Summary of Contents for Vertiv HILON 2G

  • Page 2 265069 HILON 2G User Manual...
  • Page 3: Table Of Contents

    5.11 ........................52 TATUS AND VENT STATUS CONFIGURATION PROPERTIES AND SPECIAL COMMANDS ................53 OPTIONS IN RETRIEVING DATA FROM THE HILON 2G ..................54 NOTICE TO EUROPEAN UNION CUSTOMERS: DISPOSAL OF OLD APPLIANCES ......... 55 ROHS C ................................... 55 OMPLIANCE APPENDIX A: XIF FILES .................................
  • Page 4: Introduction

    ENM160 Powerface 48 VDC 48VDC HILON 2G must be directly connected to the controller of the Unit, representing a node for a LonWorks BMS. In a LonWorks network, intelligent control devices, called nodes, communicate among each other using a common protocol. Each node in the network contains embedded intelligence that implements the protocol and performs control functions.
  • Page 5: Hardware And Firmware Info

    6 status LEDs There is neither external memory to the processor nor external UART components on RS485 channel (Hironet side). Firmware info HILON 2G Firmware has been built using: Echelon NodeBuilder FX 4.01.07 application Neuron Chip FW Version: 19. Spare Parts...
  • Page 6: User Connections

    3. User connections HILON 2G will be mounted inside the electrical panel on the DIN Rail. The pictures below show the connection that must be done, in relation also to the different types of cards that can be mounted on the Unit.
  • Page 7: Connection To Microface Eboard

    IGURE CONNECTION BETWEEN OWERFACE AND Warning: Be sure that, when you connect the Hironet cable to the card, the Unit is switched-on and the HILON 2G is switched off. Then switch on the HILON 2G. 265069 HILON 2G User Manual...
  • Page 8: Supply Connection

    Transformer 24VAC/24VAC 10VA 255877 For iCOM/MicrofaceE The Transformer (48 Vdc – 24 Vdc) to supply the HILON 2G on Units mounting Powerface 48 VDc cards is included in the HILON2G Kit Mobile 48VDC package (code 480206). This is a galvanicaly-isolated transformer.
  • Page 9: Lon Connection

    LED 6 Green: It is ON when the Hironet Communication is active, it Blinks during the start-up and in case of fault in the communication. Service PIN button: used to install the HILON 2G into a Node Manager and to become a part of a LON network by sending the Neuron ID code.
  • Page 10 For example the presence of typical TLC devices (big inverters, UPS switching-feeders…) makes it necessary the use of screened cable, to avoid possible transmission data losses. The cable must be in any case a twisted pair. 265069 HILON 2G User Manual...
  • Page 11: Architecture

    4. Architecture All Vertiv Cooling units (see Chapter ) mounting iCOM/Microface E, Powerface controllers with standard software and Hironet protocol enabled, can be connected to HILON 2G via the Hironet connector. One HILON 2G is needed per each Cooling unit: 4.1: I...
  • Page 12 Examples of network topology: 4.2: S IGURE INGLY TERMINATED TOPOLOGY 4.3: D IGURE OUBLE TERMINATED TOPOLOGY 4.4: S IGURE TAR TOPOLOGY 4.5: L IGURE OOP TOPOLOGY 4.6: M IGURE IXED TOPOLOGY 265069 HILON 2G User Manual...
  • Page 13: Hilon2G Commissioning Through Lonmaker Tm

    HILON2G is properly connected to the PC where LonMaker is running. The PC must be equipped with interface Card, such U10/U20 Network Interface https://www.echelon.com/products/interconnectivity/network-interfaces/u10-20.htm. From the main LonMaker dialog you can choos to create a new network after providing a Network Name: 4.7-M ICTURE AKER DIALOG 265069 HILON 2G User Manual...
  • Page 14 In the first Dialog choose “Network Attached”: 4.8-LON IGURE INTERFACE SELECTION In this step check the “Onnet” option. 4.9-I IGURE NTERFACE STATUS SELECTION 265069 HILON 2G User Manual...
  • Page 15 ETWORK NTERFACE DEFINITION Click on “OK” Button if further dialogs are raised up. The configuration of the LNS interface is finished, so that it is possible to add the HILON2G device to the LON network. 265069 HILON 2G User Manual...
  • Page 16 COMMISSIONING OPTION Second step is fundamental to load the correct XIF file for the Device. The XIF file is a text file provided to assign textual descriptions to the SNVT variables defined into the HILON2G. Using 265069 HILON 2G User Manual...
  • Page 17 “Browse…” button select the correct XIF file (provided in the Vertiv Connectivity CD) and then click “Next >”. 4.13- IGURE COMMISSIONING OPTION CONTINUED NOTE: do not choose the “Upload from device” option because the HILON2G device does not provide by itself any textual description of the available SNVT variables.
  • Page 18 The following step is important because the user must NOT “Load application image” since the most recent Firmware is always uploaded in the factory. NOTE: we do NOT provide .APB, .NDL or .NXE files to the client. 4.16-U IGURE PLOAD PPLICATION OPTIONS 265069 HILON 2G User Manual...
  • Page 19 If the Section “Total Received” of the Dialog shows incrementing numbers but nothing happens, probably the problem is due to a wrong .XIF file. In this case contact Vertiv Service. Now the HILON2G device is commissioned inside the LON network and ready to be monitored.
  • Page 20 UNCTIONAL LOCK Then select the Functional Block corresponding to the monitored Unit Type (see Chapter 5), and select the “Create all network variables shapes” 4.20-F IGURE UNCTIONAL LOCK OPTIONS Reply “Yes” to the confirmation dialog: 265069 HILON 2G User Manual...
  • Page 21 To open the LonBrowser window right-click on the Functional Block and choose “Browse…” 4.21-F IGURE UNCTIONAL LOCK BROWSING 265069 HILON 2G User Manual...
  • Page 22: Parameters And Event Lists

    SNVTs types used by HILON 2G The parameters related to an Air Conditioning unit can be represented by a LonWork SNVT type. The following types of SNVT are used by the LonWorks application running into the HILON 2G device. SNVT Type...
  • Page 23: Parameters For All Sw Types

    Represents the Type of SW of the Card connected: - 104 means PAL104 - 202 means SCM202 - 200 means CRV200 - 160 means EVM160 - 100 means ENM160 5.3: SNVT SW T ABLE COMMON TO ALL YPES 265069 HILON 2G User Manual...
  • Page 24: Events State Vectors

    Bit # bit40 bit41 bit42 bit43 bit44 bit45 bit46 bit47 Event # Bit # bit48 bit49 bit50 bit51 bit52 bit53 bit54 bit55 Event # Bit # bit56 bit57 bit58 bit59 bit60 bit61 bit62 bit63 Event # 265069 HILON 2G User Manual...
  • Page 25 Note that not all 255 possible bits are mapped to actual existing Events. Example of Usage: SW for PDX A9H Event 173 = Fire Alarm is raised bit45 will be set to 1 in nvoAlarms3: 45 + 128 = 173. 265069 HILON 2G User Manual...
  • Page 26: Pa 1.04+ Sw Type

    1 no sensor Glycol 2 to 25 ºK Room Temperature TempSet temp 5.0 to 40.0 ºC PA + A9H Setpoint Room Humidity HumiSet lev_percent 19 means no humidity PA + A9H Setpoint control 20 to 80 %r.H. 265069 HILON 2G User Manual...
  • Page 27 Stop FC Roomsetpoint dt3_Diff temp 0.0 means no measured PA + A9H difference 1 to 25 K High Temperature HiTemp temp 0 means no high PA + A9H Warning temperature warning 1 to 99 ºC 265069 HILON 2G User Manual...
  • Page 28 Enables the CW valve CW_Reset count reset 0 = No, 1 = Yes Enables underfloor FanPres_EN count pressure control 0 = No, 1 = Yes Fan Back Draft Control FanVSD_BDR count (Fan speed) 0 – 100% 265069 HILON 2G User Manual...
  • Page 29 PA + A9H Analog Output 2 AnaOutRam2 count 0 – 100% PA + A9H Analog Output 3 AnaOutRam3 count 0 – 100% PA + A9H Analog Output 4 AnaOutRam4 count 0 – 100% PA + A9H 265069 HILON 2G User Manual...
  • Page 30: Events For : - Pcw-Pdx Units With Icom And A9H Sw Type - Hpm Units With Icom And Pa 1.04+ Sw Type

    Warning Unit 7 disconnected Unit 7 disconnected Warning Unit 8 disconnected Unit 8 disconnected Warning Unit 9 disconnected Unit 9 disconnected Warning Unit 10 disconnected Unit 10 disconnected Warning Unit 11 disconnected Unit 11 disconnected 265069 HILON 2G User Manual...
  • Page 31 LOSS OF FLOW (CUSTOMER INPUT) LOSS OF FLOW (CUSTOMER INPUT) STBY GLYCOL PUMP ON (CUSTOMER PUMP BOARD 1 FAILURE Alarm INPUT) STANDBY UNIT ON (CUSTOMER PUMP BOARD 2 FAILURE Alarm INPUT) Warning HW/HG HRS EXCEEDED HW/HG HRS EXCEEDED 265069 HILON 2G User Manual...
  • Page 32 Unit 24 disconnected Warning Unit 25 disconnected Warning Unit 26 disconnected Warning Unit 27 disconnected Warning Unit 28 disconnected Warning Unit 29 disconnected Warning Unit 30 disconnected Warning Unit 31 disconnected Warning Unit 32 disconnected 265069 HILON 2G User Manual...
  • Page 33 GC1 TVSS FAILURE (*) Warning GC2 TVSS FAILURE (*) Warning FAN 1 WARNING Warning FAN 2 WARNING Warning FAN 3 WARNING Warning FAN 4 WARNING Warning FAN 1 ALARM Warning FAN 2 ALARM Warning FAN 3 ALARM 265069 HILON 2G User Manual...
  • Page 34 CIRC 2 HIGH SUPERHEAT Warning FAN OVERDRIVE Warning NO COOLING BY CHILLER Warning FEEDBACK SIGNAL 2 FAILURE FEEDBACK 2 FAILURE Warning SEQUENCER NOT AVAILABLE Alarm EC FAN FAULT (*) Event available for PDX units only 265069 HILON 2G User Manual...
  • Page 35: Parameters For Crv Units With Icom And B1O Sw Type

    0 = off; 1 = on Dehumidification Cooling Proportional TempProp_C temp 1.0 to 15.0 K Band Heating Proportional TempProp_H temp 1.0 to 15.0 K Band Humidity Proportional HumiProp_H lev_percent 1 to 25 %r.H. Band 265069 HILON 2G User Manual...
  • Page 36 SupplySet temp The same for Out variable Unit Alarm GenAlarm count 4 (Alarm Acknowledge) acknowledge / Reset 2 (Alarm Reset) See Chapter 5.11 Unit On-Off HMSysOn lev_disc 0 = Off (ST_OFF) 4 = On (ST_ON) 265069 HILON 2G User Manual...
  • Page 37: Events For Crv Units With Icom And B1O Sw Type

    LWD SENSOR FAIL Message HUMIDIFIER SUSPENDED Message HUMIDIFIER RESUMED Alarm RAM / BATTERY FAIL Alarm LOW MEMORY 1 Warning NO CONNECTION W/UNIT1 Alarm HIGH SUPERHEAT Alarm LOW SUPERHEAT Alarm ENVELOPE ALARM Alarm SYS STATPRES SENSFAIL 265069 HILON 2G User Manual...
  • Page 38 REM SENSOR 06 HI HUM Warning REM SENSOR 07 HI HUM Warning REM SENSOR 08 HI HUM Warning REM SENSOR 09 HI HUM Warning REM SENSOR 10 HI HUM Warning REM SENS AVG LO TEMP 265069 HILON 2G User Manual...
  • Page 39 REM SEN AVG HI HUM Warning REM SEN SYS LO HUM Warning REM SEN SYS HI HUM Warning NO COOLING FROM CHILLER Message SEC LOW PRESSURE Alarm SEC LOW PRESSURE Alarm GC1 REM SHUT DOWN 265069 HILON 2G User Manual...
  • Page 40 REM SENSOR 1 – 10 FAILURE Warning HIGH RETURN TEMPERATURE Message ROOM HUMIDITY PROBLEM Alarm EXV VALVE ALARM Alarm VSD SENSOR FAILURE Alarm VSD DRIVE FAILURE Alarm VSS LOCKED Warning BOTTOM FAN FAILURE Message COMP 1 LOCKED OUT 265069 HILON 2G User Manual...
  • Page 41: Parameters For : - Hpm Units With Icom Or Microface Eand Ev 160+ Sw Type - Powerface And En160.100 Sw Type

    Difference Room - difference Glycol 1 no sensor Glycol 2 to 25 K Room Temperature TempSet temp 5.0 to 40.0 ºC Setpoint Room Humidity HumiSet lev_percent 19 means no humidity Setpoint control 20 to 80 %r.H. 265069 HILON 2G User Manual...
  • Page 42 19 means no humidity Setpoint control 20 to 80 %r.H. Temperature TempProp temp 1.0 to 30.0 K Proportional Band Humidity Proportional HumiProp lev_percent 2 to 60 %r.H. Band Humidity Integration HumiIntg count 4 means no integration Factor factor 265069 HILON 2G User Manual...
  • Page 43 Number of Standby StdByUnit count [0..15] Unit Unit Alarm GenAlarm count 4 (Alarm Acknowledge) acknowledge / Reset 2 (Alarm Reset) See Chapter 5.11 Unit On-Off HMSysOn_Mi lev_disc 0 = Off (ST_OFF) 4 = On (ST_ON) 265069 HILON 2G User Manual...
  • Page 44: Events For - Hpm Units With Icom Or Microface Eand Ev 160+ Sw Type - Powerface And En160.100 Sw Type

    Warning (AR) Unit 7 disconnected Warning (AR) Unit 8 disconnected Warning (AR) Unit 9 disconnected Warning (AR) Unit 10 disconnected Warning (AR) Unit 11 disconnected Warning (AR) Unit 12 disconnected Warning (AR) Unit 13 disconnected 265069 HILON 2G User Manual...
  • Page 45 USER INPUT 3 TRIGGERED 94 (*) Warning USER INPUT 4 TRIGGERED 95 (*) Alarm USER INPUT 4 TRIGGERED 96 (*) Warning PUMPDOWN COMP. 2 NOT COMPLETED (*) Events from 91 to 96 only for Powerface equipped units. 265069 HILON 2G User Manual...
  • Page 46: Parameters For Hpc Units With Icom And Sc 2.02+ Sw Type

    Please note that the value Microface returned by the device holds the current alarm-status of the unit. See Chapter Analog Condenser AnaConden1 lev_percent 0 to 100 %. Output 1 Analog Condenser AnaConden2 lev_percent 0 to 100 %. Output 2 265069 HILON 2G User Manual...
  • Page 47 -25.0 to 8.0 C° Lower Than this value in °C High Water Temp. HWTempInWa temp 0.0 to 99.0 °C Warning Inlet at Low Water Temp. LWTempInWa temp 0.0 to 99.0 °C Warning Inlet at 265069 HILON 2G User Manual...
  • Page 48 General Alarm GenAlarm count 4 (Alarm Acknowledge) Microface 2 (Alarm Reset) See Chapter 5.11 System On / Off HMSysOn_Mi lev_disc 0 (Unit OFF) 4 (Unit ON) (*) Avaliable only for Units Equipped with 4 screw Compressors. 265069 HILON 2G User Manual...
  • Page 49: Events For Hpc Units With Icom And Sc 2.02.Xxx Sw Type

    Warning (AR) Unit 6 disconnected Warning (AR) Unit 7 disconnected Warning (AR) Unit 8 disconnected Warning (AR) Unit 9 disconnected Warning (AR) Unit 10 disconnected Warning (AR) Unit 11 disconnected Warning (AR) Unit 12 disconnected 265069 HILON 2G User Manual...
  • Page 50 Alarm COMPRESSOR 4 LOW PRESSURE Alarm COMPRESSOR 3 OIL PRESSURE Alarm COMPRESSOR 4 OIL PRESSURE Alarm COMPRESSOR 3 THERMAL PROTECTION Alarm COMPRESSOR 4 THERMAL PROTECTION Alarm LOW CONDENSER PRESSURE 3 Alarm LOW CONDENSER PRESSURE 4 265069 HILON 2G User Manual...
  • Page 51 CONDENSER 3 FANS FAILURE Warning CONDENSER 4 FANS FAILURE Alarm (AA, AR) SLAVE MICROFACE 2 NOT CONNECTED Warning USER INPUT 2 TRIGGERED Alarm USER INPUT 2 TRIGGERED Message (AR, NA) RECOVERY STOPPED Message (AR, NA) RECOVERY OK 265069 HILON 2G User Manual...
  • Page 52: Unit Status And Event Status

    21= Alarm not acknowledged (inact) 23= Alarm not acknowledged (act) 25= Alarm and warning acknowledged (inact) 27= Alarm and warning acknowledged (act) 29= Alarm and warning not acknowledged (inact) 31= Alarm and warning not acknowledged (act) 265069 HILON 2G User Manual...
  • Page 53: Configuration Properties And Special Commands

    - nvoGenAlarm: represents the Events status. UCPTEvtType: Type of events to be sent on LON side It is possible to set the HILON 2G device in order to filter the events coming from the Unit, and pass to the BMS only a specified sub-category.
  • Page 54: Options In Retrieving Data From The Hilon 2G

    The SNVT variable, containing the integer value related to the Event SNVT_count nvoALARME, is delivered by the HILON 2G and therefore must be read by the BMS before the next incoming Alarm. As a consequence the monitoring BMS’s Binding operation, of SNVT_switch nvoALARME variable, is strongly suggested.
  • Page 55: Notice To European Union Customers: Disposal Of Old Appliances

    (WEEE). of this equipment, please browse https://www.vertivco.com/en- us/about/contacts/. ROHS Compliance The HILON 2G device complies with the Restriction of Hazardous Substances Directive (ROHS), prohibiting use of six hazardous materials manufacturing of electronics, including lead-free solder. 265069 HILON 2G User Manual...
  • Page 56: Appendix A: Xif Files

    Appendix A: XIF files XIF configuration File. provided into Vertiv Connectivity CD: H2G_PDX_3_2.XIF File: H2G_DevTempl.XIF generated by LONNCC32 Version 5.01.07, XIF Version 4.402 Copyright (c) Echelon Corporation 1989-2010 All Rights Reserved. Run on Wed Feb 01 12:25:10 2017 90:00:E7:46:00:04:04:06 2 10 0 112 0 3 3 3 3 3 3 11 9 2 4 7 0 16 30 1 1 128 112 0 0 0 0 0 0 0 0 0 2 10 0 0 0 0 0 2 49 0 0...
  • Page 57 3 3 1 0 0 3 4 1 0 0 3 5 1 0 0 3 6 1 0 0 3 7 1 0 0 3 0 1 0 0 3 1 1 0 0 265069 HILON 2G User Manual...
  • Page 58 3 4 1 0 0 3 5 1 0 0 3 6 1 0 0 3 7 1 0 0 3 0 1 0 0 3 1 1 0 0 3 2 1 0 0 265069 HILON 2G User Manual...
  • Page 59 3 5 1 0 0 3 6 1 0 0 3 7 1 0 0 3 0 1 0 0 3 1 1 0 0 3 2 1 0 0 3 3 1 0 0 265069 HILON 2G User Manual...
  • Page 60 0 1 63 1 0 1 0 1 0 1 0 0 0 "@2#24 39 * 1 2 0 0 0 0 VAR nvoPAEEAPHumi 17 0 0 0 0 1 63 1 0 1 0 1 0 1 0 0 0 "@2#25 81 * 1 265069 HILON 2G User Manual...
  • Page 61 2 0 0 0 0 VAR nvoPAValve3P 32 0 0 0 0 1 63 1 0 1 0 1 0 1 0 0 0 "@2#40 81 * 1 2 0 0 1 0 VAR nvoPATempIntg 33 0 0 0 265069 HILON 2G User Manual...
  • Page 62 0 1 63 1 0 1 0 1 0 1 0 0 0 "@2#55 81 * 1 2 0 0 1 0 VAR nvoPALoHumiE 48 0 0 0 0 1 63 1 0 1 0 1 0 1 0 0 0 "@2#56 265069 HILON 2G User Manual...
  • Page 63 39 * 1 2 0 0 0 0 VAR nviPAHiHumiE 63 0 0 0 0 1 63 0 0 1 0 1 0 1 0 0 0 "@2#13 81 * 1 2 0 0 1 0 265069 HILON 2G User Manual...
  • Page 64 0 1 63 1 0 1 0 1 0 1 0 0 0 "@2#69 8 * 1 2 0 0 0 0 VAR nvoFanPres_EN 79 0 0 0 0 1 63 1 0 1 0 1 0 1 0 0 0 265069 HILON 2G User Manual...
  • Page 65 0 1 63 1 0 1 0 1 0 1 0 0 0 "@2#85 39 * 1 2 0 0 0 0 VAR nvoHil_InWat2 94 0 0 0 0 1 63 1 0 1 0 1 0 1 0 0 0 "@2#86 39 * 1 265069 HILON 2G User Manual...
  • Page 66 2 0 0 0 0 VAR nvoAnaOutRam2 109 0 0 0 0 1 63 1 0 1 0 1 0 1 0 0 0 "@2#103 8 * 1 2 0 0 0 0 VAR nvoAnaOutRam3 110 0 0 0 265069 HILON 2G User Manual...
  • Page 67 \x78 \x00 \x00 \x00 \x00 \x00 \x00 \x00 \x00 \x00 \x00 \x00 \x00 \x00 \x00 \x00 \x00 \x00 \x00 \x00 \x00 \x00 \x00 \x00 \x0A \x00 \x32 \x00 \x05 \x00 \x00 \x03 \x14 FILE readOnly 2 1 \x01 \x00 \x00 \x14 265069 HILON 2G User Manual...
  • Page 68 XIF configuration File. provided into Vertiv Connectivity CD: H2G_CRV_3_0.XIF File: H2G_DevTempl.XIF generated by LONNCC32 Version 5.01.07, XIF Version 4.402 Copyright (c) Echelon Corporation 1989-2010 All Rights Reserved. Run on Thu Mar 10 09:29:59 2016 90:00:E7:46:00:04:04:09 2 10 0 68 0 3 3 3 3 3 3 11 9 2 4 7 0 16 30 1 1 128 68 0 0 0 0 0 0 0 0 0 2 10 0 0 0 0 0 2 49 0 0...
  • Page 69 3 5 1 0 0 3 6 1 0 0 3 7 1 0 0 3 0 1 0 0 3 1 1 0 0 3 2 1 0 0 3 3 1 0 0 265069 HILON 2G User Manual...
  • Page 70 3 6 1 0 0 3 7 1 0 0 3 0 1 0 0 3 1 1 0 0 3 2 1 0 0 3 3 1 0 0 3 4 1 0 0 265069 HILON 2G User Manual...
  • Page 71 3 7 1 0 0 3 0 1 0 0 3 1 1 0 0 3 2 1 0 0 3 3 1 0 0 3 4 1 0 0 3 5 1 0 0 265069 HILON 2G User Manual...
  • Page 72 2 0 0 0 0 VAR nvoCRTempSet_ac 17 0 0 0 0 1 63 1 0 1 0 1 0 1 0 0 0 "@2#25 39 * 1 2 0 0 0 0 VAR nvoCRHumiSet 18 0 0 0 265069 HILON 2G User Manual...
  • Page 73 0 1 63 1 0 1 0 1 0 1 0 0 0 "@2#40 8 * 1 2 0 0 0 0 VAR nvoCRManHumi 33 0 0 0 0 1 63 1 0 1 0 1 0 1 0 0 0 "@2#41 265069 HILON 2G User Manual...
  • Page 74 39 * 1 2 0 0 0 0 VAR nvoCRFanSpeHeHu 48 0 0 0 0 1 63 1 0 1 0 1 0 1 0 0 0 "@2#56 8 * 1 2 0 0 0 0 265069 HILON 2G User Manual...
  • Page 75 0 1 63 0 0 1 0 1 0 1 0 0 0 "@2#11 81 * 1 2 0 0 1 0 VAR nviCRHiTempE 64 0 0 0 0 1 63 0 0 1 0 1 0 1 0 0 0 265069 HILON 2G User Manual...
  • Page 76 \x78 \x00 \x00 \x00 \x00 \x00 \x00 \x00 \x00 \x00 \x00 \x00 \x00 \x00 \x00 \x00 \x00 \x00 \x00 \x00 \x00 \x00 \x00 \x00 \x0A \x00 \x32 \x00 \x05 \x00 \x00 \x03 \x14 FILE readOnly 2 1 \x01 \x00 \x00 \x15 265069 HILON 2G User Manual...
  • Page 77 XIF configuration File. provided into Vertiv Connectivity CD: H2G_HPF_3_1.XIF File: H2G_DevTempl.XIF generated by LONNCC32 Version 5.01.07, XIF Version 4.402 Copyright (c) Echelon Corporation 1989-2010 All Rights Reserved. Run on Wed Apr 27 13:44:55 2016 90:00:E7:46:00:04:04:00 2 10 0 73 0 3 3 3 3 3 3 11 9 2 4 7 0 16 30 1 1 128 73 0 0 0 0 0 0 0 0 0 2 10 0 0 0 0 0 2 49 0 0...
  • Page 78 3 5 1 0 0 3 6 1 0 0 3 7 1 0 0 3 0 1 0 0 3 1 1 0 0 3 2 1 0 0 3 3 1 0 0 265069 HILON 2G User Manual...
  • Page 79 3 6 1 0 0 3 7 1 0 0 3 0 1 0 0 3 1 1 0 0 3 2 1 0 0 3 3 1 0 0 3 4 1 0 0 265069 HILON 2G User Manual...
  • Page 80 3 7 1 0 0 3 0 1 0 0 3 1 1 0 0 3 2 1 0 0 3 3 1 0 0 3 4 1 0 0 3 5 1 0 0 265069 HILON 2G User Manual...
  • Page 81 2 0 0 0 0 VAR nvoEVEEAPHumi 17 0 0 0 0 1 63 1 0 1 0 1 0 1 0 0 0 "@2#25 81 * 1 2 0 0 1 0 VAR nvoEVFC_Cond 18 0 0 0 265069 HILON 2G User Manual...
  • Page 82 0 1 63 1 0 1 0 1 0 1 0 0 0 "@2#40 81 * 1 2 0 0 1 0 VAR nvoEVTempIntg 33 0 0 0 0 1 63 1 0 1 0 1 0 1 0 0 0 "@2#41 265069 HILON 2G User Manual...
  • Page 83 81 * 1 2 0 0 1 0 VAR nvoEVLoHumiE 48 0 0 0 0 1 63 1 0 1 0 1 0 1 0 0 0 "@2#56 81 * 1 2 0 0 1 0 265069 HILON 2G User Manual...
  • Page 84 0 1 63 0 0 1 0 1 0 1 0 0 0 "@2#8 39 * 1 2 0 0 0 0 VAR nviEVHiHumi 64 0 0 0 0 1 63 0 0 1 0 1 0 1 0 0 0 265069 HILON 2G User Manual...
  • Page 85 \x78 \x00 \x00 \x00 \x00 \x00 \x00 \x00 \x00 \x00 \x00 \x00 \x00 \x00 \x00 \x00 \x00 \x00 \x00 \x00 \x00 \x00 \x00 \x00 \x0A \x00 \x32 \x00 \x05 \x00 \x00 \x03 \x14 FILE readOnly 2 1 \x01 \x00 \x00 \x14 265069 HILON 2G User Manual...
  • Page 86 XIF configuration File. provided into Vertiv Connectivity CD: H2G_HPC_3_0.XIF File: H2G_DevTempl.XIF generated by LONNCC32 Version 5.01.07, XIF Version 4.402 Copyright (c) Echelon Corporation 1989-2010 All Rights Reserved. Run on Thu Mar 10 09:37:54 2016 90:00:E7:46:00:04:04:05 2 10 0 73 0 3 3 3 3 3 3 11 9 2 4 7 0 16 30 1 1 128 73 0 0 0 0 0 0 0 0 0 2 10 0 0 0 0 0 2 49 0 0...
  • Page 87 3 5 1 0 0 3 6 1 0 0 3 7 1 0 0 3 0 1 0 0 3 1 1 0 0 3 2 1 0 0 3 3 1 0 0 265069 HILON 2G User Manual...
  • Page 88 3 6 1 0 0 3 7 1 0 0 3 0 1 0 0 3 1 1 0 0 3 2 1 0 0 3 3 1 0 0 3 4 1 0 0 265069 HILON 2G User Manual...
  • Page 89 3 7 1 0 0 3 0 1 0 0 3 1 1 0 0 3 2 1 0 0 3 3 1 0 0 3 4 1 0 0 3 5 1 0 0 265069 HILON 2G User Manual...
  • Page 90 2 0 0 0 0 VAR nvoSCHWTempOuWa 17 0 0 0 0 1 63 1 0 1 0 1 0 1 0 0 0 "@2#25 39 * 1 2 0 0 0 0 VAR nvoSCHWTempInAl 18 0 0 0 265069 HILON 2G User Manual...
  • Page 91 0 1 63 1 0 1 0 1 0 1 0 0 0 "@2#40 8 * 1 2 0 0 0 0 VAR nvoSCHourComp2 33 0 0 0 0 1 63 1 0 1 0 1 0 1 0 0 0 "@2#41 265069 HILON 2G User Manual...
  • Page 92 8 * 1 2 0 0 0 0 VAR nvoSCManPump2 48 0 0 0 0 1 63 1 0 1 0 1 0 1 0 0 0 "@2#56 8 * 1 2 0 0 0 0 265069 HILON 2G User Manual...
  • Page 93 0 1 63 0 0 1 0 1 0 1 0 0 0 "@2#7 39 * 1 2 0 0 0 0 VAR nviSCLWTempInWa 64 0 0 0 0 1 63 0 0 1 0 1 0 1 0 0 0 265069 HILON 2G User Manual...
  • Page 94 \x78 \x00 \x00 \x00 \x00 \x00 \x00 \x00 \x00 \x00 \x00 \x00 \x00 \x00 \x00 \x00 \x00 \x00 \x00 \x00 \x00 \x00 \x00 \x00 \x0A \x00 \x32 \x00 \x05 \x00 \x00 \x03 \x14 FILE readOnly 2 1 \x01 \x00 \x00 \x14 265069 HILON 2G User Manual...