Page 1
GG-CO CARBON MONOXIDE GAS SENSOR Installation and Operation Manual...
Page 2
GG-CO Warning Use this product only in the manner described in this manual. If the equipment is used in a manner not specified by Calibration Technologies, the protection provided by the equipment may be impaired. This equipment should be installed by qualified personnel.
GG-CO General Description Installation Locating the sensor The GG-CO sensor is a +24 VDC, three-wire, 4/20 mA sensor for carbon monoxide which utilizes proven One of the most important considerations when electrochemical sensor technology for fast and installing GG-CO sensors is that they must be easily accurate detection.
GG-CO Installation Guidelines: • Remove and discard protective cell cap • Always mount the sensor vertically. 6.5" • Must be easily accessible for calibration and 2.0" maintenance. • Mount the sensor close to the potential leak source. • For optimum personnel protection, mount sensor in breathing zone (approximately 5 feet from floor).
GG-CO Wiring Electrical wiring must comply with all applicable codes. Electrical Power: 24 VDC regulated, 350 mA. Output: Linear 4/20 mA output. Monitoring equipment may have a maximum input impedance of 700 ohms. Cable Recommendation: 20/3 shielded cable (General Cable C2525A or equivalent). Length of cable to sensor should be no greater than 1,500 feet.
LED functions (see Figure 2 on page 8) Calibration Note: Below are a few response characteristics which The GG-CO Sensor comes factory calibrated and may be an indication that the gas sensor is at or near should require only minimal adjustments after the end of its useful life.
Page 8
GG-CO Sensor Cable plugs into socket here Span adjustment Fault (red) LED: • On steady if supply voltage is Zero adjustment less than 10VDC. Status (amber) LED: • Blinks once per second if RFI is 40-200 mV detected. mVDC Power (green) LED: •...
Sensor Life: These electrochemical cells are extremely reliable, but several things can cause the cell chemicals to become depleted including: The GG-CO was designed for long life and minimal maintenance. For proper operation, it is essential • a period of time that the test and calibration schedule be adhered to.
GG-CO Specifications Power (green) LED: Blinks once per second for 60 seconds during power-up. If supply voltage is too Input Power: +24 VDC, 350 mA low (<10VDC) or improperly grounded, will blink once Detection Principle: Electrochemical per second continuously. Stays on steady to indicate Detection Method: Diffusion power.
No goods shall be returned to CTI until receipt by the buyer of shipping instructions from CTI; and c) the right of CTI to require that the buyer provide proof of purchase such as the original invoice, bill of sale or packing slip to establish that the product is within the warranty period.
Need help?
Do you have a question about the GG-CO and is the answer not in the manual?
Questions and answers