Warnings!
Watch out for the scratches that may be caused by the cabinet, chassis or rails.
Be aware of electric shock when installing the servers into the cabinet in use.
•
Do not block the vents on the server during installation.
Remove the protective film from the chassis before installing servers into the rack.
•
•
Leave a minimum clearance of 150 mm (5.9 in.) for the front and rear ends of the
server to ensure proper ventilation.
•
Always install blanks if the bays have not been loaded with any equipment to ensure
proper air flow and avoid air turbulence in the server room.
Servers can only be deployed in dedicated cabinets with vents or specialized liquid
•
cooling cabinets to avoid server failure from overheating as they are high power
appliances.
•
In case of multiple-equipment deployment, always load from bottom to top and
place the heaviest equipment in the bottom bay.
•
Do not install equipment beyond the cabinet's load-bearing capacity, power supply
capacity and heat dissipation capacity.
For easy access of the front and rear ports and cable routing, leave a minimum
•
clearance of 70 mm (2.8 in.) between the server front end and the cabinet front
door, and a minimum clearance of 150 mm (5.9 in.) between the server rear end
and the cabinet rear door.
For equipment _ 15 kg (33.07 lbs), use at least 2 people.
For equipment _ 30 kg (66.14 lbs), use at least 3 people.
For equipment _ 50 kg (110.23 lbs), use at least 4 people.
Please keep this document for future reference.