POINT WITH ISOLATOR - FIRE ALARM SOLUTIONS TECHNICAL DESCRIPTION 11. APPROVALS Applicable directive/ Approval Applicable standards Notified body EN54-11 EN54-17 No. 0786-CPR-21235 EN54-11 EN54-17 VdS2344 No. G213004 VdS2504 EN61000-6-3 (Emission) Self declaration EN50130-4 (Immunity) RoHS EN IEC 63000...
Page 12
DOCUMENT NAME: TECHNICAL DESCRIPTION 4433 DOCUMENT NUMBER: MEW01937 EN DATE OF ISSUE: 2015-11-25 REV: 6 DATE OF REVISION: 2024-02-22 Panasonic Fire & Security Europe AB Jungmansgatan 12 SE-211 11 Malmö Sweden Tel: +46 (0)40 697 70 00 www.panasonic-fire-security.com...