Nittan EVA-ZMU-SCI Instruction Manual

Nittan EVA-ZMU-SCI Instruction Manual

Zone module

Advertisement

Quick Links

Instruction Manual
EVA-ZMU-SCI Zone Module

Before Installation

Please read these instructions carefully and keep for future reference.
The information in this document is subject to change without notice.
For updates please refer to our website.
Do not use the products outside the rated power supply voltage range
specified in the Specifications. It may cause a fire or damage to
equipment.
Do not disassemble, repair, or modify the products. It may cause a fire or
electric shock.
Make sure to turn the power off before commencing any wiring work.
Otherwise it may cause electric shock or damage to equipment.
Note : Follow the requirements for the installation of the product in
accordance with the Specifications. Otherwise it may cause malfunction.
Note : Do not install the product in any location where oil, dust, iron
powder, chemicals, or hydrogen sulphide may occur or affect the product.
It may cause malfunction.
This package contains the following items:
Main unit
........................................................................ 1
Outer cover EVA..................................................................1
Instruction Manual
............................................................1
Tapping screw
.................................................................. 2
Pan head screw
..................................................................2
EOL Resistor(RE-10k)...............................................................1

General Description

EVA-ZMU-SCI Zone Module with Short Circuit Isolator is intended for
use in addressable two wire systems, which can be connected with
2-wire conventional detectors. The module monitors and transmits the
status (normal, open, short, or alarm) of zone with the detectors to a
control panel. The initiating device circuit (IDC) can be wired on Class A
or Class B.

General Operation

Normal standby condition: The module receives polling from the control
panel at the regular interval. Polling LED (green) flashes.
Alarm condition: When an external input is activated, Input LED (red)
CAUTION
!
CAUTION
!
CAUTION
!
1-54-5 SASAZUKA, SHIBUYA-KU, TOKYO 151-8535, JAPAN
illuminates, and the module communicates to the control panel the
alarm status.
Trouble condition: If an overcurrent occurs because SLC (Signaling Line
Circuit) is shorted, SCI LED (yellow) illuminates, and the module
communicates to the control panel the short status. The module also
communicates to the control panel the open/short status of IDC,
depending on the Subtype Setting described below.
SCI (Short Circuit Isolator) Function
The module has a built-in short circuit isolator. SCI circuit prevents
entire loop failure in the event of a short between L+ and L- on the loop.
If a short is detected between L+ and L-, the yellow LED indicator is
illuminated. The line between Lin- and Lout- is disconnected
automatically to isolate the short circuit, and short circuit status is
communicated to the control panel. Upon removal of the short condition,
the module will automatically connect between Lin- and Lout- to restore
the entire loop to the normal operating status.
1
NITTAN COMPANY, LIMITED
http://www.nittan.com
Figure 1
Figure 2
DW1401990 Rev.K2
Dec 18, 2019

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the EVA-ZMU-SCI and is the answer not in the manual?

Questions and answers

Summary of Contents for Nittan EVA-ZMU-SCI

  • Page 1 EOL Resistor(RE-10k)………………………………………………………1 Figure 1 General Description EVA-ZMU-SCI Zone Module with Short Circuit Isolator is intended for use in addressable two wire systems, which can be connected with 2-wire conventional detectors. The module monitors and transmits the status (normal, open, short, or alarm) of zone with the detectors to a control panel.
  • Page 2 Electrical box 10th edition. Main unit Please contact Nittan customer service for any required details. Pan head screw Tapping screw Compatible Two wire detector for use with EVA-ZMU-SCI with Zone Outer cover EVA Identifier A: Figure 3 Detector Compatibility Detector...
  • Page 3 Class A (Short circuit detection is available) CAUTION Use cable AWG12-22 for wiring. Do not connect different gauge cables Detectors are connected between A+ (B+) and A- (B-) in EVA-ZMU-SCI. at one terminal in order to prevent loosening. Use a fork terminal for crimping two cables.
  • Page 4 Standby 2.6mA marks on or in relation to the products, unlawful. Alarm 35.9mA (max) 1.2 In the event of any breach of the Nittan's warranty in Clause 1.1(a) SLC Line Impedance Up to 50 ohms whether by reason of defective materials, production faults or...