  • Page 1 GG-CO CARBON MONOXIDE GAS SENSOR Installation and Operation Manual...
  • Page 2 GG-CO Warning Use this product only in the manner described in this manual. If the equipment is used in a manner not specified by Calibration Technologies, the protection provided by the equipment may be impaired. This equipment should be installed by qualified personnel.
  • Page 3: Table Of Contents

    GG-CO Table of Contents General description . . . . . . . . . . . . . . . . . . . . . 4 Installation .
  • Page 4: General Description

    GG-CO General Description Installation Locating the sensor The GG-CO sensor is a +24 VDC, three-wire, 4/20 mA sensor for carbon monoxide which utilizes proven One of the most important considerations when electrochemical sensor technology for fast and installing GG-CO sensors is that they must be easily accurate detection.
  • Page 5: Installation Guidelines

    GG-CO Installation Guidelines: • Remove and discard protective cell cap • Always mount the sensor vertically. 6.5" • Must be easily accessible for calibration and 2.0" maintenance. • Mount the sensor close to the potential leak source. • For optimum personnel protection, mount sensor in breathing zone (approximately 5 feet from floor).
  • Page 6: Wiring

    GG-CO Wiring Electrical wiring must comply with all applicable codes. Electrical Power: 24 VDC regulated, 350 mA. Output: Linear 4/20 mA output. Monitoring equipment may have a maximum input impedance of 700 ohms. Cable Recommendation: 20/3 shielded cable (General Cable C2525A or equivalent). Length of cable to sensor should be no greater than 1,500 feet.
  • Page 7: Operation

    LED functions (see Figure 2 on page 8) Calibration Note: Below are a few response characteristics which The GG-CO Sensor comes factory calibrated and may be an indication that the gas sensor is at or near should require only minimal adjustments after the end of its useful life.
  • Page 8 GG-CO Sensor Cable plugs into socket here Span adjustment Fault (red) LED: • On steady if supply voltage is Zero adjustment less than 10VDC. Status (amber) LED: • Blinks once per second if RFI is 40-200 mV detected. mVDC Power (green) LED: •...
  • Page 9: Maintenance

    Sensor Life: These electrochemical cells are extremely reliable, but several things can cause the cell chemicals to become depleted including: The GG-CO was designed for long life and minimal maintenance. For proper operation, it is essential • a period of time that the test and calibration schedule be adhered to.
  • Page 10: Specifications

    GG-CO Specifications Power (green) LED: Blinks once per second for 60 seconds during power-up. If supply voltage is too Input Power: +24 VDC, 350 mA low (<10VDC) or improperly grounded, will blink once Detection Principle: Electrochemical per second continuously. Stays on steady to indicate Detection Method: Diffusion power.
  • Page 11: Limited Warranty And Limitation Of Liability