Warnings!
Watch out for the scratches that may be caused by the cabinet, chassis or rails.
Be aware of electric shock when installing the servers into the cabinet in use.
For servers of 2U or larger form factor, use at least 2 people.
•
Do not block the vents on the server during installation.
•
Remove the protective film from the chassis before installing servers into the rack.
•
Leave a minimum clearance of 150 mm (5.9 in.) for the front and rear ends of the server to
•
ensure proper ventilation.
•
Always install blanks if the bays have not been loaded with any equipment to ensure proper
air flow and avoid air turbulence in the server room.
•
Servers can only be deployed in dedicated cabinets with vents or specialized liquid cooling
cabinets to avoid server failure from overheating as they are high power appliances.
Always load equipment into a cabinet from the bottom up and place the heaviest equipment
•
in the bottom bay.
Do not install equipment beyond the cabinet capacities of load bearing, power supply and
•
heat dissipation.
For easy access to the front and rear ports and cable routing, leave a minimum clearance of
•
70mm (2.8 in.) between the server front end and the cabinet front door, and a minimum
clearance of 150 mm (5.9 in.) between the server rear end and the cabinet rear door.
For equipment ≥ 15 kg (33.07 lbs), use at least 2 people.
For equipment ≥ 30 kg (66.14 lbs), use at least 3 people.
For equipment ≥ 50 kg (110.23 lbs), use at least 4 people.
Please keep this document for future reference.