5. Disconnect the auxiliary power supply. 6. Replace the protective cap onto the auxiliary power connector. FIELD CONFIGURATION SOFTWARE Currently the sensor configuration will be performed by the GE grid solutions service team. USING THE CAPMD SENSOR The target capacitor impedance and the warning/failure thresholds will be set at the factory or by the field service team.
CAPACITOR UNIT FIELD MEASUREMENT To measure capacitor unit capacitance, use a GE’s NCM-20 capacitance meter or equivalent. Disconnect the leads, remove the sensor (needed?) and test capacitance between terminal A and B as per instructions of the capacitance meter manual/manufacturer.
If sensor is not responding, please contact us with serial#. The sensor can be replaced by a spare one while the investigation is performed. 10 SUPPORT CONTACTS Factory address: GE ITI - 1925 Calumet St, Clearwater, FL 33765 Factory contacts - Sales: capmd-sales@ge.com Factory contacts - Service: capmd-sales@ge.com...