INSTALLATION, USE AND MAINTENANCE MANUAL KHRP PINCH-POINT ENERGY RECOVERY UNITS Pag. 1 KHRP INSTALLATION, USE AND MAINTENANCE MANUAL...
Page 2
INDEX GENERALITY ...................................... 4 1.1.1 INTRODUCTION ................................... 4 1.1.2 BASIC SAFETY RULES ..............................4 1.1.3 SYMBOLOGY ..................................5 1.1.4 WARNINGS ..................................5 1.1.5 COMPLIANCE ..................................6 1.1.6 IDENTIFICATION ................................6 1.1.7 DELIVERY STATE .................................. 6 1.1.8 PACKAGING AND TRANSPORT ............................. 7 1.1.9 DISASSEMBLY AND DISPOSAL ............................
Page 3
6.1.1 CLEANING OR REPLACING FILTERS ............................ 24 6.1.2 CLEANING THE HEAT EXCHANGER ............................ 24 6.1.3 GENERAL CLEANING OF THE UNIT ............................ 24 6.1.4 OPERATION AND INFORMATION ON WIRELESS COMMUNICATION ................25 6.1.5 REMOTE CONTROL BATTERY SIGNAL AND REPLACEMENT ....................25 ALARMS ......................................
Page 4
GENERALITY INTRODUCTION This manual has been conceived with the aim of making the installation and management of your system as simple as possible. By reading and applying the suggestions in this manual, you will be able to get the best performance from the product you have purchased. We would like to thank you for the choice you made with the purchase of our product.
Page 5
SYMBOLOGY The symbols shown in the following booklet allow you to quickly provide information necessary for the correct use of the unit. Safety symbols ATTENTION Warns that the operations indicated are important for the safe operation of the machines. Only authorized personal DANGER Warns you that failure to comply with the prescriptions creates a risk of electric shock.
Page 6
COMPLIANCE The CE marking (present on each machine) certifies compliance with the following Community standards: • Low Voltage Directive 2014/35 / EC Electromagnetic Compatibility Directive 2014/30 / EC • • Ecodesign 2009/125 / EC • RoHS2 2011/65 / EU • WEEE 2012/19 / EC IDENTIFICATION...
Page 7
PACKAGING AND TRANSPORT The units are supplied for transport placed in cardboard boxes to be handled with care. The unit can be stored in a room protected from atmospheric agents with temperatures not below 0 ° C, up to a maximum of 40 ° C. DISASSEMBLY AND DISPOSAL Do not disassemble or dispose of the product yourself.
Page 8
INSTALLATION INSTALLATION CONDITIONS The unit must be installed according to national and local standards that regulate the use of electrical devices and according to the following indications: - install the unit inside residential buildings with an ambient temperature between 0 ° C and 45 ° C; - avoid areas near sources of heat, steam, flammable and / or explosive gases and particularly dusty areas;...
Page 9
If two units are used on the same wall, maintain a minimum distance of 1,2m between one core drilling and the next. If, on the other hand, two adjacent walls at an angle are used, maintain the minimum distance of 1,2m from the corner shared by the two walls with the coring.
Page 10
Sprinkle the hole made with cement mortar or polyurethane foam. Insert the telescopic tube inside the hole made and bring the part of the tube with the largest diameter flush with the external wall. Move the part of the pipe with the smaller diameter, bringing it flush with the internal wall.
Page 11
Release the cover from the motor holder by pressing on the side holes (1) using a small screwdriver (fig. 6). Fig. 6 Front cover release Break the shutter provided for the passage of connections (2), in the case of external connections not in the trench fracture the areas provided (3) both on the motor holder and on the cover (fig.
Page 12
ELECTRICAL CONNECTIONS GENERALITY - Before starting any operation to make the electrical connection make sure that the unit is not electrically powered. - Make the necessary electrical connections by consulting only the wiring diagram attached to this manual. - Install a suitable breaking and differential protection device for the exclusive service of the unit. - Check that the electrical components chosen for the installation (main switch, circuit breakers, cable section and terminals) are suitable for the electrical power of the installed unit and that they take into an account the starting currents of the compressor as well as the maximum load that can be reached.
Page 13
UNIT WIRING DIAGRAM Connect the 230/1/50 power supply to each installed appliance. Communication between devices takes place via wireless communication. There will be a master device with the supplied remote control and several slave units (up to 16) that will operate controlled through the network generated by the master unit.
Page 14
SYSTEM CONFIGURATION PROCEDURE GENERALITY The configuration must be carried out during the first commissioning by the installer or by qualified personnel. An incorrect configuration could compromise the proper functioning of the system. Carefully follow the configuration procedure described below. MASTER UNIT Power up all units in the system.
Page 15
SLAVE UNIT CONFIGURATION NB - The configuration of the slaves can only be carried out with the Master unit powered and in operation; Press and hold the info button for at least 5 seconds. The central signalling LED will flash quickly as indicated in the figure to the side, signalling the entry into the configuration.
Page 16
When the slave is coupled, the OUT led for extraction only (left led) and the IN led for supply only (central) will light up and flash alternately with the IN / OUT led of the automatic cycle (right) ↕ Max 5 cm Slave functioning mode selection It will now be possible to select the operating mode of the unit with respect to the master unit in supply / extraction...
Page 17
Confirm the choice by pressing and holding the IN / OUT cycle key and wait for the temporary stop of the fan which will then start operating again. ↕ Max 5 cm Confirm Slave configuration Use the remote control to approach the second slave and repeat the configuration in succession for all the slaves ↕...
Page 18
SLAVES REST / DISCONNECT PROCEDURE Press and hold the ON OFF key and wait for the central LED to start flashing quickly. The central signalling LED will flash quickly as indicated in the figure to the side, signalling the entry into the configuration.
Page 19
COMMISSIONING AND METHOD OF USE GENERALITY To ensure the “discharge” of the humidity that is naturally created inside the house, the unit must operate continuously at least at reduced speed (speed 1). If you turn off the ventilation unit, condensation may occur inside the unit and inside the building with possible moisture damage. OPERATION OF THE CONTROL UNIT The control unit consists of ten buttons which contain all the product functions inside them.
Page 20
REMOTE CONTROL UNLOCK / REENABLING After three minutes of inactivity, the remote control will go into lock / sleep mode to save energy. Press the Info button for at least 2 seconds to reactivate and unlock the remote control. 3 The remote control is ready for commands. READY Remote control unlocks from standby ON OFF UNIT / MODE AND SPEED SELECTION...
Page 21
SYSTEM STATUS REQUEST With the remote control active it is possible to interrogate the system to understand the status and the active functions. Press the info button and wait for the remote control to light up the status LEDs: The remote control will show after a few seconds and for a few seconds: Mode set •...
Page 22
EXTRA CYCLE OPERATION AND MODULATING REGENERATIVE RECOVERY The master in auto mode has the purpose of controlling the injection and extraction time to optimize the regenerative recovery cycle of the system. When the "Auto" mode is first activated, after 10 minutes and then every 12 hours, the "Master"...
Page 23
SETTING OF PARAMETERS (HUMIDITY THRESHOLD AND ACTIVATION OF LIGHT FUNCTION) Press and hold the AUTO button until the central LED flashes quickly. The central signalling LED will flash quickly as indicated in the figure to the side, signalling the entry into the parameter configuration.
Page 24
MAINTENANCE To always ensure correct and optimal operation of the unit, all maintenance interventions must be carried out periodically. WARNING: By removing the cover of the ventilation unit, in the -E- version, you can access live parts. CLEANING OR REPLACING FILTERS Disconnect the fan unit from the power supply.
Page 25
OPERATION AND INFORMATION ON WIRELESS COMMUNICATION The radio control interacts exclusively with the MASTER ventilation unit, which in turn sends the commands to the Slave Units. The Slave units that are out of range of the radio coverage of the MASTER unit receive commands from the nearest Slave unit;...
Page 26
ALARMS GENERALITY In the event of problems or breakdowns, contact the installer or the authorized service center. PROBLEMS RELATED TO THE OPERATION OF THE UNIT PROBLEM IT CAUSES REMEDIES -The power supply is not switched on -Check the power supply on the fan -The control unit of the unit does not work -Check the control unit and its relative power supply The fan does not turn on...
Page 27
ACCESSORIES The unit may be equipped with some installation accessories. Carefully read the instructions below for installing each individual accessory. KHRP-D WALL FIXING TEMPLATE The wall fixing template allows you to remove the unit from the wall without the need to remove the fixing screws to the wall.
Page 28
KHRP-E AESTHETIC EXTERNAL GRILLE The external aesthetic grille is a finishing grille external alternative to the external grill already supplied with the product. The grille provides for two-piece construction. One piece consists of a flat plate for convenient attachment of the grill to the wall. Fix the flat part of the aesthetic grid with the supplied plugs.
Page 29
KHRP-A CORNER EXIT KIT INSTALLATION The kit provides the possibility to install the product with the discharge not directed on the wall, but with an angular flow direction. For example, if you have parapets between the window and the external wall, it is possible to hide the grille using the corner kit and exiting close to the window.
Page 30
SYSTEM CONFIGURATION TABLE During installation, it is advisable to fill in the summary table of the system in order to keep track of the settings made, in order to facilitate any maintenance interventions. ARAMETER ETTINGS OCAL NVIRONMENT Direction of rotation in the Alternate Cycle HR% M...
Page 31
Produced by Sinergia s.r.l. Via del Commercio 1/A, 23017 Morbegno (SO) ITALY Distributed by Giacomini S.p.A. under the trademark Via per Alzo 39, 28017 San Maurizio d’Opaglio (NO) Italia consulenza.prodotti@giacomini.com +39 0322 923372 giacomini.com The data contained in this manual may be changed by the manufacturer without prior notice.