Carrier bryant 935CB Installation, Start-Up, Operating And Service And Maintenance Instructions
Carrier bryant 935CB Installation, Start-Up, Operating And Service And Maintenance Instructions

Carrier bryant 935CB Installation, Start-Up, Operating And Service And Maintenance Instructions

Single-stage, upflow/horizontal communicating, variable speed ecm, ultra low nox, 35-in tall condensing gas furnace

Advertisement

Quick Links

935CB
Single-Stage, Upflow/Horizontal Communicating,
Variable Speed ECM, Ultra Low NOx, 35-in Tall
Condensing Gas Furnace
NOTE: Read the entire instruction manual before starting the
installation.
Approved for installations up to 5,400 feet (1646 meters)
TABLE OF CONTENTS
REQUIRED NOTICE FOR MASSACHUSETTS INSTALLATIONS2
Table 1 – Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
SAFETY CONSIDERATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Table 2 – Minimum Clearances to Combustible Materials for
All Units. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
INTRODUCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Table 3 – Loose Parts Bag . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
CODES AND STANDARDS. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
ELECTROSTATIC DISCHARGE (ESD) PRECAUTIONS PROCE-
DURE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
ACCESSORIES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
LOCATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
AIR FOR COMBUSTION AND VENTILATION . . . . . . . . . . . . . . 8
Table 4 – Minimum Free Area Required for Each Combustion
Air Opening or Duct to Outdoors . . . . . . . . . . . . . . . . . . . . . . . . . 9
Table 5 – Minimum Space Volumes for 100% Combustion,
Ventilation and Dilution Air from Outdoors . . . . . . . . . . . . . . . . . 9
CONDENSATE TRAP. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Condensate Drain Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Table 6 – Condensate Trap Configurations . . . . . . . . . . . . . . . . . 13
INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Table 7 – Evaporator Coil Spacer or Shield Requirements. . . . . 16
Table 8 – Opening Dimensions - In. (mm) . . . . . . . . . . . . . . . . . 20
FILTER ARRANGEMENT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Table 9 – Optional Filter Media Pressure Drop (Clean) Versus
Airflow - in. w.c. (Pa) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Table 10 – Optional Filter Media Pressure Drop (Clean) Versus
Face Velocity- in. w.c. (Pa) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
AIR DUCTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Table 11 – Air Filter Selection and Duct Sizing - In. (mm) . . . . 23
GAS PIPING. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Table 12 – Maximum Capacity of Pipe . . . . . . . . . . . . . . . . . . . . 23
ELECTRICAL CONNECTIONS. . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Table 13 – Electrical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
TEMPERATURE SENSOR . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
VENTING. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Table 14 – Vent Termination Kit for Direct Vent (2-pipe) Sys-
tems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Table 15 – Approved Combustion-Air and Vent Pipe, Fitting
and Cement Materials . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Table 16 – Maximum Equivalent Vent Length - Ft. . . . . . . . . . . 38
Table 17 – Deductions from Maximum Equivalent Vent Length
- Ft.(M). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
Table 18 – Maximum Allowable Exposed Vent Length in Un-
Portions of the text and tables are reprinted from NFPA 54/ANSI Z223.1E, with permission of National Fire Protection Association, Quincy, MA
02269 and American Gas Association, Washington DC 20001. This reprinted material is not the complete and official position of the NFPA or ANSI
Installation, Start-up, Operating and
Service and Maintenance Instructions
on the referenced subject, which is represented only by the standard in its entirety.
conditioned Space - Ft. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
Table 19 – Hanger Spacing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
AIRFLOW DELIVERY - CFM . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
Table 20 – 48060C17 Airflow in CFM . . . . . . . . . . . . . . . . . . . . 45
Table 21 – 60080C21 Airflow in CFM . . . . . . . . . . . . . . . . . . . . 45
Table 22 – 66100C21 Airflow in CFM . . . . . . . . . . . . . . . . . . . . 46
FURNACE CONTROL PROGRAMMING AND NAVIGATION 46
Table 23 – System Status Display Codes . . . . . . . . . . . . . . . . . . 47
Table 24 – Main Menu Options . . . . . . . . . . . . . . . . . . . . . . . . . . 47
SERVICE LABEL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
START-UP, ADJUSTMENT, AND SAFETY CHECK . . . . . . . . . 49
Table 25 – Test Sequence . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
WIRING DIAGRAM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
ADJUSTMENTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
Table 26 – Altitude Derate Multiplier for USA. . . . . . . . . . . . . . 52
Table 27 – Gas Rate (CU ft./hr). . . . . . . . . . . . . . . . . . . . . . . . . . 53
Table 28 – Gas Valve Outlet Pressure for Gas Heat Values at
Altitude - 60,000 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
Table 29 – Gas Valve Outlet Pressure for Gas Heat Values at
Altitude - 80,000 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
Table 30 – Gas Valve Outlet Pressure for Gas Heat Values at
Altitude - 100,000 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
SERVICE AND MAINTENANCE PROCEDURES. . . . . . . . . . . . 56
ELECTRICAL CONTROLS AND WIRING . . . . . . . . . . . . . . . . . 57
CARE AND MAINTENANCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
WINTERIZATION. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62
SEQUENCE OF OPERATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62
PARTS REPLACEMENT INFORMATION GUIDE . . . . . . . . . . . 68
MODEL NOMENCLATURE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68
TRAINING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68
To learn more about this appliance and installation via a mobile device,
go to
https://bryant.hvacpatners.com/NFC
access airflow tables or troubleshooting guide on your mobile device go
to
mlctraining.com/training/techdocs/102/
or use the QR code below. To
or use the QR code below.
A230292
A200352

Advertisement

loading
Need help?

Need help?

Do you have a question about the bryant 935CB and is the answer not in the manual?

Questions and answers

Summary of Contents for Carrier bryant 935CB

  • Page 1 935CB Single-Stage, Upflow/Horizontal Communicating, Variable Speed ECM, Ultra Low NOx, 35-in Tall Condensing Gas Furnace Installation, Start-up, Operating and Service and Maintenance Instructions NOTE: Read the entire instruction manual before starting the conditioned Space - Ft....... . . 41 installation.
  • Page 2 935CB: Installation, Start-up, Operating and Service and Maintenance Instructions REQUIRED NOTICE FOR MASSACHUSETTS INSTALLATIONS IMPORTANT The Commonwealth of Massachusetts requires compliance with regulation 248 CMR as follows: 5.08: Modifications to NFPA-54, Chapter 10 2) Revise 10.8.3 by adding the following additional requirements: a.
  • Page 3 935CB: Installation, Start-up, Operating and Service and Maintenance Instructions A210796 Fig. 1 – Dimensional Drawing Table 1 – Dimensions SHIP WT. FURNACE SIZE LB (KG) CABINET WIDTH OUTLET WIDTH BOTTOM INLET WIDTH AIR INTAKE 48060C17 17-1/2 (445) 15-7/8 (403) 16 (406) 8-3/4 (222) 149.6 (67.9) 60080C21...
  • Page 4 935CB: Installation, Start-up, Operating and Service and Maintenance Instructions Improper installation, adjustment, alteration, service, maintenance, or WARNING use can cause explosion, fire, electrical shock, or other conditions which may cause death, personal injury, or property damage. Consult a FIRE, EXPLOSION, ELECTRICAL SHOCK, AND qualified installer, service agency, or your distributor or branch for information or assistance.
  • Page 5 935CB: Installation, Start-up, Operating and Service and Maintenance Instructions INTRODUCTION 6. Always install furnace to operate within the furnace’s intended temperature-rise range with a duct system which has an external static pressure within the allowable range, as specified in the “Start-Up, Adjustments, and Safety Check”...
  • Page 6 935CB: Installation, Start-up, Operating and Service and Maintenance Instructions WARNING FIRE HAZARD Failure to follow this warning could result in personal injury, death and/or property damage. Do not install the furnace on its back or hang furnace with control compartment facing downward. Safety control operation will be adversely affected.
  • Page 7 935CB: Installation, Start-up, Operating and Service and Maintenance Instructions ELECTROSTATIC DISCHARGE (ESD) PRECAUTIONS PROCEDURE CAUTION FURNACE RELIABILITY HAZARD Failure to follow this caution may result in unit component damage. Electrostatic discharge can affect electronic components. Take precautions during furnace installation and servicing to protect the furnace electronic control.
  • Page 8 935CB: Installation, Start-up, Operating and Service and Maintenance Instructions Location Relative to Cooling Equipment WARNING The cooling coil must be installed parallel with, or on the downstream side of the unit to avoid condensation in the heat exchangers. When CARBON MONOXIDE POISONING / COMPONENT installed parallel with the furnace, dampers or other flow control must DAMAGE HAZARD prevent chilled air from entering the furnace.
  • Page 9 935CB: Installation, Start-up, Operating and Service and Maintenance Instructions Outdoor Combustion Air Method WARNING 1. Provide the space with sufficient air for proper combustion, ventilation, and dilution of flue gases using permanent horizontal or CARBON MONOXIDE POISONING HAZARD vertical duct(s) or opening(s) directly communicating with the Failure to follow this warning could result in personal injury or death.
  • Page 10 935CB: Installation, Start-up, Operating and Service and Maintenance Instructions Standard Method 1. The space has no less volume than 50 cubic feet per 1,000 BTUh of the maximum input ratings for all gas appliances installed in the space and 2. The air infiltration rate is not known to be less than 0.40 air changes per hour (ACH).
  • Page 11 935CB: Installation, Start-up, Operating and Service and Maintenance Instructions 4. Unusually tight construction is defined as Construction with: CAUTION a. Walls and ceilings exposed to the outdoors have a continuous, sealed vapor barrier. Openings are gasketed or sealed and PROPERTY DAMAGE HAZARD b.
  • Page 12 935CB: Installation, Start-up, Operating and Service and Maintenance Instructions A200072 A200069 A200073 A200070 A200074 NOTE: Coil may require metal spacer or shield between furnace and coil. See coil install requirements, see Table A200071 Fig. 10 – Example of Field Drain Attachment (Not Allowed) Fig.
  • Page 13 935CB: Installation, Start-up, Operating and Service and Maintenance Instructions Table 6 – Condensate Trap Configurations Installation Configuration Part Upflow Horizontal Upflow Offset Required Required Required A200090 Main Trap Required Required Required A230035 NOTE: Locate the plug that needs to be removed. Using a screw driver A200091 Adapter or tool, place end against rim on plug.
  • Page 14 935CB: Installation, Start-up, Operating and Service and Maintenance Instructions A200119 A200076 Fig. 17 – Upflow Right Side Return Configuration - Trap Fig. 14 – Upflow Example of Trap Adapter Installation Interference A200120 Fig. 18 – Upflow Right Side Return Configuration - Required Upflow Offset Installation A200064 Fig.
  • Page 15 935CB: Installation, Start-up, Operating and Service and Maintenance Instructions Upflow Specific Steps – Offset Installation 1. Trap Offset Adapter Accessory Kit (purchased separately) is required. Instead of installing the trap to the adapter plate, screw the trap offset adapter to the adapter plate, see Fig.
  • Page 16 935CB: Installation, Start-up, Operating and Service and Maintenance Instructions Alternate Horizontal Option - 8. Allow at least 1/4-in. per foot (20 mm per meter) of slope down and away from the furnace in horizontal sections of drain line. Remote Trap Installation Specific Steps 1.
  • Page 17 935CB: Installation, Start-up, Operating and Service and Maintenance Instructions All adapters are field fabricated according to the dimensions for the Cabinet Size Dimension “B” metal shield, see Fig. 25, and for the 8-in. tall sheet metal spacer, see 17-in. 17-1/2-in. Fig.
  • Page 18 935CB: Installation, Start-up, Operating and Service and Maintenance Instructions NOTE: For Upflow Right Side Return, use upflow offset installation for condensate trap. Refer to footnotes for other Table 20 thru Table 22 return-air restrictions. A200426 Fig. 29 – Upflow Return Air Configurations and Restrictions Representative drawing only, some models may vary.
  • Page 19 935CB: Installation, Start-up, Operating and Service and Maintenance Instructions hung from floor joists, rafters or trusses or installed on a non-combustible platform, blocks, bricks or pad. Supply Air Connections For a furnace not equipped with a cooling coil, the outlet duct shall be provided with a removable access panel.
  • Page 20 935CB: Installation, Start-up, Operating and Service and Maintenance Instructions FILTER ARRANGEMENT WARNING FIRE, CARBON MONOXIDE AND POISONING HAZARD Failure to follow this warning could result in fire, personal injury or death. Never operate a furnace without a filter or filtration device installed. Never operate a furnace with filter or filtration device access doors removed.
  • Page 21 935CB: Installation, Start-up, Operating and Service and Maintenance Instructions match the required filter or IAQ device dimensions. See the instructions supplied with factory-accessory duct adapters. Table 9 – Optional Filter Media Pressure Drop (Clean) Versus Airflow - in. w.c. (Pa) Representative After-Market Filter Media* 16 x 25 Filter Factory-Accessory...
  • Page 22 935CB: Installation, Start-up, Operating and Service and Maintenance Instructions AIR DUCTS NOTICE Many states, provinces and localities are considering or have implemented standards and/or restrictions on duct sizing practices, ductwork leakage, and/or ductwork thermal, airflow and electrical efficiencies. CONSULT LOCAL CODE OFFICIALS for ductwork design and performance requirements in your area.
  • Page 23 935CB: Installation, Start-up, Operating and Service and Maintenance Instructions For recommended gas pipe sizing, see Table 12. Risers must be used to Table 11 – Air Filter Selection and Duct Sizing - In. (mm) connect to furnace and to meter. Support all gas piping with appropriate Filter Size straps, hangers, etc.
  • Page 24 935CB: Installation, Start-up, Operating and Service and Maintenance Instructions Gas Pipe Grommet CAUTION For direct vent (2-pipe) applications, the opening for the gas pipe must be sealed to prevent air leakage. Remove the knockout or plug, install FURNACE DAMAGE HAZARD the grommet in the hole, then insert the gas pipe.
  • Page 25 935CB: Installation, Start-up, Operating and Service and Maintenance Instructions GROUND NEUTRAL LINE VOLTAGE A200310 Fig. 38 – Typical Single-Stage Wiring Diagram WARNING ELECTRIC FIRE HAZARD DISCONNECT SWITCH COPPER Failure to follow this warning could result in personal injury, death, or WIRE ONLY property damage.
  • Page 26 935CB: Installation, Start-up, Operating and Service and Maintenance Instructions The J-Box cover, mounting bracket and screws are shipped in the loose For a side-mounted external electrical box, complete parts bag included with the furnace. J-Box mounting locations, see the following: Fig.
  • Page 27 935CB: Installation, Start-up, Operating and Service and Maintenance Instructions 6. Connect power cord power and neutral leads to furnace power 6. Route SAT wire leads into furnace blower compartment along with leads, see Fig. the thermostat wires. Use provided grommet to protect the wires through the furnace casing.
  • Page 28 935CB: Installation, Start-up, Operating and Service and Maintenance Instructions A230452 Fig. 42 – Example of Furnace Control ACCESSORIES communication plug is supplied with the User Interface. Refer to the instructions supplied with the User Interface for complete 1. Electronic Air Cleaner (EAC) details, see Fig.
  • Page 29 935CB: Installation, Start-up, Operating and Service and Maintenance Instructions VENTING WARNING NOTE: Planning for the venting system should be done in conjunction with planning for the ductwork, drainage, and furnace accessories, such CARBON MONOXIDE POISONING HAZARD as air cleaners and humidifiers. Begin assembling the venting system Failure to follow the instructions outlined below for each appliance AFTER the furnace is set in place in the required orientation.
  • Page 30 935CB: Installation, Start-up, Operating and Service and Maintenance Instructions Table 14 – Vent Termination Kit for Direct Vent (2-pipe) Systems Approved Two-Pipe Termination Fittings Vent and Combustion Allowable Concentric Vent Kit 1 1/2-in. 2-in. 2 1/2-in. 3-in. 4-in. Air Pipe Diameters Concentric Vent Kit (38 mm) (51 mm)
  • Page 31 935CB: Installation, Start-up, Operating and Service and Maintenance Instructions These furnaces can be vented as direct-vent (two-pipe), ventilated atmosphere. Combustion-air and vent pipes must terminate together in combustion air or non-direct (single-pipe) vent system. Each type of the same atmospheric pressure zone, either through the roof (preferred) venting system is described below.
  • Page 32 935CB: Installation, Start-up, Operating and Service and Maintenance Instructions A05091 Fig. 44 – Vent Pipe Termination for Non-Direct Vent and Ventilated Combustion Air System A190032 Fig. 45 – Inside Corner Termination Inside Corner Terminations Inside corner vent terminations are permitted provided that: •...
  • Page 33 935CB: Installation, Start-up, Operating and Service and Maintenance Instructions Vertical clearance to a soffitt located above the vent termination within a horizontal distance of 2 ft. (61 cm) from the centerline of 6 ft. (2 M) the vent termination Clearance to a ventilation exhaust (including HRV/ERV) on either Wall A or Wall B 12-in.
  • Page 34 935CB: Installation, Start-up, Operating and Service and Maintenance Instructions 9 in. (9 mm) for appliances >10,000 BTUh (3 kW) Clearance to non—mechanical air supply inlet 12 in. (305 mm) for appliances >10,000 BTUh(3 kW) and </= 50,000 BTUh (15 kW), to building or the combustion air inlet to any and </= 100,000 BTUh (30 kW), 12 in.(305 mm) for appliances >50,000 BTUh...
  • Page 35 935CB: Installation, Start-up, Operating and Service and Maintenance Instructions Clearance to each side of the centerline 3 ft. (.9 M) within 15 ft. (4.6 M) 3 ft. (.9 M) within 15 ft. (4.6 M) extended above electrical meter or gas service above the meter/regulator assembly.
  • Page 36 935CB: Installation, Start-up, Operating and Service and Maintenance Instructions RECOMMENDED SUPPORT NOTICE WARNING CARBON MONOXIDE POISONING HAZARD VENT TERMINATIONS It is recommended that sidewall vent terminations in excess of 24 Failure to follow the instructions outlined below for each appliance being placed into operation could result in carbon monoxide poisoning inches (0.6 M) or rooftop terminations in excess of 36 inches (1 M) in or death.
  • Page 37 935CB: Installation, Start-up, Operating and Service and Maintenance Instructions The Maximum Vent Length for the vent and combustion air pipe (when NOTICE used) is determined from the Maximum Equivalent Vent Length (Table 16) minus the number of fittings multiplied by the deduction for each type of fitting used, see Table OPTIONAL CONFIGURATION FOR COMBUSTION AIR...
  • Page 38 935CB: Installation, Start-up, Operating and Service and Maintenance Instructions 3. For each pipe, multiply the number of elbows by the equivalent ADDITIONAL INFORMATION NOTICE length for the type of elbow used. Record the equivalent length of all the elbows for each pipe. 4.
  • Page 39 935CB: Installation, Start-up, Operating and Service and Maintenance Instructions Table 17 – Deductions from Maximum Equivalent Vent Length - Ft.(M) Pipe Diameter (in): 1-1/2 2-1/2 Mitered 90º Elbow (2.4) (2.4) (2.4) (2.4) (2.4) (1.5) (1.5) (1.5) (1.5) (1.5) Medium Radius 90º Elbow Long Radius 90º...
  • Page 40 935CB: Installation, Start-up, Operating and Service and Maintenance Instructions A230010 UPFLOW LEFT CONFIGURATION HORIZONTAL LEFT-VERTICAL VENT CONFIGURATION A11327A A230009 UPFLOW RIGHT CONFIGURATION HORIZONAL LEFT-LEFT VENT CONFIGURATION A11328A A230011 UPFLOW VERTICAL VENT Fig. 55 – Upflow Configurations (Appearance may vary) See “Notes for Venting Options” HORIZONTAL LEFT-RIGHT VENT CONFIGURATION A11329A Fig.
  • Page 41 935CB: Installation, Start-up, Operating and Service and Maintenance Instructions HORIZONTAL RIGHT-VERTICAL VENT CONFIGURATION HORIZONTAL RIGHT-RIGHT VENT CONFIGURATION A11337 A11335 Fig. 57 – Horizontal Right (Appearance may vary) See “Notes for Venting Options” Notes for venting options 1. Attach vent pipe adapter with gasket to furnace casing. 5.
  • Page 42 935CB: Installation, Start-up, Operating and Service and Maintenance Instructions Installing the Vent Pipe Adapter and Combustion Air recommended that all pipes be cut, prepared, and pre-assembled before permanently cementing any joint. Pipe Adapter 1. Working from furnace to outside, cut pipe to required length(s). CAUTION 2.
  • Page 43 935CB: Installation, Start-up, Operating and Service and Maintenance Instructions Table 19 – Hanger Spacing NOTICE Material Diameter RECOMMENDED SUPPORT FOR VENT PVC Sch SDR 21 & Polyprop- CPVC ylene TERMINATIONS 1 1/2-in. 3-ft. 2 1/2-ft. 3-ft. 3-ft. 3.25-ft. It is recommended that rooftop vent terminations in excess of 36 inches (1 M) in vertical length be supported by EITHER the Direct Vent Ter- 38-mm 914-mm...
  • Page 44 935CB: Installation, Start-up, Operating and Service and Maintenance Instructions 4. Disassemble loose pipe fittings. Clean and cement using same (Direct Vent / 2-Pipe System ONLY) procedures as used for system piping. DO NOT CEMENT When two or more furnaces are vented near each other, two vent POLYPROPYLENE FITTINGS.
  • Page 45 935CB: Installation, Start-up, Operating and Service and Maintenance Instructions AIRFLOW DELIVERY - CFM Table 20 – Airflow in CFM Table 21 – Airflow in CFM 48060C17 60080C21 Setting ESP (in.w.c.) Setting ESP (in.w.c.) 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.1 0.2 0.3 0.4 0.5 0.6 0.7 †...
  • Page 46 935CB: Installation, Start-up, Operating and Service and Maintenance Instructions FURNACE CONTROL PROGRAMMING AND Table 22 – Airflow in CFM 66100C21 NAVIGATION Setting ESP (in.w.c.) On-Board Control Method 0.1 0.2 0.3 0.4 0.5 0.6 0.7 WARNING ELECTRICAL SHOCK HAZARD Failure to follow this warning could result in personal injury, or death. Blower access door switch removes 115-V power to control.
  • Page 47 935CB: Installation, Start-up, Operating and Service and Maintenance Instructions Table 23 – System Status Display Codes Display Operating Mode Notes: Idle/Standby Mode No active demands Heating Mode Gas Heating active High Cooling Mode Cooling or Heat Pump active Low Cooling Mode Cooling or Heat Pump active Heat Pump Defrost Mode Gas Heating cycle active during Heat Pump Defrost cycle...
  • Page 48 935CB: Installation, Start-up, Operating and Service and Maintenance Instructions best results, it is recommended to keep your mobile device within will operate. Do NOT program the control board with a Model Program 10 feet of the equipment throughout this whole process. Number different than what is specified on the rating plate.
  • Page 49 935CB: Installation, Start-up, Operating and Service and Maintenance Instructions SERVICE LABEL A230391 Fig. 60 – Service Label Information START-UP, ADJUSTMENT, AND SAFETY 5. Blower door must be in place to complete 115-V electrical circuit and supply power to the furnace components. CHECK Start-Up Procedures NOTICE...
  • Page 50 935CB: Installation, Start-up, Operating and Service and Maintenance Instructions c. To initiate the component test sequence, the control must be in CAUTION (idL) mode. no thermostat demands (W, Y, G). Select component test (Ct) from menu select buttons to start the SHOCK HAZARD component test sequence.
  • Page 51 935CB: Installation, Start-up, Operating and Service and Maintenance Instructions WIRING DIAGRAM A230393 Fig. 61 – Wiring Diagram Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
  • Page 52 935CB: Installation, Start-up, Operating and Service and Maintenance Instructions Prime Condensate Trap with Water CAUTION UNIT OPERATION HAZARD Failure to follow this caution may result in intermittent unit operation or performance satisfaction. Condensate trap must be PRIMED or proper draining may not occur. The condensate trap has two internal chambers which can ONLY be primed by pouring water into the inducer drain side of condensate trap.
  • Page 53 935CB: Installation, Start-up, Operating and Service and Maintenance Instructions Clocking the Meter 9. Remove jumper across thermostat connections to terminate call for heat. Wait until the blower off delay is completed. 2. Verify natural gas input rate by clocking meter. 10.
  • Page 54 935CB: Installation, Start-up, Operating and Service and Maintenance Instructions 3. Restore furnace to normal operating condition. Table 28 – Gas Valve Outlet Pressure for Gas Heat Values at a. When correct input rate and temperature rise is achieved, remove Altitude - 60,000 jumper across thermostat connections to terminate call for heat.
  • Page 55 935CB: Installation, Start-up, Operating and Service and Maintenance Instructions Table 29 – Gas Valve Outlet Pressure for Gas Heat Values at Table 30 – Gas Valve Outlet Pressure for Gas Heat Values at Altitude - 80,000 Altitude - 100,000 (Tabulated Data Based on 80,000 BTUh Input for 0-ft (0m) to 5400-ft (Tabulated Data Based on 100,000 BTUh Input for 0-ft (0m) to 5400-ft (1646 M) above sea level) (1646 M) above sea level)
  • Page 56 935CB: Installation, Start-up, Operating and Service and Maintenance Instructions Adjust Airflow SERVICE AND MAINTENANCE PROCEDURES The ECM blower can be adjusted for a range of airflows for low-speed Untrained personnel can perform basic maintenance functions such as or high-speed cooling. See –...
  • Page 57 935CB: Installation, Start-up, Operating and Service and Maintenance Instructions ELECTRICAL CONTROLS AND WIRING e. Press Next/Option button to cycle through the fault history. Faults remain in memory for 72 hours of powered operation after the last fault occurs. Faults may be manually cleared by selecting WARNING (CLr) with the menu/select button.
  • Page 58 935CB: Installation, Start-up, Operating and Service and Maintenance Instructions 3. Check electrical connections for tightness and controls for proper 3. All factory wires can be left connected, but field thermostat connections may need to be disconnected depending on their length operation each heating season.
  • Page 59 935CB: Installation, Start-up, Operating and Service and Maintenance Instructions WARNING ELECTRICAL SHOCK HAZARD Failure to follow this warning could result in personal injury, or death. Blower access door switch opens 115-V power to furnace control. No component operation can occur unless switch is closed. Exercise caution to avoid electrical shock from exposed electrical components when manually closing this switch for service purposes.
  • Page 60 935CB: Installation, Start-up, Operating and Service and Maintenance Instructions Servicing Hot Surface Igniter WARNING FIRE OR EXPLOSION HAZARD Failure to follow this warning could result in personal injury, death, and/or property damage. When servicing the flame sensor, only use the factory-provided 1/4-in. length screws.
  • Page 61 935CB: Installation, Start-up, Operating and Service and Maintenance Instructions Remove the pressure transducer tube from the collector box. WARNING NOTE: Do NOT blow into tube with tube connected to the pressure transducer. ELECTRICAL SHOCK, FIRE OR EXPLOSION HAZARD 9. Clean pressure transducer port on collect box with a small wire. Failure to follow this warning could result in personal injury or death, Shake any water out of pressure transducer tube.
  • Page 62 935CB: Installation, Start-up, Operating and Service and Maintenance Instructions 12. Check for gas leaks. 10. Repeat Steps 5 through 8. 11. If a condensate pump is used, check with pump manufacturer to WARNING verify pump is safe for use with antifreeze used. Allow pump to start and pump anti-freeze to open drain.
  • Page 63 935CB: Installation, Start-up, Operating and Service and Maintenance Instructions will be reset automatically after three hours, or by momentarily low-cooling speed, and the R-to-G-and-Y1 circuits starts the furnace interrupting 115 VAC power to the furnace, or by interrupting 24 blower motor BLWM at low-cooling airflow Low cooling airflow is VAC power at SEC1 or SEC2 to the furnace control CPU (not at based on cooling blower speed (CL1) selection, see Fig.
  • Page 64 935CB: Installation, Start-up, Operating and Service and Maintenance Instructions (continuous fan) selection shown in Fig. 59. Factory default is energized, in which case the blower motor BLWM will operate at shown in Fig. 59. Terminal EAC-1 is energized as long as the continuous blower airflow.
  • Page 65 935CB: Installation, Start-up, Operating and Service and Maintenance Instructions A230404 Fig. 69 – Troubleshooting Guide Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
  • Page 66 935CB: Installation, Start-up, Operating and Service and Maintenance Instructions A230405 Troubleshooting Guide (Continued) Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
  • Page 67 935CB: Installation, Start-up, Operating and Service and Maintenance Instructions A230406 Troubleshooting Guide (Continued) Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
  • Page 68 © 2024 Carrier. All rights reserved. Edition Date: 10/24 Catalog No: II935CB-02 A Proud Member of the Carrier Family Replaces II935CB-01 Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.