Page 1
Installation Manual REFRIGERANT This AIR-TO-WATER HEATPUMP INDOOR UNIT contains and operates with refrigerant R32. THIS PRODUCT MUST ONLY BE INSTALLED OR SERVICED BY QUALIFIED PERSONNEL. WARNING Refer to National, State, Territory and local legislation, regulations, codes, installation & operation manuals, before the installation, maintenance and/or service of this product.
Page 3
PRECAUTION FOR USING R32 REFRIGERANT If the total refrigerant charge in the system is <1.84 k If the total refrigerant charge in the system is 1.84 k Symbol Description Unit Maximum refrigerant charge allowed, Total Floor Area of compliance to Minimum Venting Opening Area Bottom opening: Installation...
Page 4
For WH-SDC0309K3E5, WH-SDC0309K6E5 Minimum floor area Table I Maximum refrigerant charge allowed in a room (k ) 1.15m 1.20m 1.30m 1.40m 1.50m 1.60m 1.70m 1.80m Maximum refrigerant charge in a room ) (k ) 1.15m 1.20m 1.30m 1.40m 1.50m 1.60m...
Page 5
For WH-SXC09K3E5, WH-SXC09K6E5, WH-SXC12K6E5 Minimum floor area Table I Maximum refrigerant charge allowed in a room (k ) 1.15m 1.20m 1.30m 1.40m 1.50m 1.60m 1.70m 1.80m Maximum refrigerant charge in a room ) (k ) 1.15m 1.20m 1.30m 1.40m 1.50m 1.60m 1.70m...
CUTTING AND FLARING CONNECT THE CABLE TO THE INDOOR UNIT THE PIPING...
Page 10
INSTALLATION OF REMOTE CONTROLLER AS ROOM THERMOSTAT...
Page 11
Preparation: Mount the bottom case to the wall. Mount the top case. Connect the remote control wiring Preparation: Mount the top case. Mount the bottom case to the wall. Connect the remote control wiring...
Page 12
CHARGING THE WATER Water temperature (°C) Water expansion rate RECONFIRMATION...
Page 22
2. Insert a at head screwdriver into the slot on the top of the adaptor and remove the cover. Connect the other end of the CN-CNT cable connector to the connector inside the adaptor. Temperature Resistance Temperature Resistance (°C) (k ) (°C) (k )
System installation 3-1. Remote Controller Outline...
Page 24
For WH-SDC0309K3E5, WH-SDC0309K6E5 For WH-SXC09K3E5, WH-SXC09K6E5, WH-SXC12K6E5 First time of power ON (Start of installation) First time of power ON (Start of installation)
Page 32
21. Force Defrost 22. Defrost signal 23. Pump owrate 24. DHW defrost 25. Heating control 26. External meter...
Page 33
3-4. Operation Setup Heat 55°C 27. Water temp. for heating ON 35°C -5°C 15°C 28. Outdoor temp. for heating OFF 24°C 29. T for heating ON 30. Heater ON/OFF 0° 0 : 30 -2° -4° Cool 20°C 31. Water temp. for cooling ON 5°C 20°C 30°C...
Page 34
Auto 33. Outdoor temp. for (Heat to Cool) 15° 34. Outdoor temp. for (Cool to Heat) 10° Tank 35. Floor operation time (max) 36. Tank heat up time (max) 37. Tank re-heat temp. 38. Sterilization...
Page 35
3-5. Service Setup 39. Pump maximum speed 40. Pump down 45°C 41. Dry concrete 40°C 40°C 35°C 35°C 30°C 42. Service contact 3-6. Remote control setup 43. RC selection...
Service and maintenance Check Water Pressure from Remote Controller If forget Password and cannot operate remote controller Maintenance menu Setting method of Maintenance menu Custom menu Setting method of Custom menu...