1 DESCRIPTION AND OPERATION
1.1
Purpose
1.1.1 S2000-KPB Executive Unit (hereinafter referred to as the unit) is intended for:
– Operating control appliances (light and sound fire alarm indicating appliances etc.) and
automatic fire-fighting equipment in notification and smoke removal systems;
– Operating fire extinguishing modules and automatic fire-fighting equipment in water
extinguishing systems, foam extinguishing systems, clean agent extinguishing systems, dry
chemical powder extinguishing systems, and aerosol fire extinguishing systems;
– Generating signals to control engineering equipment, process signaling equipment, and other
devices involved in fire safety providing;
– Operating other appliances (light and sound alarms, video cameras, electromagnetic locks and
so on) in intrusion alarm systems, panic alarm systems, auxiliary alarm systems, and access
control systems;
– Monitoring two process signaling inputs.
It is used as a component of modular control and indicating equipment under S2000M Monitoring and
Control Panel or Sirius Fire Alarm Control Panel and their revisions.
1.1.2 The unit is intended for round-the-clock operation.
1.1.3 The unit is classed as a restorable and regularly maintainable item.
1.1.4 The design of the unit doesn't provide its operation in aggressive and / or dusty environments as
well as in explosion hazardous and flammable premises.
1.2
Specifications
1.2.1 Power inputs
1.2.2 Power input voltage, V dc
1.2.3 Consumed current, mA, max
1.2.4 Start-up time, s
1.2.5 Outputs
1.2.6 Commuting voltage, V (from the unit power supply)
1.2.7 Output switched current, A
1.2.8 Circuit fault monitoring current, mA, max
1.2.9 Maximum total unit switched current, A, max
1.2.10 Inputs
1.2.11 Resistance of initiating device circuit wires without regard to
termination resistor), Ohm, max
1.2.12 Resistance of leakage between initiating device circuit wires or
between each wire and the earth, kOhm, at least
1.2.13 Enclosure protection degree as per GOST 14254-2015
1.2.14 Resistance to mechanical exposure as per OST 25 1099-83
S2000-KPB EXECUTIVE UNIT
OPERATIONS MANUAL
Parameter
Table 1.2.1
Value
2
10.2 through 28.4
100
3
6
10.2 ÷ 28.4
0.005 ÷ 2.5
1.5
6
2
100
50
IP40
Arrangement Category III
1
Need help?
Do you have a question about the S2000-KPB and is the answer not in the manual?
Questions and answers