Summary of Contents for Hokuetsu AIRMAN SDG400S-8E1

  • Page 49 4. Failure and Troubleshooting 4.1.2 Circuit Breaker  In case of an overload or short-circuited wire connection, the circuit-breaker trips.  When the breaker is tripped, stop the machine immediately and reset the circuit breaker after resolving the cause of the trouble. <How to reset>...
  • Page 51 4. Failure and Troubleshooting Symptom Cause Counter measures Circuit breaker (1) Overloaded Reduce the load trips. (2) Short-circuit occurred at the load side. Get rid of cause of short-circuiting. Even when operated (1) Poor tightening of terminals Check/tightening at a rated speed, no (2) Broken or short-circuited circuit to Repair voltage or too low...
  • Page 54 5. Periodic Inspection Every Every Every Maintenance Daily 1,000 Ref. Remarks hours hours hours Check interior 3-13 ○ Check oil fence drain 3-15 ○ Check terminal and wirings 5-13 Every 4 months ○ Check engine/generator mount 5-14 Every 1 year ○...
  • Page 60 5. Periodic Inspection 5.4.8 Check Insulation Resistance Every 2 months or 250 Hours <Procedure> 1. Remove the load side cable from the output terminal board. To Bonnet 2. Loose and remove the bolt (M8) securing the ground cable between [N] and [GROUND] on the output terminal board. 3.