RELAY OUTPUT MODULE OCM-AS3
INTRODUCTION
DESCRIPTION
The OCM-AS3 forms part of the Nittan (UK)'s
SENSORTEC-ANALOGUE range of Analogue
Addressable Devices.
This module is designed to perform a loop powered,
control relay output function from the detection signal-
ling loop of an analogue-addressable fire detection
system.
The OCM-AS3 may be used for a variety of purposes
such as closing fire doors, shutting down plant machin-
ery and operating smoke extraction systems via this
loop powered device.
OPERATION
The fire alarm control equipment must be capable of
communicating with the OCM-AS3 relay output control
module. If in doubt, check with panel manufacturer.
The OCM-AS3 is a loop powered, two-wire signalling de-
vice, it is connected onto the detection signalling loop's
SIG+ and -S wires, exactly as any other 'AS' sensor or
device.
FEATURES
* A relay control output for the switching of external
equipment such as fire doors etc..
* Loop powered, no PSU requirements
OCM-AS3 Relay Output Contol Module
is made up as follows:-
1 x Metal enclosure c/w 20mm knockouts
1 x OCM-AS3 PCB c/w internal plastic PCB enclosure
with hinged lid.
1 x Earth point (on lid)
1 x Earth point (inside of enclosure)
1 x 200mm Earth Strap
1 x Label inside lid for product identification and
device address identification.
www.acornfiresecurity.com
OCM-AS3 LOOP POWERED
RELAY OUTPUT CONTROL MODULE
INSTALLATION & TECHNICAL
MANUAL
www.acornfiresecurity.com
SENSORTEC-ANALOGUE FAMILY:-
SENSORS:-
ST-I-AS - Analogue Ionisation Smoke Sensor
ST-P-AS - Analogue Photoelectric Smoke Sensor
ST-H-AS - Analogue Heat Sensor
STB-4 - Standard Base for above sensors
DEVICES:-
ST-NCP-AS - Addressable Call Point
BACK BOX - Back Box for ST-NCP-AS
MCM-AS4 - Zone Monitor/Control Unit
SCM-AS4- Addressable Sounder Control Module
NAM-AS3 - Addressable Input Module
OCM-AS3 - Relay Output Control Module
SCI-5 - Base mounted Short Circuit Isolator
SCI-6 - Plate mounted Short Circuit Isolator
1-Gang Box - Single gang box for SCI-6
ADDRESSABLE SOUNDERS:-
VCT-03-AS-NB - Addressable Wall Sounder
c/w Vector Plate/Cap (R = Red, W = White Plate/Cap).
VCT-03-CP(W) - Spare Vector Plate/Cap (White)
VCT-03-CP(R) - Spare Vector Plate/Cap (Red)
VCT-03-NT-AS - Addressable Sounder c/w STB-4 Base
pre-wired to the sounder.
VPR-SA2-NTAS - Addressable Sounder, IP65 rated,
wall mounted.
No:
NISM/OCMAS3/01
DATE:
JANUARY 2002
PAGE:
ISSUE:
01
1
of 9