LO-1600W Water Chiller Operation Manual
1) Ensure good contacts on the AC power pug: L, N, and G
2) Stable AC voltage is necessary. +/-5%
3) Stable AC frequency (Hz) is required. No square wave or modified sinusoid wave accepted
4) Do not operate without water or the water pump will suffer damage.
5) Remove any obstacle that is blocking the intake or the outlet from the fan
6) Air filter need to be cleaned periodically.
7) Change water every 2 weeks. Distilled water is highly recommended.
8) Operate the unit by trained and skill personnel only.
Introduction
The LO-1600W is an industrial grade water chiller with a high efficiency compressor running on R410A
environmental friendly Freon. The chiller is controlled by the sophisticated microcontroller with a large easy LCD
readout. Two control modes Intelligence or Constant provides an accurate and fast control to the change of
temperature.
Control modes
Intelligence – The target temperature changed accordingly upon the change from the ambient temperature. The
amount of temperature change (drop) is controlled the 'deviation' value.
Constant – The target temperature is fixed at set by the "SV" parameter. Regardless of how an ambient
temperature changes, the chiller will always reach the target temperature with a plus or minus variation of the
'Feedback' value
Caution and Conditions

Advertisement

loading
Need help?

Need help?

Do you have a question about the LO-1600W and is the answer not in the manual?

Questions and answers

Summary of Contents for LIGHT OBJECT LO-1600W

  • Page 1 8) Operate the unit by trained and skill personnel only. Introduction The LO-1600W is an industrial grade water chiller with a high efficiency compressor running on R410A environmental friendly Freon. The chiller is controlled by the sophisticated microcontroller with a large easy LCD readout.
  • Page 2 LCD Display and control aand Power indicator Air filter grid Water flow alarm Water Inlet Water filling Water Outlet Alarm output AC power plug Water level Cooling Fan Water drain out...
  • Page 3 Startup procedures 1) Open the cap from the top of the unit and fill with water until the water level reaches the green zone. 2) Connect a water tubing from the intake of the chiller to the machine outlet. Connect another water tubing from the Outlet of the chiller to the machine intake.
  • Page 4 Deviation: This is the range of fluctuation allowed for the Intelligence mode only Feedback: This is the range of fluctuation allowed for the Constant mode only Max Temp: This is the max water temperature (over heated) before the alarm is set off Language: Either English or Chinese can be set for the default language.
  • Page 5 Intelligence mode: By default, Constant mode is selected. Cooling on power: If ‘Yes’, the chiller will start to run once power is on. If you want to manually turn on the cooling, select ‘No’ System Reset: Reset all parameters to the manufacturer default value. Or, reflect the change once system OS is updated.
  • Page 6 WC-LO1650WSH2V WC-LO1650WSH1V Model Voltage: AC220V +/- 5% AC110V +/- 5% 60Hz 60Hz Frequency: 3.3A 6.5A Amp: Compressor power: 0.5KW (0.68HP) 0.68KW (0.93HP) Cooling power: 1.65kW 1.750kW Freon type: R-410A R-410A 380g 350g Water pump power: 0.1kW 0.1kW Flow rate: 13L/min or 95GPH 13L/min or 95GPH Cut off range: 10m (33ft)