Page 1
ID-E359-001-GB AUTOMATIC FIRE EXTINGUISHING CONTROL PANEL IGNIS 2500 _________________________________________________________________________________ OPERATION & MAINTENANCE MANUAL ID-E359-001-GB Edition I IGNIS 2500 AUTOMATIC FIRE EXTINGUISHING CONTROL PANEL...
Page 2
ID-E359-001-GB The IGNIS 2500 fire extinguishing control panel, which is the subject of this OMM, meets the essential requirements of the European Parliament as well as the EU Council and European Union directives as the following regulations: CPR/305/2011 European Parliament and the EU Council Regulation of March 9, 2011 establishing harmonized conditions for marketing of the construction products and repealing Council Directive 89/106/EEC;...
Housing of a single-zone control panel ................. 17 3.4. Housing of a two-zone control panel ..................18 3.5. The arrangement of modules in the exemplary versions of the IGNIS 2500 control panels 19 3.6. User interface ........................21 3.7. General principles of menu navigation ................. 25 Technical data ........................
Page 4
Connection terminals for input and output circuits, hard-wired installation ....... 94 11. Operation of the control panel in the event of a system failure........... 95 12. Instructions for commissioning and checking the correct operation of the control panel after installation ..........................96 IGNIS 2500 AUTOMATIC FIRE EXTINGUISHING CONTROL PANEL...
Page 5
Fulfils Strength Research Fulfils Optional functions Extinguishing signal delay Fulfils 4.17 Signal indicating the effect of the extinguishing agent Fulfils 4.18 Monitoring condition of the components Fulfils 4.19 Emergency stop device Fulfils 4.20 IGNIS 2500 AUTOMATIC FIRE EXTINGUISHING CONTROL PANEL...
Page 6
Testing status Fulfils Structural requirements Fulfils Additional structural requirements Fulfils concerning software-controlled panels Marking Fulfils Durability of operational reliability: resistance to heat Cold resistance Fulfils 15.4 Durability of operational reliability: resistance to vibration IGNIS 2500 AUTOMATIC FIRE EXTINGUISHING CONTROL PANEL...
Page 7
Essential characteristics of the product PN-EN 54-4:2001+ properties A1:2002+A2:2007 chapter Power supply efficiency General requirements Fulfils Functionality Fulfils Materials, structure and workmanship Fulfils Operational reliability General requirements Fulfils Functionality Fulfils Materials, structure and workmanship Fulfils IGNIS 2500 AUTOMATIC FIRE EXTINGUISHING CONTROL PANEL...
Page 8
Moist solid heat (resistance) Fulfils Moist solid heat (strength)) Fulfils 9.14 Intended use: Panels for use in gas extinguishing devices installed in buildings, forming a complete and operating installation. For technical data, see documentation: ID-E359-001-GB IGNIS 2500 AUTOMATIC FIRE EXTINGUISHING CONTROL PANEL...
1.2. Intended use of the control panel The IGNIS 2500 automatic extinguishing control panel is a device designed for use in fixed fire-fighting systems and for the following tasks: - activating fixed fire extinguishing devices based on the signal received from an automatic detectors or from manual "start extinguishing"...
Maintenance work and periodic inspections must be carried out by an authorized personnel of companies authorized or trained by the POLON-ALFA. All repairs must be made by the manufacturer. POLON-ALFA shall not be liable for the operation of equipment maintained and repaired by unauthorized personnel. 1.4. Terms Detection status - operating mode in which the control panel is powered from an electric power source meeting the specified requirements and in which no other operating status is signalled;...
Page 11
Fire extinguishing device - a set of tanks with the extinguishing agent, pipelines and nozzles arranged so as to distribute the extinguishing agent in the protected space in a way that allows to obtain the extinguishing concentration; Manual actuation – actuation, requiring human intervention. IGNIS 2500 AUTOMATIC FIRE EXTINGUISHING CONTROL PANEL...
Operation and Maintenance Manual (OMM) ID-E359-001 User Manual IO-E359-003 Warranty book Unit package of the control panel *) OMM in a set with the control panel or downloadable from the www.polon-alfa.pl website as a file. Table 2/2 Accessories for self-ordering Housing component Element type...
"MSS-25 extended module"; mounting the second MSG-25 module. All versions with the MGR-64 bus allow for the installation of optional modules. IGNIS 2500 AUTOMATIC FIRE EXTINGUISHING CONTROL PANEL...
Versions 10*, 11, 12, 13 - MSG-25 modules mounted in a package one above the other. Free space allows the control panel to be expanded with any optional modules such as MPK-60, MWS-60, MKS- 60 up to 2 pcs. IGNIS 2500 AUTOMATIC FIRE EXTINGUISHING CONTROL PANEL...
- Compatibility with 30 and 40 series conventional detectors manufactured by POLON-ALFA, - Cooperation with addressable systems, - Operation of up to 20 IGNIS 2500 panels on a POLON 6000 system detection line, - Up to 6 conventional detection lines in one extinguishing zone,...
ID-E359-001-GB 3.2. Cooperation with fire alarm systems The IGNIS 2500 has universal potential-free relay outputs, allowing to transmit basic status signals to most fire systems or monitoring stations. It also has an optional possibility of cooperation with the POLON 6000 addressable system after applying the MKA-25 module.
ID-E359-001-GB The signals transmitted by the addressable detection line between the IGNIS 2500 panel and the PO- LON 6000 system are described in section 8.4 "Communication Module via Addressable Line MKA-25" 3.3. Housing of a single-zone control panel Figure 3.3/1 Dimensions of a single-zone control panel...
ID-E359-001-GB 3.4. Housing of a two-zone control panel Figure 3.4/1 Dimensions of a two-zone control panel IGNIS 2500 AUTOMATIC FIRE EXTINGUISHING CONTROL PANEL...
MSO-25 MZU-25 MKA-25 Figure 3.5/2. An example of a single-zone control panel with the MKA module allowing connection to the POLON 6000 system addressable detection line (version 2 according to table 2.1.1 /1) IGNIS 2500 AUTOMATIC FIRE EXTINGUISHING CONTROL PANEL...
Page 20
MZU-25 - universal power supply module MKA-25 - addressable communication module (enables connection with the addressable line of the POLON 6000 system) MGR-64 - bus module (enables installation of additional two optional modules) IGNIS 2500 AUTOMATIC FIRE EXTINGUISHING CONTROL PANEL...
Figure 3.5/4. An example of a two-zone control panel with two MSG-25 modules arranged next to each other (version 8* according to Table 2.2.1/1) 3.6. User interface Figure 3.6/1 User interface of a single-zone control panel IGNIS 2500 AUTOMATIC FIRE EXTINGUISHING CONTROL PANEL...
Page 22
Disabling all alarm signalling devices (outputs ALARM DEVICES assigned to the alarm signalling group) /yellow Intermittent Partial deactivation - in case of more than one output assigned to a group of alarm devices (at IGNIS 2500 AUTOMATIC FIRE EXTINGUISHING CONTROL PANEL...
Page 23
Display of control panel status messages and configuration settings ← ↑ ↓ → DIREC- Designed to operate the control panel menu as TION BUTTONS described in section 5 "Display functions and menu operation" Enter IGNIS 2500 AUTOMATIC FIRE EXTINGUISHING CONTROL PANEL...
Page 24
During signalling, the countdown of the extinguishing agent release delay time is stopped. ADDITION START Continuous Signalling that the discharge of additional /red extinguishing agent is activated IGNIS 2500 AUTOMATIC FIRE EXTINGUISHING CONTROL PANEL...
Move the cursor to the right or enter a sub-menu Exit from the sub-menu - entering a higher level Entering a sub-menu, moving to the next window or field and confirming changes made in functional or configuration settings. IGNIS 2500 AUTOMATIC FIRE EXTINGUISHING CONTROL PANEL...
Max. number of buttons EXTINGUISHING START, EXTINGUISHING STOP, EXTINGUISHING BLOCK 6.2 kΩ Terminating resistor 2 x 100 Ω Line resistance max. Supervised potential outputs Number of outputs max.* Current of outputs L7, L8 max. IGNIS 2500 AUTOMATIC FIRE EXTINGUISHING CONTROL PANEL...
Page 27
Communication module with supervisory line of POLON 3000 and POLON 6000 systems Number of modules Power consumption 20 mA Cooperation with devices Interface for connection with Control panel configuration a computer Readout of events IGNIS 2500 AUTOMATIC FIRE EXTINGUISHING CONTROL PANEL...
LCD display.In order to enter or change the level 3 (P3) or 4 (P4) access code, select the "ACCESS LEVEL" line in the main menu and proceed according to table 4.1/1. IGNIS 2500 AUTOMATIC FIRE EXTINGUISHING CONTROL PANEL...
Page 29
Enter the 4 digits of the access code by di- alling the displayed digits on the screen. - deleting the entered digits. Enter the following digits and confirm the code with the button IGNIS 2500 AUTOMATIC FIRE EXTINGUISHING CONTROL PANEL...
3rd access level, using the information displayed on the LCD display or using a PC, with the "IGNIS 2500 configurator" program installed and connection of the USB port with a typical cable with connectors: type A (computer) and type B (control panel - MSO-25 module).
Page 31
window for programming the coincidences of detection LINE COINCIDENCES lines LCD contrast settings, clock correction, language selection SYSTEM SETTINGS window PROGR./CONFIG.VERSIONS window for reading the program version and configuration settings IGNIS 2500 AUTOMATIC FIRE EXTINGUISHING CONTROL PANEL...
The number "2" should be set on the SW 1 switch located on the PCB of the added module. The modules must have different ad- dresses. Return to the main menu. IGNIS 2500 AUTOMATIC FIRE EXTINGUISHING CONTROL PANEL...
4.2.2. Removing modules Table 4.2.2/1 Removing modules Use of but- Screen Description of activities tons Select the MODULES +/- line. Go to the next window. Select a module from the displayed list. IGNIS 2500 AUTOMATIC FIRE EXTINGUISHING CONTROL PANEL...
Page 34
In case of any changes made to the control panel configuration, a win- dow appears which allows to save or discard them(return to the previ- ous configuration settings). IGNIS 2500 AUTOMATIC FIRE EXTINGUISHING CONTROL PANEL...
Go to next window In the small window, select the correct module number (e.g., module #2). Confirm module number Select the I/O No. (L1...L22) for configuration. Go to next window IGNIS 2500 AUTOMATIC FIRE EXTINGUISHING CONTROL PANEL...
Page 36
The detected errors window will be displayed if the neces- sary parameters for activated I/Os are not configured. After reading the error list, save the configuration of the activated I/Os and complete the missing settings. IGNIS 2500 AUTOMATIC FIRE EXTINGUISHING CONTROL PANEL...
Confirm module number Select the monitoring line to be configured Go to the next window Select a parameter in order to change its value or function. Go to the next window IGNIS 2500 AUTOMATIC FIRE EXTINGUISHING CONTROL PANEL...
Page 38
In case of any changes made to the control panel configuration, a window appears which allows you to save or cancel those changes (return to the previous configura- tion settings). IGNIS 2500 AUTOMATIC FIRE EXTINGUISHING CONTROL PANEL...
Select the detection line to be configured Go to the next window Delay Off means that an alarm from this line will trigger a 2nd stage alarm without counting down the T1 or T2 delay. IGNIS 2500 AUTOMATIC FIRE EXTINGUISHING CONTROL PANEL...
The number of detection lines available in the coincidence configuration window depends on previously performed I/O declaration. Lines configured in the coincidence window should be on the same MSG-25 module. Figure 4.2.6/1 Line coincidence programming window IGNIS 2500 AUTOMATIC FIRE EXTINGUISHING CONTROL PANEL...
To change the module, select the first line. Go to the next window Select the correct module num- ber from the small windows list . IGNIS 2500 AUTOMATIC FIRE EXTINGUISHING CONTROL PANEL...
It is recommended that the inputs/outputs in one module are assigned to the same zone. The possible module failure will not affect the operation of another zone. IGNIS 2500 AUTOMATIC FIRE EXTINGUISHING CONTROL PANEL...
In order to enter the standard configuration in the main menu (after entering the 3rd access level) select the "CONFIGURATION" line, and then the "STANDARD CONFIG." line in the sub-menu. After IGNIS 2500 AUTOMATIC FIRE EXTINGUISHING CONTROL PANEL...
Page 44
L7- potential line with EZ criterion; 1 pulse-4 s, no delay, − L8 - potential line with criteria ALARM 2st.; continuous signal, no delay, − L9 - potential line with criteria EXTINGUISHING START; cyclical 1s/1s, no delays, IGNIS 2500 AUTOMATIC FIRE EXTINGUISHING CONTROL PANEL...
Page 45
L3 potential-free relay output with EXTING. START criterion; con- tinuous signal; no delay, − L4 potential-free relay outputs with DISCHARGE criterion; con- tinuous signal; no delay, MWS-60 S1-L1..L4 - configuration 4 potential outputs; zone 1, IGNIS 2500 AUTOMATIC FIRE EXTINGUISHING CONTROL PANEL...
"EVENTS" window contains all the events that have occurred including alarms. In the event reading window (Figure 4.2.13/1), the first two lines show the date, time and data related to the selected event name. Figure 4.2.13/1 Event reading window IGNIS 2500 AUTOMATIC FIRE EXTINGUISHING CONTROL PANEL...
Page 47
MEMORY CLEARING option from the main menu and following the instructions on the screen. Using the “IGNIS 2500 Configurator” program installed on a PC is a convenient way to read and store events data. The program can be downloaded from the manufacturer's website www.polon-alfa.com.
Blocking the group of ALARM DEVICES is signalled by lighting a lamp next to the button. Intermittent lighting of the lamp occurs in the case of partial blocking of the IGNIS 2500 AUTOMATIC FIRE EXTINGUISHING CONTROL PANEL...
Page 49
ALARM DEVICES Group or individual blocking Enables quick ac- cess to blocking a (WARNING ALARM DEVICES) group of alarm de- vices SAFETY DEVICES Group or individual blocking TRANSMISSION MKA-25 Blocking transmission to POLON 6000 IGNIS 2500 AUTOMATIC FIRE EXTINGUISHING CONTROL PANEL...
Page 50
ID-E359-001-GB Figure 4.4/1 Blocking Table 4.4/2 Blocking Use of Screen Description of activities buttons Select "BLOCKING" Go to the next window Select group blocking "OUTPUT GROUPS" or single blocking "IN- PUTS/OUTPUTS" IGNIS 2500 AUTOMATIC FIRE EXTINGUISHING CONTROL PANEL...
(for a 2-zone control panel) opening the control panel door, if the ZW 9 jumper is set in position 2-3 on the MSO module, - system fault in a given zone or communication with modules disturbed. IGNIS 2500 AUTOMATIC FIRE EXTINGUISHING CONTROL PANEL...
− enabled (automatically, if they are not blocked in the detection mode), − silenced (manually) - another alarm re-activates alarm devices, provided that the "reactiva- tion" option has been enabled, − blocked. IGNIS 2500 AUTOMATIC FIRE EXTINGUISHING CONTROL PANEL...
In case of activating the potential outputs on the MSG-25 module, the active state is signalled by LED diodes at the L7… L16 connectors. IGNIS 2500 AUTOMATIC FIRE EXTINGUISHING CONTROL PANEL...
Page 54
"enter" key again cancels the testing status of the selected line. Outputs testing is possible after en- tering the code of the 3rd access level and additional confirmation in the window which appears. IGNIS 2500 AUTOMATIC FIRE EXTINGUISHING CONTROL PANEL...
- setting the type of LCD display (contrast change) ZW 7 - not used BAT 1 - battery to support the clock during power failure Z 33 - connector for testing in the production process J 2, J foil keyboard connectors IGNIS 2500 AUTOMATIC FIRE EXTINGUISHING CONTROL PANEL...
- 24 V power supply from the MZU-25 module, - 2 connectors for a 24 V battery bank (2x12 V) coupling. The module also includes a system monitoring the condition and charging of 24 V (2x12 V) batteries. IGNIS 2500 AUTOMATIC FIRE EXTINGUISHING CONTROL PANEL...
Page 57
ID-E359-001-GB Figure7.1/1 MSG-25 module IGNIS 2500 AUTOMATIC FIRE EXTINGUISHING CONTROL PANEL...
Page 58
ID-E359-001-GB Figure 7.1/2 Outputs/inputs of the MSG-25 module IGNIS 2500 AUTOMATIC FIRE EXTINGUISHING CONTROL PANEL...
1 way of connecting a control line to the MSG- 25 module inputs 25 module inputs R1=2 kΩ R1=2 kΩ (or 750 Ω for "Y" active status) Rk=6.2 kΩ R2=4.3 kΩ Rk=R1+R2=6.3 kΩ IGNIS 2500 AUTOMATIC FIRE EXTINGUISHING CONTROL PANEL...
Page 60
Example of using the two-state monitoring line mode to supervise the status of external devices, e.g. the position of the room decompression damper. An incorrect position can be indicated as a failure of an external devices. Figure7.2/1 Ways of using control inputs IGNIS 2500 AUTOMATIC FIRE EXTINGUISHING CONTROL PANEL...
- the zone detection state causes the control panel to return to the AUTO- "MANUAL CON- MATIC (and manual) mode, provided that the control panel has not been TROL" switched to the manual mode by means of the button on the control panel door. IGNIS 2500 AUTOMATIC FIRE EXTINGUISHING CONTROL PANEL...
Page 62
The line can be connected to a contact coupled to a pressure gauge or “PRES- scale which changes its state if a loss of extinguishing agent occurs during SURE/WEIGHT" the detection of the control panel. IGNIS 2500 AUTOMATIC FIRE EXTINGUISHING CONTROL PANEL...
Actuation of the The function is intended to be used in a multi-zone configuration with common solenoid more than one IGNIS 2500 control panel and a common extinguishing valve agent resource. It enables: "EZ-(SV)COMMON"...
ALARM 1 Alarm state of the 1st stage of the control Alarm state - description panel. in Section 9.2 ALARM 2 Control panel stage 2 alarm condition: EXTING. START Start the extinguishing procedure: IGNIS 2500 AUTOMATIC FIRE EXTINGUISHING CONTROL PANEL...
Page 65
- PK1 * - with the contact circuit control on/off connected to the PK1 option contacts. Zone setting: -no zone (--------) RESETTING Resetting (clearing) the fire alarm status of the control panel IGNIS 2500 AUTOMATIC FIRE EXTINGUISHING CONTROL PANEL...
Page 66
(damage) causes release of relay and lack of damage causes activation of relay. The remaining relay outputs and potential outputs act directly, i.e. the fault condition causes activation. IGNIS 2500 AUTOMATIC FIRE EXTINGUISHING CONTROL PANEL...
Page 67
0...99 min. 0...99 min. 0...99 min. 0...99 [every 1 s] [every 1 s] [every 1 s] [every 1 s] Continuous 1 pulse Cyclical Cyclical- finished O - time available in a given mode IGNIS 2500 AUTOMATIC FIRE EXTINGUISHING CONTROL PANEL...
Page 68
Rk. D - rectifying diode selected so that max. conduction current (IF) is greater than max. load current, e.g.: 1N4001...1N4008 - 1 A, 100 V..1200 V 1N5401...1N5408 - 3 A, 100 V..1000 V IGNIS 2500 AUTOMATIC FIRE EXTINGUISHING CONTROL PANEL...
Page 69
D - rectifying diode selected so that max. conduction current (IF) is greater than max. load current, e.g.: 1N4001...1N4008 - 1 A, 100 V..1200 V 1N5401...1N5408 - 3 A, 100 V..1000 V IGNIS 2500 AUTOMATIC FIRE EXTINGUISHING CONTROL PANEL...
Page 70
In such a system, the failure of one output does not deprive the E solenoid valve the possi- bility of controlling it. Any potential outputs can be connected in the presented manner. Terminal re- sistors and diodes should be installed at the solenoid valve. IGNIS 2500 AUTOMATIC FIRE EXTINGUISHING CONTROL PANEL...
For the PK1 relay with the programmed "general fault" criterion and the circuit continuity monitoring turned on (the Z11 jumper, exceptionally in position 2-3), the circuit continuity failure may not be signalled by the control panel in case of simultaneous occurrence of other faults. IGNIS 2500 AUTOMATIC FIRE EXTINGUISHING CONTROL PANEL...
Page 72
S12 jumper in po- sition 1-2. The operation of the external circuit continuity control depends on the exter- nal voltage and requires polarity (+,-) as shown. IGNIS 2500 AUTOMATIC FIRE EXTINGUISHING CONTROL PANEL...
Page 73
- S13… 16 jumpers in po- sition 1-2, respectively. The operation of the external circuit continuity control system depends on the external voltage and requires the polarity (+, -) as shown in the fig. IGNIS 2500 AUTOMATIC FIRE EXTINGUISHING CONTROL PANEL...
ID-E359-001-GB 7.3.3. An example of using control panels in a multi-zone system Figure 7.3.3/1 Example of connection of two control panels in a multi-zone system IGNIS 2500 AUTOMATIC FIRE EXTINGUISHING CONTROL PANEL...
Page 75
Panel LK EZ COM- CYLINDER 2 + TOTAL S1+2 MSG-25 No. 1 - CYLINDER 3 L8 or TOTAL S1+2 MSG-25 No2 -L8 LK EZ COM- Control Panel MSG-25 No1 -L8 MSG-25 No2 -L8 IGNIS 2500 AUTOMATIC FIRE EXTINGUISHING CONTROL PANEL...
Page 76
PK3 forcing active state on LK - S1+2 EXTINGUISHING BLOCK MSG-25 No2 - Auxiliary potential-fee output Control Panel PK4 forcing active state on LK - S1+2 EXTINGUISHING BLOCK and MSG-25 No2 - LK -EZ COMMON IGNIS 2500 AUTOMATIC FIRE EXTINGUISHING CONTROL PANEL...
Ensure that the lines are connected correctly (±) during installation. Unused L11 ÷ L16 inputs, after reconfiguration, can serve as detection control lines, potential lines or supply external devices with +24 V voltage or remain inactive. IGNIS 2500 AUTOMATIC FIRE EXTINGUISHING CONTROL PANEL...
MSO-25 controller. The yellow-green wire that all modules are equipped with should be connected to the control panel housing. IGNIS 2500 AUTOMATIC FIRE EXTINGUISHING CONTROL PANEL...
Control line inputs -LK2 +LK2 -LS1 Potential outputs, +LS1 -LS2 supervised (signal lines) +LS2 On/Off jumpers for PK outputs cir- S1, S2 cuit continuity control system Figure 8.3/1 MKS-60 monitoring and control module IGNIS 2500 AUTOMATIC FIRE EXTINGUISHING CONTROL PANEL...
ID-E359-001-GB 8.4. Communication module via the MKA-25 addressable line The MKA-25 module is an interface that enables the IGNIS 2500 control panel to be connected to an addressable detection line of the POLON 6000 system. Cooperation with the POLON 6000 system, after programming the appropriate alarm variants, allows the use of detectors on the system's addressable lines in the automatic fire extinguishing zones supervised by the IGNIS 2500 control panel.
Page 83
- in the IGNIS 2500 control panel - adding the MKA-25 module according to point 4.2.1., - in the POLON 6000 system - adding the IGNIS 2500 control panel as a line element and activating (selected or all) signals that can be sent through the addressable line.
3. Active state of a control line config- Alarm delays of the 2nd st. alarm ured as an external alarm input until are enabled. the T1 or T2 delay counts down. T1, T2 > 0 IGNIS 2500 AUTOMATIC FIRE EXTINGUISHING CONTROL PANEL...
2nd stage alarm 2. The coincidence of the detection The 2nd stage alarm delay enabled. lines is fulfilled, but T1 or T2 time has T1, T2 > 0 not yet been counted down. IGNIS 2500 AUTOMATIC FIRE EXTINGUISHING CONTROL PANEL...
Page 86
- a window with information on the type and number of alarms appears on the LCD display, - an internal acoustic signalling device is activated, - the outputs programmed to operate from the 1st stage alarm are activated, - It is possible to mute the sound signalling. IGNIS 2500 AUTOMATIC FIRE EXTINGUISHING CONTROL PANEL...
Page 87
STOP lamp and changing the signal controlling the alarm devices by extending the pause time in relation to the pulse duration. The EXTINGUISHING STOP button stops the extinguishing signal and interrupts the countdown of the evacuation time. IGNIS 2500 AUTOMATIC FIRE EXTINGUISHING CONTROL PANEL...
Page 88
IGNIS 2500 AUTOMATIC FIRE EXTINGUISHING CONTROL PANEL...
Signalling of the second level alarm occurs after occurrence of the alarm on the second line, provided that the time T1 is counted down in advance (or T2 after acknowledgement). IGNIS 2500 AUTOMATIC FIRE EXTINGUISHING CONTROL PANEL...
ID-E359-001-GB 9.3.2. Manual activation with the EXTINGUISHING START button 9.3.3. Starting the extinguishing in automatic mode IGNIS 2500 AUTOMATIC FIRE EXTINGUISHING CONTROL PANEL...
You should also pay attention to the permissible current values of the individual outputs. In case of using a greater number of e.g. alarm devices and exceeding the acceptable current value, an external power supply should be taken into consideration. IGNIS 2500 AUTOMATIC FIRE EXTINGUISHING CONTROL PANEL...
Page 92
Automatic power off. When the control panel is operated only from the battery bank - it causes gradual, natural reduction of the supply voltage. Decrease of reserve supply voltage to approx. 22 V is signalled acoustically. Further decrease of the battery bank voltage and reaching the final discharge IGNIS 2500 AUTOMATIC FIRE EXTINGUISHING CONTROL PANEL...
The control panel should be mounted on the wall with three expansion bolts with a diameter of at least 8 mm. The arrangement of the control panel fastening holes is shown in Figure 10.1/1. Mounting is possible with the batteries removed. Figure 10.1/1 Mounting the control panel IGNIS 2500 AUTOMATIC FIRE EXTINGUISHING CONTROL PANEL...
In the vicinity of module connectors and cable grommets coming out of the control panel, on the rear wall of the casing, there are rails intended for connecting shielding wires to the metal casing of the control panel. IGNIS 2500 AUTOMATIC FIRE EXTINGUISHING CONTROL PANEL...
"confirmation" buttons may not function, then in the emergency mode it is possible to confirm and cancel the alarm by pressing the "manual control" button (approx. 4 seconds) on the second zone keypad. IGNIS 2500 AUTOMATIC FIRE EXTINGUISHING CONTROL PANEL...
- check the correctness of activation of the potential outputs that control the actuating devices by observing the control LEDs on the module PCB (printed circuit board) at each potential line connector or by measuring the voltage at the output before and after activation, IGNIS 2500 AUTOMATIC FIRE EXTINGUISHING CONTROL PANEL...
Page 97
(without signalling any faults or disablements) - the system can be handed over to the user. ID-E359-001/07.2024 IGNIS 2500 AUTOMATIC FIRE EXTINGUISHING CONTROL PANEL...
Page 98
ID-E359-001-GB IGNIS 2500 AUTOMATIC FIRE EXTINGUISHING CONTROL PANEL...
Need help?
Do you have a question about the IGNIS 2500 and is the answer not in the manual?
Questions and answers