IK-E379-001-GB, Edition I, 08.2023 MICROPROCESSOR BASED ADDRESSABLE CONTROL ELEMENT EKS-6008 POLON 3000 / POLON 6000 INTERACTIVE FIRE DETECTION AND ALARM SYSTEM _________________________________________________________________________________ INSTALLATION AND MAINTENANCE MANUAL IK-E379-001-GB Edition I __________________________________________________________________________________ EKS-6080 CONTROL ELEMENT...
Page 2
IK-E379-001-GB, Edition I 08.2023 The EKS-6008 control element, which is the subject of this manual, meets the essential requirements of the following regulations of the European Parliament and of the Council (EU) and European Union directives: CPR/305/2011 Regulation (EU) of the European Parliament and of the Council of 9 March 2011 laying down harmonised conditions for the marketing of consumer products repealing Council Directive 89/106/EEC;...
The EKS-6008 control element is an addressable device designed for: control on activation of automatic safety and fire devices, The EKS-6008 control element is designed to work in addressable detection lines of POLON 6000 fire alarm control panels. Device is adapted for indoor and outdoor operation.
IK-E379-001-GB, Edition I, 08.2023 3. Design description The EKS-6008 control element is made in the form of a printed circuit board with set of connectors and electronic components placed in enclosure. Wall mounting slots are located in the corners of the enclosure.
(erroneous data stored in non-volatile memory). The way in which the EKS-6008 control element is to operate and behave is determined by the operating modes of the individual outputs. After the automatic configuration of the POLON 3000 or POLON 6000 control panels, the control outputs are inactive.
Page 7
IK-E379-001-GB, Edition I, 08.2023 The same rules apply to IN HV inputs. If the IN HV outputs or inputs are not used, the position of corresponding jumpers is not relevant. Figure 4.1 EKS-6008 PCB labelling __________________________________________________________________________________ EKS-6080 CONTROL ELEMENT...
Safe state of the relay: Yes (undriven, driven) No (no change) d) Continuity control of the cable connected to the control output – (Yes, No) e) Group number - (0, 65535) f) Number of cycles (0 ÷ 255) __________________________________________________________________________________ EKS-6008 CONTROL ELEMENT...
Page 9
IK-E379-001-GB, Edition I, 08.2023 The following table shows how the control element is configured depending on the type of operation of the control output: Control output operation type Time parameters to be defined Disabled Continuous Triggering Mode Triggering delay time - T Reset delay time - T T ow T ok...
Figure 6.1 TEST button – switch on method 7. Installation The EKS-6008 control elements are recommended to be installed on the detection line in the vicinity of the controlled devices. The elements can operate in loop, loop with straight branches or in radial detection lines of POLON 3000 or POLON 6000 control panels (see the Installation and Maintenance Manual of control panels).
Page 11
Control elements installation is not recommended in rooms with a corrosive atmosphere, containing gases and caustic vapours as well as dust. The EKS-6008 controls are equipped with a "Pressure equalization element", especially useful when mounted outdoors. __________________________________________________________________________________...
Page 12
OFF6 Power supply Power COM3 COM6 24 VDC Controlled Controlled supply device device 230 VAC Power Power Supply COM4 COM5 supply Controlled 230 VAC 24 VDC Controlled device device OFF4 OFF5 Rysunek 7.1 EKS-6008 connection diagram __________________________________________________________________________________ EKS-6008 CONTROL ELEMENT...
Maintenance and periodic inspections must be carried out by authorized personnel of companies trained or approved by POLON-ALFA. All repairs must be carried out by the manufacturer. POLON-ALFA is not responsible for the operation of equipment maintained and repaired by unauthorized personnel. 8.2.