Page 3
HEATER LOCATION Avoid quiet areas: Preferred installation locations Directly above, below or outside bedrooms, living room, Above, below or outside laundry, bathroom, kitchen, garage lounge room, dining room etc. etc’ SEELEY INTERNATIONAL – INSTALLATION MANUAL...
Page 4
HEATER CONFIGURATION Standard External Configuration Reversed External Configuration Increase inlet spigot and duct Swapping inlet & outlet panels diameter by 50mm The heater side panels can be moved to suit a range of installations. To do this: Remove heater top panel. ...
Page 5
- this is not supplied by Braemar. Ensure that “COOL 2” is selected during system set-up to enable the system to operate the Braemar add-on cooling system - refer to “Commissioning” section in these instructions. SEELEY INTERNATIONAL – INSTALLATION MANUAL...
Page 6
GOOD DUCTING GUIDLINES 1. Based on standard 100 x 300mm floor outlets and 150mm round ceiling outlets. 2. Minimum outlets open to achieve optimum turndown performance. Correct ductwork installation is critical to ensure correct operation of 3. 'X' in model refers to extra-air models - maximum outlets will be the heating system, and to prevent premature failure of the fan reduced when a add-on cooling coil is installed.
Page 7
Ensure that all air is purged out of the gas line. for each additional zone - SCC/loom kit P/No 076010. Ensure that there are no gas leaks. and suitable wiring (not supplied by Seeley Zone dampers International) Gas Connection All Models SEELEY INTERNATIONAL – INSTALLATION MANUAL...
Page 8
ELECTRICAL CONNECTION SCC CONNECTION - TH, TSS3 Electrical wiring & fittings must be installed by a licensed Electrician. The SCC is connected directly to the BSC eeley International recommends that all Braemar gas ducted In a multiple-SCC system, this becomes the “master” SCC. Refer heaters are wired with a dedicated circuit from the distribution to instructions supplied with zone kit for connection of up to 3 board with a separate circuit breaker.
Page 9
SEELEY INTERNATIONAL – INSTALLATION MANUAL...
Page 11
Terminate condensate plug is secure condensate drain in drain in a suitable location a suitable location Remove & Remove & discard lower discard lower Condensate drain elbow Condensate drain elbow transit plug transit plug SEELEY INTERNATIONAL – INSTALLATION MANUAL...
Page 12
Flue 750 Min Isolation CEILING INSTALLATION valve Heater platform and clearances A = 385 or 510 ROOM FAN HX END supply Depends on model. The heater must be mounted on a platform to enable access for END OF OF HEATER servicing and maintenance.
Page 13
Flue drain hose Remove & discard Remove & discard Terminate condensate transit plugs Terminate condensate transit plugs Condensate drain tee drain in a suitable location Condensate drain tee drain in a suitable location assembly assembly SEELEY INTERNATIONAL – INSTALLATION MANUAL...
Page 14
FLUE SYSTEM & CONDENSATE DRAIN TH5, THM6, TSS5, TSS6 Flue system Braemar TH5, THM6, TSS5, TSS6 heaters must be flued using 100mm DWV plastic pipe and components complying with AS1260. The flue terminal on the side of the heater is designed to accept either the male end of a 100mm DWV M-F elbow, or 100mm DWV pipe. ...
Page 15
1000 +/- 100 Pa -TH516 1100 +/- 100 Pa -TH523/32 800 +/- 100 Pa OUTLET PRESSURE TEST POINT Outlet pressure test point HIGH PRESSURE ADJUSTMENT Gas Out LOW PRESSURE ADJUSTMENT INLET PRESSURE TEST POINT INLET PRESSURE TEST POINT SEELEY INTERNATIONAL – INSTALLATION MANUAL...
Page 16
SYSTEM SETUP Enable installed zones (SCC thermostat heaters only - not Set the time and day (SCC thermostat) required where multiple SCC's are installed) With the SCC in OFF mode, press and hold SET With the SCC in OFF mode, press and hold SET and press ZONE 1 ...
Page 17
WARRANTY SERVICE: 1300 650 644 TECHNICAL SUPPORT: 1300 650 399 Please have your appliance model number, serial number, and any displayed fault codes available prior to calling. SEELEY INTERNATIONAL – INSTALLATION MANUAL...
Page 18
DIAGNOSTIC CODES - Non Modulating Heaters (SCC thermostat required - refer service manual for full instructions) 3 STAR HEATERS Code Shut down SCC display Description type P-100 closed at start Reset, 1 P-100 failed to close Reset, 2 P-100 open during run Normal Ignition failure Reset, 7...
Page 19
SW 4 Heater model THM516N THM520N Heaters are THM530N supplied Example THM618N pre-set to THM623N the follow- THM623N THM632N dipswitch THM5X20 LPG settings 1 2 3 4 THM5X30 LPG THM6X23 LPG THM6X32 LPG TSS420N TSS523N TSS623N SEELEY INTERNATIONAL – INSTALLATION MANUAL...
Page 20
Warranty Service Australia 1-300-650-644 seeleyinternational.com It is the policy of Seeley International to introduce continual product improvement. Accordingly, specifications are subject to change without notice. Please consult with your dealer to confirm the specifications of the model selected. www.braemar.com.au 645377a...
Need help?