Hussmann OCU-CR400VF8 Installation Manual

Hussmann OCU-CR400VF8 Installation Manual

4hp outdoor refrigeration unit

Advertisement

Quick Links

4
ADIABATIC COOLING SOLUTION
HP
OUTDOOR REFRIGERATION UNIT
INSTALLATION MANUAL
OCU-CR400VF8/OCU-CR400VF8SL
JULY 2022 - AJHH9A2000140A

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the OCU-CR400VF8 and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Hussmann OCU-CR400VF8

  • Page 1 ADIABATIC COOLING SOLUTION OUTDOOR REFRIGERATION UNIT INSTALLATION MANUAL OCU-CR400VF8/OCU-CR400VF8SL JULY 2022 - AJHH9A2000140A...
  • Page 2: Table Of Contents

    CONTENTS GENERAL INFORMATION SPRINKLING CONTROL AND TEMPERATURE SETTINGS Symbols Stop Think Act 5.1 Controller Settings 1.3 Staff Training 1.4 Electrical Connections 1.5 Refrigerants 1.6 Rated Specification DECOMMISSIONING & DISPOSAL PRE-INSTALLATION 6.1 Decommisioning 6.2 Disposal 2.1 Name of Each part 2.2 Operating Environment 2.3 Handling and Transporting Cases 2.4 Shipping Damages and Shortages TROUBLESHOOTING 2.5 Rating Plates 7.1 Troubleshooting...
  • Page 3: General Information

    Personal Protective Equipment whilst leakage, electric shock or fire may installing the case. occur. Always keep manual in safe place. NO WALK: Do not walk on top or on any parts of the unit. Unit damages or personal injuries may occur. NO SIT: Do not sit on top or on any parts of the unit. Unit damages or personal injuries may occur. PAGE 3 4HP OUTDOOR REFRIGERATION UNIT - HUSSMANN...
  • Page 4 NO CONNECTING SOCKETS: Do not use any connecting socket or extension cords. Be sure to use private line or socket as the main power source. Failure to do so could result in electric shock or fire. PAGE 4 4HP OUTDOOR REFRIGERATION UNIT - HUSSMANN...
  • Page 5: Stop Think Act

    Incomplete attachment may lead to penetration of out the training and requirements needed for their water, thereby causing current leak and fire/electrical maintenance technician staff to be educated to use the shock. unit correctly. The unit should always be kept in good - Confirm that solenoid valve cover is securely installed working order to ensure installer and user safety. Injury to personnel and damage to the unit and its components may occur if instructions in the manual are not correctly followed. If information would like to be added to this manual, or if suggestions would like to me made, contact Hussmann directly at any time. PAGE 5 4HP OUTDOOR REFRIGERATION UNIT - HUSSMANN...
  • Page 6: Refrigerants

    Pay close attention during transport, installation and dismantling not to damage the refrigerant pipelines. CAUTION: Gas is under high pressure. EVENT OF DAMAGE: Keep surrounding flames or sources of ignition away from the appliance. Properly ventilate the premises and use a breathing apparatus. Turn the unit off and notify the customer service department. Fire and heat may cause gas receptacles to rupture. Use water spray/ not jet or fog to extinguish. RATED SPECIFICATION PAGE 6 4HP OUTDOOR REFRIGERATION UNIT - HUSSMANN...
  • Page 7: Pre-Installation

    PRE INSTALLATION Name of Each Part Back of the Adiabatic Solution Water Pipe Elbow 90º Side Panel RH Evaporative Cooling Pad Panasonic 4hp Unit Front of the Adiabatic Solution Manual Ball Valve (Control Water Flow) Drain Bracket Solenoid Drain Outlet Valve Box PAGE 7 4HP OUTDOOR REFRIGERATION UNIT - HUSSMANN...
  • Page 8: Operating Environment

    Warehouse Managers may refuse loading. packing etc confirm with the parts list, attached Transportation requirements are to ensure unit to the unit for any short supplied and or damaged integrity and prevent unnecessary damage and avoid parts etc. If required notify Hussmann or delays in the unit installation schedule. representative within seven (7) days of delivery. Before storing the unit, ensure packaging is unbroken and does not display defect that may compromise preservation of the unit.
  • Page 9: Shipping Damages And Shortages

    PPE, first aid, disposal and emergency management. Refer page 29 (Risk Analysis) For MSDS sheet contact your Hussmann CAUTION: Care must be taken to avoid damage to solenoid valve box and electrical cable mounted under or at the left hand side of the unit INSPECT UNDERSIDE BEFORE LIFTING WITH FORKLIFT.
  • Page 10: Installation

    Side panel RH Next, assemble the Bottom panels using the existing holes and screws. Screw in together the other panels into each hole respectively. Mount both the rear panels. Use the existing holes and screws on the unit to fix the panel and avoid drilling. Rear panel RH Rear panel LH Rear Bottom Side Bottom Panel Panel NOTE: Information in this manual is to be followed in conjunction with specifications, work practices and regulations of the customer, installing company and relevant industry. PAGE 10 4HP OUTDOOR REFRIGERATION UNIT- HUSSMANN...
  • Page 11 Screw in place the panels all together Use silicone sealant to fill the edges and gaps Fix the drain brackets using the PVC valve and make sure the drain trays are water tight. socket, faucet socket and rubber seal. , the drain The final assembly should look like below. bracket corners are sealed and the PVC socket is tightened to avoid leakage. Use thread seal tape where necessary. Side drain Tray Lip over bottom panel edge PVC Valve socket Rubber seal Silicone here PAGE 11 4HP OUTDOOR REFRIGERATION UNIT- HUSSMANN...
  • Page 12 WARNING: Before Gluing the pipes ensure the pipe holes are facing downwards, and it is tightened to avoid leakage. PVC Pressure End Cap 3.12 Use cable ties to secure the pipes in place as Diameter: 20mm shown. PVC Pressure Pipe Length: 470mm Diameter: 20mm PVC Pressure Pipe Length: 615mm Diameter: 25mm PVC Praessure Elbow Diameter: 20mm Cable ties PAGE 12 4HP OUTDOOR REFRIGERATION UNIT- HUSSMANN...
  • Page 13 Fix the Valve Box bracket in place using the Connect the elbow and the pipes as shown existing holes and screws below. PVC Pressure Elbow Diameter: 20mm 3.16 Connect the elbow and pipes as shown below PVC Pressure Pipe for the drain and glue them togetherw. Length: 806mm Diameter: 20mm 3.14 Use cable tie to secure the pipes in place as shown. Cable ties PVC Pressvure pipe Diameter: 25mm PVC Pressure Elbow Diameter: 25mm PAGE 13 4HP OUTDOOR REFRIGERATION UNIT- HUSSMANN...
  • Page 14 Rear cover Side cover Corner Cover 3.20 Fix the Top cover on the body and screw it in place using the Tek Screws provided in the kit. Top Cover Cable tie here Solenoid Valve NC Pipe Nipple Threaded ¾” 240VAC 3/4” Diameter: 20mm Sprinkler Adapter Solenoid Valve Flow PVC Pressure Elbow Direction Nylex 3/4 Diameter: 20mm Manual Ball Valve PVC Valve Socket (Flow Controller) 20mm PVC Pipe Diameter; 20mm Length: 50mm PAGE 14 4HP OUTDOOR REFRIGERATION UNIT- HUSSMANN...
  • Page 15 INSTALLATION 3.21 Connect the water pipe / hose into the water inlet as marked Water Inlet Manual Ball Valve (control water flow) PAGE 15 4HP OUTDOOR REFRIGERATION UNIT- HUSSMANN...
  • Page 16 Rotate by 90° to open the solenoid valve manually. c. Open the manual ball valve turn it by 10° or less to avoid water overflow. d. Monitor the water flow to be sufficient across the cooling pads and ensure that there is no leakage from the pipe fittings and the drain. WARNING: During this test, if the water flow is high or more than it is needed, use the manual ball valve to control the water flow and set it for the actual automatic operation. e. After checking for leakage and the optimal water flow, set the solenoid valve state back to automatic. Set it at upward position for automatic control. PAGE 16 4HP OUTDOOR REFRIGERATION UNIT- HUSSMANN...
  • Page 17: Wiring And Circuit Diagram

    STEP B. the side cap. Earth Active (Label 1) Neutral (Label 2) STEP F. Screw back the housing cover and tighten Unscrew housing cover Unscrew side cap the side cap. STEP C. Once the side cap has been remove. Take Screw the out the washer and seal. Housing cover Washer Seal Tighten the side PAGE 17 4HP OUTDOOR REFRIGERATION UNIT- HUSSMANN...
  • Page 18 Insert the universal bush through the Solenoid Valve cover. Feed the solenoid valve shielded cable through a conduit and out through the universal bush as pictured. Front Panel STEP K. Remove the electrical controller panel to gain access to the electrical controller as picture below. Universal Bush Feed cable/conduit through the Solenoid cover and Universal Bush STEP i. Mount the box cover onto the bracket and use screws to fix it. Mount cover and screw cover to bracket PAGE 18 4HP OUTDOOR REFRIGERATION UNIT- HUSSMANN...
  • Page 19 Connect the Solenoid valve shielded cable into located on the left side of the unit. Run the the terminal strip number 7 and 8 labelled (Liquid cable and conduit around and into the hole tube electromagnetic valve). Connect the active brown wire to the terminal block (7). Connect the neutral blue wire to the terminal block (8). Connect the Green/yellow earth wire to the Earth screw. Neutral Earth Active WARNING:- To avoid serious injury from electrical shock, always disconnect the electrical power at Push and snap out the the main when replacing or fitting eyelet hole. Run the cable through the hole. any electrical component. PAGE 19 4HP OUTDOOR REFRIGERATION UNIT- HUSSMANN...
  • Page 20 Connect the active red wire to the terminal block (L1). Connect the white wire to the terminal block (L2). Connect the blue wire to the terminal block (L3). Connect the neutral black wire to the terminal block (N). Connect the Green/yellow earth wire to the Earth screw. Wiring Access Lower Panel Hole WARNING:- To avoid serious injury from electrical shock, always disconnect the electrical power at the main when replacing or fitting any electrical component. PAGE 20 4HP OUTDOOR REFRIGERATION UNIT- HUSSMANN...
  • Page 21 WIRING AND CIRUIT DIAGRAM STEP D. STEP K. Attached the cable clip to the conduit and Screw back the electrical controller panel. screw onto the front panel as shown. Electrical Controller Panel Attached cable clip Screw back the 4HP front panel. STEP D. Screw on Front Panel Attached cable clip PAGE 21 4HP OUTDOOR REFRIGERATION UNIT- HUSSMANN...
  • Page 22 Cautions for Electrical Wiring Work Electrical Shock and Fire Prevention (1) Apply grounding wiring. (2) The circuit must not be shared with other circuits. (The wire should not be shared with other equipment) (3) Electric wire should not touch high temperature components (compressor, gas cooler, discharge piping, etc.) and any metal edge. PAGE 22 4HP OUTDOOR REFRIGERATION UNIT- HUSSMANN...
  • Page 23: Wiring Diagram

    WIRING AND CIRUIT DIAGRAM 3.24 Adiabatic cooling solution with Solenoid valve wiring diagram PAGE 23 4HP OUTDOOR REFRIGERATION UNIT- HUSSMANN...
  • Page 24: Cleaning And Maintenance

    • Confirm correct operation of RCD (if fitted) (by • Visually check the 4HP refrigeration unit for any Licensed Person) damage and take appropriate remedial action • Ensure that the solenoid valve is installed the right (Call a licence technician or call Hussmann) way up (refer to 3.19 section) • Check that all pvc pipe are installed correctly CAUTION: If any damaged electrical components are identified during inspection isolate case power and contact service contractor.
  • Page 25: Six Monthly Maintenance

    5. Visual check solenoid valve for wear and tear or broken. If broken (Call a licence electrician to replaced soleniod valve) 6. Ensure all cable connections, including screw terminals, earth leads and straps, are secure. 7. Ensure that the correct fuse rating and type is fitted for all circuits. 8. Ensure that there are no refrigerant leaks. 9. Check that all case panels, pvc pipe and extrusions are secure and undamaged. 10. Check for rust or paint damage. 11. Safely switch power to the unit back on. With case power turned on: 12. Check that solenoid valve and controls are working correctly. PAGE 25 4HP OUTDOOR REFRIGERATION UNIT- HUSSMANN...
  • Page 26: Maintenance And Inspection

    MAINTENANCE AND INSPECTION EVAPORATIVE COOLING PAD REPLACEMENT Remove the old evaporative cooling pads 4.52 Unscrew the removable corner bracket from the top. EVAPORATIVE COOLING PAD REPLACEMENT Unscrew the Side, corner and rear cover 4.51 panels and remove it to expose the cooling Place the new evaporative cooling pads. 4.54 pads. PAGE 26 4HP OUTDOOR REFRIGERATION UNIT- HUSSMANN...
  • Page 27 MAINTENANCE AND INSPECTION Install back the three cover panels. 4.55 Side Cover Rear Cover Corner Cover 4.56 Screw back the top panel to the side panels. PAGE 27 4HP OUTDOOR REFRIGERATION UNIT- HUSSMANN...
  • Page 28: Sprinkling Control And Temperature Settings

    SPRINKLING CONTROL & TEMPERATURE SETTINGS CONTROLLER SETTINGS Setting method of sprinkling control for 4HP CO2 condensing unit Target model: OCU-CR400VF8 OCU-CR400VF8ASL Change the liquid tube electromagnetic valve output to the sprinkling electromagnetic valve output 1. Turn ON No.8 of 8P DIP switch (SW13). 2. Set the rotary switch (SW11) to “ALM HISTORY” 7seg LED display: “OFF” (initial setting) 3. Operate the ▲/▼ switch and change the setting to ON. 7seg LED display: “ON” 4. Set the rotary switch back to “OPERATION”. 5. Turn OFF No.8 of 8P DIP switch (SW13). The liquid tube electromagnetic valve output operates as the sprinkling electromagnetic valve output. Set the ambient temperature which start sprinkling control.
  • Page 29: Decommissioning And Disposal

    Removal of the refrigeration unit is to be in the • Sheet Metal and other various metals. reverse order of installation listed previously. • Copper / Aliminum • Cardboard • Dismantle the in accordance refrigeration unit • with the local laws on waste disposal and in respect of the environment in which we live. Remaining by commercial waste management PAGE 29 4HP OUTDOOR REFRIGERATION UNIT- HUSSMANN...
  • Page 30: Troubleshooting

    Evaporative cooling Worn pad and sign of Deteriorating Inspect the evaporative cooling pads and if required ideally replace them within 1-2 years to avoid clogs of dirt ACTION AT THE TIME OF FAILURE When the adiabatic cooling solution fails to operate, close the water supply manual ball valve to avoid over flow. To avoid failure recurrence, use caution for the following. (1) To avoid recurrence of the same failure, execute reliable failure diagnosis and identify the true cause before starting a repair. (2) When the piping is to be corrected, be sure to close the water supply and disconnect the solenoid valve from the power supply. Disconnect is to be undertaken by qualified persons only. (3) Always check and if necessary, shut down power and restart the unit. CAUTION: If any damaged electrical components are identified during inspection isolate case power and contact service contractor. PAGE 30 4HP OUTDOOR REFRIGERATION UNIT- HUSSMANN...
  • Page 31: Appendix

    HAZARD CONTROL MEASURES Electrical - Replacement of solenoid valve Request a service call. Electrically isolate unit before works Ergonomic - Moving/ positioning/ adjusting unit Staff must be trained in the correct procedures for setting up unit and ergonomic practices. PPE must be worn Falling -Connecting wiring during installation Use of barriers & fall arrest systems as appropriate & in accordance with State & Territory Legislation. Safe working at heights Falling - Climbing on 4HP refrigeration unit Staff must be trained in OH&S procedures. MUST not climb on unit. Slipping - Drain may leak or become blocked causing Visual Inspection and regular maintenance. Request water spillage service call when necessary. Cuts and stabbing - Potential for cuts caused by Visual Inspection and regular maintenance. Request damaged or missing parts service call when necessary. PPE must be worn when handling broken or damaged parts. PAGE 31 4HP OUTDOOR REFRIGERATION UNIT- HUSSMANN...
  • Page 32: Appendix 2 - Warranty

    APPENDIX APPENDIX 2 - WARRANTY APPENDIX 3 - DISCLAIMER The information in this manual is for “Qualified Hussmann reserves the right to modify the Persons Only”. It is NOT an Installation Guide for components within the case, as well as alter “NON Qualified Persons”. the descriptions and intructions provided in the manual.