Advertisement
The manual describes a series of AC air conditioners' instructions, wiring, operating instructions.
The manual is mainly used to guide users to install and maintain the series of air conditioners.
For the series of products of any operation must be made by the professional technicists according to the requirements of the manual.
This series of products are designed for communication or related industrial equipment applications of high-performance ac type air conditioning unit, cabinet internal devices suitable for heat, temperature sensitive, and inside and outside completely isolated applications.
Grid application scope: AC 220VAC±15% 50Hz/60Hz
(Optional other power grid: 220VAC±30%,please contact us.)
Other power supply system, please refer to the nameplate.
Warning: In the process of transportation, storage and use must be in strict accordance with the instructions on the package to keep air conditioning placed vertically upward.
For example:
TA 0** / M / E / A / H**
T:Outdoor enclosure cooling of Quick;
A: Standard air conditioner;
0**: Cooling Capacity is **×100W(L35/L35);
M: Series: M series;
E: E--Semi-embedded Mounting;
A: Power: 230VAC 50/60Hz;
H**: Heating Capacity is **×100W(L35/L35)
Remarks:
There installations of M series: E-- Semi-embedded Mounting, D-- Door Mounting, and S-- Side Mounting;
Only one installation L and N series have.
Standard | Description |
GB/T 17626.7-1998 | Electromagnetic compatibility(EMC) |
GB4706.1 | Safety household and similar electrical appliance |
GB4798.1 | Environmental conditions existing in the application of electric and electronic products - storage |
GB4798.2 | Environmental conditions existing in the application of electric and electronic products - transport |
GB4798.3 | Environmental conditions existing in the application of electric and electronic products - use |
CE | The third party certification |
Air conditioner packed in paper cases, the package includes Annex.
The air conditioner during the transportation, please pay attention to the following matters:
Figure 2-1 Packing mark
You have to prepare the following tools before installation: cross screwdriver, slot type screwdriver, sealing strip, vice.
Air Conditioner-N&L Series' schematic of installation as follow:
Air Conditioner-M Series' schematic of installation as follow:
Attention:
Installation steps:
Double check lists after Installation:
Does Electrical Wiring according to the manual before use the air conditioner; we suggested preferring to use cables in the attachments. You should call the After-sale Service Department of QUICK, if you cannot sure the cable specification be made by your-self.
Figure 3-1 Schematic of power terminal
Table 3-1 Terminal instructions
No. | Symbol | Definition |
1: | L | Live line of AC power |
2: | N | Neutral line of AC power |
3: | PE | Ground wire of AC power |
4: | T/R+ | Positive pole of 485 communication |
5: | T/R- | Negative pole of 485 communication |
6: | NO | Normal open port of dry contract alarm output |
7: | COM | Common port of dry contract alarm output |
8: | NC | Normal closed port of dry contract alarm output |
9、10: | I/O | Hydrogen discharging port or external signal input port |
Completed and confirmed the wiring correct, then you can connect to the AC power to air conditioner for the first time to run on electricity.
After power on air conditioner, first of all it will be self-checking: internal fan, temperature sensor, heater, external fan, and compressor.
When the air conditioner is running, if there is abnormal noise, vibration, please cut off power immediately and notify the professionals to inspect.
Operational mode: standby, cooling, heating, and alarming.
The display panel shows cabinet temperature under normal circumstance, and shows alarm code when there is a malfunction.
In the bottom is the status bar, different lamp represents different status.
You can check and set various parameters of air conditioner by the display panel (User Parameters).
Figure 4-1 the display panel diagram
Table 4-1 the meanings of lamps on the display panel
lamps | Description |
![]() | Flashing when self diagnose or temperature setting mode |
![]() | Lamp on when cooling |
![]() | Lamp on when heating |
![]() | Lamp on when external fan is running |
![]() | Flashing when alarm |
Table 4-2 Setting Code
Code | Parameter name | Default Value | Range | Remarks |
F01 | Compressor start temperature | 35 | 20~50℃ | |
F02 | Compressor stop hysteresis temperature | 5 | 2~8℃ | |
F03 | Heater start temperature | 0/5 | -5~10℃ | This function is only applicable to the models with heater. |
F04 | Heater stop hysteresis temperature | 5/10 | 1~5℃ | |
F05 | High temperature alarm | 55 | 35~70℃ | |
F06 | Low temperature alarm | -40 | -42~15℃ | |
F07 | Communication address | 1 | 1~255 |
The monitor displays return air temperature at normal, If the alarms, temperature and alarm codes are displayed alternately, the alarm code as follows:
Table 4-3 Alarm Code
Code | Code Name | Principle | Process Method |
E01 | Return air temperature sensor fault | Return air temperature sensor is short circuit or open circuit |
|
E02 | Evaporator temperature sensor alarm | Evaporator temperature sensor is short circuit or open circuit | Check whether the evaporator temperature sensor is short circuit or open circuit. |
E03 | Condenser temperature sensor alarm | Condenser temperature sensor is short circuit or open circuit | Check whether the condenser temperature sensor is short circuit or open circuit. |
E04 | Internal fan alarm |
|
|
E05 | External fan alarm |
|
|
E06 | Refrigerant leakage alarm |
|
|
E07 | Low temperature alarm | The cabinet temperature is higher than the set point | The heater is running until the alarm elimination. |
E08 | High temperature alarm | The cabinet temperature is higher than the set point. | Open the cabinet door until the alarm stop. |
Fault state | Analysis of the reasons | Solutions |
Power on the switch, the cabinet temperature is too high but the air conditioner is not working. |
|
|
The air conditioner is running but the cooling effect is not good. |
|
|
The machine is stopping suddenly, and the electric system is normal. |
|
|
Prepare tools
(Table 5 -1 Malignance Tools)
No. | Tools |
1 | Multimeter |
2 | Phillips screwdriver |
3 | Slotted screwdriver |
Routine maintenance
(Table 5 -2 Routine maintenance)
No. | Check items | Check methods | Solution |
1 | Power line firm |
| If there is a power line to loose or loosening, You should be used to tie tight power line; use a screwdriver to loose screw. |
2 | Voltage Stability | Use the multimeter to measure air conditioner input voltage to watch whether the voltage is within normal range. | If the voltage is not within the normal range, Please turn off the power supply immediately. Power on the air conditioner until the supply voltage within normal range. |
3 | Screw firmly | Use screwdriver to screw the screws and watch whether the screw is loosening | If the screw is loosening, please tighten it. |
Here you can download full pdf version of manual, it may contain additional safety instructions, warranty information, FCC rules, etc.
Advertisement
Need help?
Do you have a question about the AC Series and is the answer not in the manual?
Questions and answers