LanPro UPS
OPERATING MANUAL
UNINTERRUPTIBLE POWER SUPPLY
LanPro 31
8 - 10 - 15 - 20 kVA
Series 1
6595 Riazzino (Locarno)
Switzerland
Technology for the digital world
GE Digital Energy
Telephone: +41 (0) 91/850 51 51
Fax:
+41 (0) 91/850 51 44

Advertisement

loading
Need help?

Need help?

Do you have a question about the LanPro 1 Series and is the answer not in the manual?

Questions and answers

Summary of Contents for GE LanPro 1 Series

  • Page 1 GE Digital Energy OPERATING MANUAL UNINTERRUPTIBLE POWER SUPPLY LanPro 31 8 - 10 - 15 - 20 kVA Series 1 GE Digital Energy 6595 Riazzino (Locarno) Telephone: +41 (0) 91/850 51 51 General Electric Company Switzerland Fax: +41 (0) 91/850 51 44...
  • Page 2 The present publication and any other documentation supplied with the UPS system is not to be reproduced, either in part or in its entirety, without the prior written consent of GE Digital Energy. The illustrations and plans describing the equipment are intended as general reference only and are not necessarily complete in every detail.
  • Page 3 GE Digital Energy Dear Customer, We thank you for selecting our products and are pleased to count you amongst our very valued customers at GE Digital Energy. We trust that the use of the Lanpro 31 Uninterruptible Power Supply system,...
  • Page 4 GE Digital Energy Table of contents 1. INTRODUCTION & SAFETY RULES..................6 INTRODUCTION ........................6 SAFETY RULES ........................6 1.2.1 General ..........................6 1.2.2 Installation ..........................6 1.2.3 Storage ..........................7 1.2.4 Batteries ..........................7 2. FUNCTIONAL EXPLANATION ....................8 THE PRINCIPLES OF OPERATION ..................8 NORMAL CONDITIONS ......................8 MAINS FAILURE........................9...
  • Page 5 GE Digital Energy 5. INTERFACE FEATURES ......................33 COMCONNECT (RS232) INTERFACE...................33 POTENTIAL FREE CONTACT INTERFACE................34 SNMP INTERFACE (OPTIONAL) ..................34 6. OPTIONS ..........................35 EXTENDED RUN-TIME VERSIONS ..................35 SNMP INTERFACE CARD .....................35 7. MAINTENANCE ........................36 GENERAL..........................36 COOLING FAN........................36 BATTERIES ..........................36 SAFETY ..........................37...
  • Page 6 GE Digital Energy 1. INTRODUCTION & SAFETY RULES 1.1 INTRODUCTION More than ever before, today's advanced electronic equipment, with complex integrated circuits and other sensitive electronics, needs a stable and continuous AC power supply to operate correctly. While the power coming from the wall socket outlet is often unreliable, a LanPro 31 UPS provides the security of completely uninterrupted power.
  • Page 7 GE Digital Energy 1.2.3 Storage Store the UPS in a dry location, storage temperature must be within –20°C to +45°C. If the unit is stored for a period exceeding 3 months, the batteries must be recharged periodically. Connect the unit to the mains and switch it on for a period of approx. 48 hours, minimum every 3 months.
  • Page 8 GE Digital Energy 2. FUNCTIONAL EXPLANATION 2.1 THE PRINCIPLES OF OPERATION The LanPro 31 UPS stores electric energy in batteries housed in the unit. This allows the UPS to supply output power even when the incoming mains power is cut OFF completely.
  • Page 9 GE Digital Energy 2.3 MAINS FAILURE In the event of a mains power failure (i.e. absent or outside tolerance) the system uses the energy reserve stored in the battery to continue to produce AC power, ensuring unbroken output (fig. 2). No interruption or alteration will ever be noticed in the output power.
  • Page 10 GE Digital Energy 2.5 AUTOMATIC BYPASS SWITCH If the output converter is unable to deliver the demanded output power (overload, overtemperature) the bypass switch will automatically transfer the load to the mains. If bypass operation is caused by an overload situation, the UPS will only switch back to output converter if the load is reduced to less than 100%.
  • Page 11 GE Digital Energy 2.6 MANUAL BYPASS SWITCH The system can be bypassed manually using the manual bypass switch located at the rear panel. It is a two-position switch: the normal position is “1”: as in figures 1-2. Position “2” is the service position: the load is directly connected to the mains input.
  • Page 12 The shipping box contains a LanPro 31 UPS and this manual. Inspect the UPS for damage after unpacking. If any damage is present please immediately notify the carrier and the GE Digital Energy distributor. If a battery extension pack is to be connected to the UPS, a connection kit is required.
  • Page 13 GE Digital Energy Installation procedure: Please refer to figure 6 in chapter 4.1 and drawing “TERMINALS” for the location of terminals. Remove the rear grid by loosening the 4 screws. Remove the middle front panel that covers the MCB-switches. Hold the panel at both sides and pull firmly.
  • Page 14 GE Digital Energy 18. In order to calculate the available back-up time related to the actual load, information on the capacity of the battery set is stored in the UPS. As the total battery capacity changes when battery extension packs are installed, the battery capacity must be re-programmed.
  • Page 15 GE Digital Energy 4. OPERATION 4.1 DESCRIPTION OF FRONT AND REAR PANEL LCD screen 2x16 characters, shows UPS system data, status messages, settings. 2 - 4 Push-buttons With the button keypads “down” (2) and “up” (4) you can scroll through the...
  • Page 16 GE Digital Energy Figure 6 – Rear panel 10 Manual Bypass Switch: 1 = load on UPS 2 = load on bypass 11 Input terminals: 7 (L1) / 8 (L2) / 9 (L3) 10 = neutral 11 = protective earth...
  • Page 17 GE Digital Energy 4.2 START-UP Switch on the UPS with switch “inverter ON/OFF” (7), MCB “mains ON/OFF” (8) and MCB “bypass ON/OFF” (9). If battery extension packs are part of the system, turn the DC-MCBs on the UPS as well as on the extension pack(s) into “ON” position.
  • Page 18 GE Digital Energy 4.3 USE Once the unit is in operation, there is no need to switch the unit ON/OFF during use. If an emergency shutdown switch has been installed (see chapter 3.3) the UPS will stop immediately when the switch is opened.
  • Page 19 GE Digital Energy 4.3.1 Information screens When the default screen is displayed the first information screen can be entered by depressing the “up” key (4). Using “up” and “down” (2) you can scroll through the several information screens. After the last information screen the default screen will appear.
  • Page 20 GE Digital Energy 4.3.2 Status Messages and Alarm Messages The LanPro 31 UPS alerts the user with a standard alarm screen that the operating mode has changed and/or that an alarm situation occurs: ON LINE The actual operating mode, the possible modes are ALARM (press up) mentioned below.
  • Page 21 GE Digital Energy LOADnotPROTECTED The temperature of the cooling plates or output transformer is TEMP TOO HIGH too high. As a result the load may be transferred to bypass. The operating temperature can rise intolerable as a result of: • extreme environmental temperature;...
  • Page 22 GE Digital Energy LOADnotPROTECTED The remaining autonomy is less than the set time (standard 2 BATTERY LOW minutes). This text alternates with the following screen: UPS SHUTDOWN The output voltage can be lost after the indicated time due to LEFT 2 MINUTES discharged battery.
  • Page 23 GE Digital Energy INPUT AND OUTPUT The output frequency is not synchronised to the mains (input) NOT SYNCRONIZED frequency. The automatic bypass switch is not able to transfer the load from output converter to bypass and reverse (see chapter 2.5).
  • Page 24 GE Digital Energy 4.3.3 Service screens When the default screen is displayed you can enter the first service screen by depressing the keys “down” (2) and “enter/reset” (3) simultaneously during approx. 1 second. Using “up” and “down” (2) you can scroll through the several service screens.
  • Page 25 GE Digital Energy QUICK BATTERY Start of the manual Quick Battery Test. TEST PRESS ENTER See for more information chapter 4.4.2 “Quick Battery Test”. CALIBRATE BAT Start of the manual Deep Battery Calibration Test. Press DOWN+ENTER See for more information chapter 4.4.3 “Deep Battery Calibration Test”.
  • Page 26 GE Digital Energy 4.3.4 Setup menu To enter the setup menu: 1- Be sure the UPS is switched OFF. 2- Press push-button “enter/reset“ (front panel) and simultaneously turn switch “UPS ON/OFF“ (front panel) into position “ON“ (up). Using push-buttons “up“ and “down“ you can scroll through the several setup screens, “enter/reset“...
  • Page 27 GE Digital Energy OUTPUT VOLTAGE The system output voltage. 230V Range: 220/230/240 VAC. BATTERY CAPACITY Battery capacity. Range: 7 through 590 Ah, in 1 Ah steps. WARNING ! If you proceed, the information about the actual battery condition (as a result of a deep battery test) is lost.
  • Page 28 GE Digital Energy 4.4 TEST SCREENS These screens show the test procedure, either started from the service menu (front panel keys) or via the UPS monitoring software (ComConnect Port). The upper line indicates the kind of test, the second line its proceeding.
  • Page 29 GE Digital Energy QUICK BATTERY The test status (indicated by the second line) can be: TEST START TEST ACTIVATED testing. TEST SUCCESSFUL battery has been tested with positive result. TEST FAILED battery test was terminated due to a load variation superior 200 Watt.
  • Page 30 GE Digital Energy Procedure From the standard menu first enter the service menu (press “down” and “enter/reset” simultaneously during 2 seconds). Subsequently press “down” until the following screen appears: CALIBRATE BAT Press “down” (2) + “enter/reset” (3) simultaneously, during at Press DOWN+ENTER least 1 second.
  • Page 31 GE Digital Energy 4.5 OTHER FEATURES 4.5.1 ECO-mode The UPS is equipped with the “ECO-Mode” feature. If the feature is enabled, the load is operated on mains through the electronic bypass switch. If the mains is interrupted or out of limits the load is automatically transferred to the inverter.
  • Page 32 GE Digital Energy 4.5.4 Sleep and wake-up Probably your UPS monitoring software allows you to program a “sleep period” of the UPS by sending two commands to the UPS: - shutdown after # minutes and subsequently: - shutdown during # hours.
  • Page 33 LANserver, IBM AS/400. Remote servicing through a modem (external) is possible with GE Service Software. We strongly recommend to use only original GE software products in combination with the ComConnect interface port. We only guarantee proper operation of original GE products.
  • Page 34 GE Digital Energy 5.2 POTENTIAL FREE CONTACT INTERFACE Furthermore four potential free contacts are available for signalling to a user-defined system: see fig. 6 connector 17 – Section 4.1. Potential free contacts: functions and pin numbers Function Normally open Coommon...
  • Page 35 GE Digital Energy 6. OPTIONS 6.1 EXTENDED RUN-TIME VERSIONS Extended run-time versions are equipped with additional batteries to increase the autonomy time of the unit. These additional batteries are housed in a separate battery cabinet. Additional batteries will increase the recharging time for the unit.
  • Page 36 GE Digital Energy 7. MAINTENANCE 7.1 GENERAL When used properly, the LanPro 31 UPS is virtually maintenance free. Take care of proper environmental conditions (see chapter 3.2 – “location”) and keep air inlets/outlets free from dust. 7.2 COOLING FAN The expected operational life of the cooling fans is approximately 20.000 to 40.000 hours of continuous operation.
  • Page 37 GE Digital Energy 7.4 SAFETY WARNING! When the LanPro 31 is operating, all parts of the electronics are directly connected to the mains and high voltages are present on all internal parts, including the battery. Even after disconnection from the mains, all parts inside the UPS, including the battery, conduct dangerous voltages (except the ComConnect output).
  • Page 38 GE Digital Energy 8. TROUBLESHOOTING Whenever a malfunction occurs, first check external factors (e.g. connections, temperature, humidity or load) to determine whether the problem is caused by the unit itself or by its environment. Always check these external factors before concluding that your LanPro 31 UPS is faulty.
  • Page 39 GE Digital Energy SELFTEST FAILURE The step-up converter, which is a part of the input converter, IC STEP UP failed during start-up. Please contact your dealer. SELFTEST FAILURE Checking the external batteries, the UPS detected a failure in EXT. BATTERY the hardware.
  • Page 40 GE Digital Energy 9. ANNEX 9.1 TECHNICAL DATA SHEETS Can be found included in the last section and are listings of the technical data of the UPS. 9.2 TECHNICAL DIAGRAMS These are included in the last sections and include assembly layouts and functional drawings.