Fujitsu AIRSTAGE ASEH07KMCG Design & Technical Manual
Fujitsu AIRSTAGE ASEH07KMCG Design & Technical Manual

Fujitsu AIRSTAGE ASEH07KMCG Design & Technical Manual

Air conditioner wall mounted type
Hide thumbs Also See for AIRSTAGE ASEH07KMCG:
Table of Contents

Advertisement

Quick Links

AIR CONDITIONER
Wall mounted type
DESIGN & TECHNICAL MANUAL
INDOOR
ASEH07KMCG
ASEH09KMCG
ASEH12KMCG
ASEH14KMCG
OUTDOOR
AOEH07KMCG
AOEH09KMCG
AOEH12KMCG
ASEH07KMCG-B
ASEH09KMCG-B
ASEH12KMCG-B
ASEH14KMCG-B
AOEH14KMCG
DR_AS228ES_02
2024.06.11

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the AIRSTAGE ASEH07KMCG and is the answer not in the manual?

Questions and answers

Summary of Contents for Fujitsu AIRSTAGE ASEH07KMCG

  • Page 1 AIR CONDITIONER Wall mounted type DESIGN & TECHNICAL MANUAL INDOOR ASEH07KMCG ASEH07KMCG-B ASEH09KMCG ASEH09KMCG-B ASEH12KMCG ASEH12KMCG-B ASEH14KMCG ASEH14KMCG-B OUTDOOR AOEH07KMCG AOEH14KMCG AOEH09KMCG AOEH12KMCG DR_AS228ES_02 2024.06.11...
  • Page 2 App Store is a service mark of Apple Inc., registered in the U.S. and other countries. IOS is a trademark or registered trademark of Cisco in the U.S. and other countries and is used under license. Copyright © 2024 Fujitsu General Limited. All rights reserved.
  • Page 3: Table Of Contents

    CONTENTS Part 1. INDOOR UNIT................1 1. Specifications....................2 2. Wireless LAN control ..................4 2-1. System requirement......................4 3. Dimensions....................5 3-1. Models: ASEH07KMCG, ASEH09KMCG, ASEH12KMCG, ASEH14KMCG, ASEH07KMCG-B, ASEH09KMCG-B, ASEH12KMCG-B, and ASEH14KMCG-B ....5 3-2. Pipe exit length from the rear ...................7 4. Wiring diagrams ....................8 4-1.
  • Page 4 CONTENTS (continued) Part 2. OUTDOOR UNIT..............49 1. Specifications....................50 2. Dimensions....................51 2-1. Models: AOEH07KMCG, AOEH09KMCG, and AOEH12KMCG........51 2-2. Model: AOEH14KMCG ....................52 3. Installation space ..................53 3-1. Models: AOEH07KMCG, AOEH09KMCG, AOEH12KMCG, and AOEH14KMCG ..53 4. Refrigerant circuit ..................56 4-1. Models: AOEH07KMCG, AOEH09KMCG, and AOEH12KMCG........56 4-2.
  • Page 5: Part 1. Indoor Unit

    Part 1. INDOOR UNIT WALL MOUNTED TYPE: ASEH07KMCG ASEH09KMCG ASEH12KMCG ASEH14KMCG ASEH07KMCG-B ASEH09KMCG-B ASEH12KMCG-B ASEH14KMCG-B...
  • Page 6: Specifications

    1. Specifications Wall mounted Type Inverter, Heat pump ASEH07KMCG ASEH09KMCG ASEH12KMCG ASEH14KMCG Model name ASEH07KMCG-B ASEH09KMCG-B ASEH12KMCG-B ASEH14KMCG-B Power supply intake Outdoor unit Voltage System power supply Frequency Available voltage range 198—264 V Indoor unit power supply (from outdoor unit) Rated Btu/h 6,800...
  • Page 7 Wall mounted Type Inverter, Heat pump ASEH07KMCG ASEH09KMCG ASEH12KMCG ASEH14KMCG Model name ASEH07KMCG-B ASEH09KMCG-B ASEH12KMCG-B ASEH14KMCG-B Material Polypropylene + High-density polyethylene Drain hose Tip diameter Ø13.8 (I.D.), Ø15 to Ø16.8 (O.D.) °C 18 to 32 Cooling Operation range 80 or less Heating °C 16 to 30...
  • Page 8: Wireless Lan Control

    After installation of mobile app, user registration is required. For user registration and setup infor- mation, refer to Setting Manual attached with the product. For the latest version of the wireless LAN control manuals, refer to the following web site. https://www.fujitsu-general.com/global/support/ - 4 - 2-1. System requirement...
  • Page 9: Dimensions

    3. Dimensions 3-1. Models: ASEH07KMCG, ASEH09KMCG, ASEH12KMCG, ASEH14KMCG, ASEH07KMCG-B, ASEH09KMCG-B, ASEH12KMCG-B, and ASEH14KMCG-B Unit: mm Outline of indoor unit for pipe inlet Ø65 for pipe inlet Ø65 - 5 - 3-1. Models: ASEH07KMCG, ASEH09KMCG, ASEH12KMCG, ASEH14KMCG, 3. Dimensions ASEH07KMCG-B, ASEH09KMCG-B, ASEH12KMCG-B, and ASEH14KMCG-B...
  • Page 10: Installation Space Requirement

    ¢ Installation space requirement Provide sufficient installation space for product safety. Unit: mm 40 or more 70 or more Wall hook bracket 107 or more 183 or more Outline of the indoor unit 1,500 or more A: Install so that the flare connection part is outdoors. - 6 - 3-1.
  • Page 11: Pipe Exit Length From The Rear

    3-2. Pipe exit length from the rear Design the system considering the length of the pipes or hose exiting from the rear of the indoor unit. NOTE: Detailed shapes of the indoor unit and the tip of each pipe or hose may vary depending on the model.
  • Page 12: Wiring Diagrams

    4. Wiring diagrams 4-1. Models: ASEH07KMCG, ASEH09KMCG, ASEH12KMCG, ASEH14KMCG, ASEH07KMCG-B, ASEH09KMCG-B, ASEH12KMCG-B, and ASEH14KMCG-B - 8 - 4-1. Models: ASEH07KMCG, ASEH09KMCG, ASEH12KMCG, ASEH14KMCG, 4. Wiring diagrams ASEH07KMCG-B, ASEH09KMCG-B, ASEH12KMCG-B, and ASEH14KMCG-B...
  • Page 13: Capacity Table

    5. Capacity table Capacity tables show each of following values calculated based on the outdoor temperature and the indoor temperature, under given Airflow Rate (AFR): For cooling capacity: Total Capacity (TC), Sensible Heat Capacity (SHC), and Input Power (IP) For heating capacity: Total Capacity (TC) and Input Power (IP) 5-1.
  • Page 14 ¢ Models: ASEH14KMCG and ASEH14KMCG-B Indoor temperature °CDB °CWB °CDB 3.77 3.49 0.67 4.11 3.62 0.66 4.34 3.70 0.66 4.57 3.79 0.65 4.85 3.86 0.65 5.03 3.95 0.65 5.37 4.08 0.64 3.59 3.39 0.88 3.92 3.51 0.88 4.14 3.60 0.87 4.35 3.68 0.87...
  • Page 15: Heating Capacity

    5-2. Heating capacity NOTE: Values mentioned in the table are calculated based on the maximum capacity. ¢ Models: ASEH07KMCG and ASEH07KMCG-B Indoor temperature °CDB °CWB 1.85 0.95 1.83 0.97 1.81 0.98 1.80 1.02 1.78 1.04 2.22 1.00 2.20 1.02 2.17 1.03 2.16 1.07...
  • Page 16: Fan Performance

    6. Fan performance 6-1. Air velocity distributions ¢ Models: ASEH07KMCG, ASEH09KMCG, and ASEH12KMCG, ASEH07KMCG-B, ASEH09KMCG-B, and ASEH12KMCG-B Fan speed Operation mode Measuring conditions HIGH Unit: m/s Top view Horizontal louver: Up Vertical louver: Center Unit: m/s Top view Horizontal louver: Up Vertical louver: Left &...
  • Page 17 ¢ Models: ASEH14KMCG and ASEH14KMCG-B Fan speed Operation mode Measuring conditions HIGH Unit: m/s Top view Horizontal louver: Up Vertical louver: Center Unit: m/s Top view Horizontal louver: Up Vertical louver: Left & Right Unit: m/s Side view Horizontal louver: Up Vertical louver: Center Unit: m/s Side view...
  • Page 18: Airflow

    6-2. Airflow ¢ Models: ASEH07KMCG and ASEH07KMCG-B  Cooling Fan speed Airflow HIGH QUIET  Heating Fan speed Airflow HIGH QUIET - 14 - 6-2. Airflow 6. Fan performance...
  • Page 19 ¢ Models: ASEH09KMCG and ASEH09KMCG-B  Cooling Fan speed Airflow HIGH QUIET  Heating Fan speed Airflow HIGH QUIET - 15 - 6-2. Airflow 6. Fan performance...
  • Page 20 ¢ Models: ASEH12KMCG and ASEH12KMCG-B  Cooling Fan speed Airflow HIGH QUIET  Heating Fan speed Airflow HIGH QUIET - 16 - 6-2. Airflow 6. Fan performance...
  • Page 21 ¢ Models: ASEH14KMCG and ASEH14KMCG-B  Cooling Fan speed Airflow HIGH QUIET  Heating Fan speed Airflow HIGH QUIET - 17 - 6-2. Airflow 6. Fan performance...
  • Page 22: Operation Noise (Sound Pressure)

    7. Operation noise (sound pressure) 7-1. Noise level curve ¢ Models: ASEH07KMCG and ASEH07KMCG-B  Cooling  Heating NC-65 NC-65 NC-60 NC-60 NC-55 NC-55 NC-50 NC-50 HIGH NC-45 NC-45 HIGH NC-40 NC-40 NC-35 NC-35 NC-30 NC-30 NC-25 NC-25 NC-20 NC-20 QUIET QUIET NC-15...
  • Page 23 ¢ Models: ASEH12KMCG and ASEH12KMCG-B  Cooling  Heating NC-65 NC-65 NC-60 NC-60 NC-55 NC-55 NC-50 NC-50 NC-45 NC-45 HIGH HIGH NC-40 NC-40 NC-35 NC-35 NC-30 NC-30 NC-25 NC-25 NC-20 NC-20 NC-15 NC-15 QUIET QUIET 1,000 2,000 4,000 8,000 1,000 2,000 4,000 8,000...
  • Page 24: Sound Level Check Point

    7-2. Sound level check point Microphone Microphone NOTE: Detailed shape of the actual indoor unit might be slightly different from the one illustrated above. - 20 - 7-2. Sound level check point 7. Operation noise (sound pressure)
  • Page 25: Safety Devices

    8. Safety devices Model Type of Protection form ASEH07KMCG ASEH09KMCG ASEH12KMCG protection ASEH07KMCG-B ASEH09KMCG-B ASEH12KMCG-B Circuit Current fuse (PCB*) 250 V, 3.15 A protection °C Activate Fan motor stop Fan motor Thermal protection protection °C Reset Fan motor restart Model Type of Protection form ASEH14KMCG...
  • Page 26: External Input And Output

    9. External input and output External Input and Output PCB Indoor unit PCB CN47 (Ext. out) CN65 (Ext. in/out PCB) CN46 (Ext. in) SW301 SW302 Rotary switch CN314 CN313 CN312 CN311 CN310 CN308 Connecting point Input/Output Function Input select Input signal Operation/Stop CN46 Input...
  • Page 27: External Input

    9-1. External input With using external input function, some functions on this product can be controlled from an external device. • “Operation/Stop” mode or "Forced stop" mode can be selected with function setting of indoor unit. • A twisted pair cable should be used. Maximum length of cable is 150 m. •...
  • Page 28: External Input And Output Pcb

    ¢ External Input and Output PCB The indoor unit Operation/Stop can be set by using the input connector on the PCB. • Input select Use either one of these types of connectors according to the application. (Both types of connec- tors cannot be used simultaneously.) –...
  • Page 29: Input Signal Type

    ¢ Input signal type • Indoor unit Input signal type is only "Edge". Edge • External Input and Output PCB The input signal type can be selected. Signal type (edge or pulse) can be switched by the DIP switch 2 (SW302) on the External Input and Output PCB.
  • Page 30: External Output

    9-2. External output Use an external output cable with appropriate external dimension, depending on the number of ca- bles to be installed. ¢ Indoor unit • A twisted pair cable should be used. Maximum length of cable is 25 m. •...
  • Page 31 ¢ External Input and Output PCB • A twisted pair cable should be used. Maximum length of cable is 25 m. • Output voltage: High DC 12 V ±2 V, Low 0 V. • Permissible current: 50 mA • For details, refer to "Setting of external input and output"...
  • Page 32: Setting Of External Input And Output

    9-3. Setting of external input and output • Indoor unit Input Connection point Function setting number 46 Function Operation/Stop mode 1 (R.C. enabled) (Setting prohibited) CN46 Forced stop mode Operation/Stop mode 2 (R.C. disabled) Output Connection point Function setting number 60 Function Operation/Stop 01 to 08...
  • Page 33: Details Of Control Input Function

    9-4. Details of control input function ¢ Operation/Stop mode 1 • In the case of "Edge" input External Input and Output PCB Function External input Input signal Command setting Rotary SW302 switch Off → On Operation — Input of indoor unit CN46 On →...
  • Page 34 ¢ Forced stop • In the case of "Edge" input External Input and Output PCB Function External input Input signal Command setting Rotary SW302 switch Forced stop Off → On (R.C. disabled) — Input of indoor unit CN46 Normal On → Off (R.C.
  • Page 35: Operation/Stop Mode

    ¢ Operation/Stop mode 2 • In the case of “Edge” input External Input and Output PCB Function External input Input signal Command setting Rotary SW302 switch Operation Off → On (R.C. enabled) — Input of indoor unit CN46 Stop On → Off (R.C.
  • Page 36: Forced Thermostat Off

    ¢ Forced thermostat off External Input and Output External input Input signal Command Rotary switch Off → On Thermostat off External Input and 2, B, C, D CN313 Output PCB On → Off Normal operation CN313 Compressor Room temp. Set temp. - 32 - 9-4.
  • Page 37: Details Of Control Output Function

    9-5. Details of control output function ¢ Operation status External Input and Function Output PCB External output Output signal Status setting Rotary switch Off → On Operation 60-00 1, 2 Output of indoor unit CN47 On → Off Stop Off → On Operation External Input and —...
  • Page 38: Indoor Unit Fan Operation Status

    ¢ Indoor unit fan operation status External Input and Function Output PCB External output Output signal Status setting Rotary switch Off → On Fan run 60-10 Output of indoor unit CN47 On → Off Fan stop Off → On Fan run External Input and —...
  • Page 39: Group Connection

    10. Group connection NOTE: Group control cannot be used together with WLAN Adapter. Installation procedure for group control system: A number of indoor units can be operated at the same time using a single remote controller. NOTE: When different type of indoor units (such as wall-mounted type and cassette type, cassette type and duct type, or other combinations) are connected using group control system, some functions may no longer be available.
  • Page 40: Remote Controller

    11. Remote controller 11-1. Wireless remote controller ¢ Overview Signal transmitter MODE button FAN button 10°C HEAT button ECONOMY button SWING button OUTDOOR UNIT SET button LOW NOISE button TEMP. button ON TIMER button POWERFUL button OFF TIMER button Start/Stop button TIMER SELECT button RESET button...
  • Page 41 ¢ Specifications  Controller Unit: mm Top view Front view Side view Size (H × W × D) 205 × 61 × 17 Weight 124 (without batteries)  Holder Unit: mm 48.5 Ø 3.5 (Hole) Hole 26.2 69.3 Front View Side View Bottom View Size (H ×...
  • Page 42: Function Settings

    12. Function settings To adjust the functions of this product according to the installation environment, various types of function settings are available. NOTE: Incorrect settings can cause a product malfunction. 12-1. Function settings by using remote controller Some function settings can be changed on the remote controller. After confirming the setting proce- dure and the content of each function setting, select appropriate functions for your installation envi- ronment.
  • Page 43 NOTES: • The air conditioner custom code is set to prior to shipment. • If you do not know the air conditioner custom code setting, try each of the custom codes ( → → → ) until you find the code that operates the air conditioner. - 39 - 12-1.
  • Page 44: Contents Of Function Setting

    ¢ Contents of function setting Each function setting listed in this section is adjustable in accordance with the installation environ- ment. NOTE: Setting will not be changed if invalid numbers or setting values are selected.  Function setting list Function no. Functions Filter sign 30/31...
  • Page 45 2) Room temperature control for indoor unit sensor Depending on the installed environment, correction of the room temperature sensor may be re- quired. Select the appropriate control setting according to the installed environment. The temperature of the room temperature sensor is corrected as follows: Corrected temp.
  • Page 46 3) Room temperature control for wired remote controller sensor Depending on the installed environment, correction of the wire remote temperature sensor may be required. Select the appropriate control setting according to the installed environment. To change this setting, set Function 42 to Both “01”. Ensure that the Thermo Sensor icon is displayed on the remote controller screen.
  • Page 47 6) Remote controller custom code (Only for wireless remote controller) The indoor unit custom code can be changed. Select the appropriate custom code. Function number Setting value Setting description Factory setting ♦ 7) External input control “Operation/Stop” mode or “Forced stop” mode can be selected. Function number Setting value Setting description...
  • Page 48 10) Switching functions for external output terminal Functions of the external output terminal can be switched. For details, refer to “External input and output”. Function number Setting value Setting description Factory setting Operation status ♦ 01—08 (Setting prohibited) Error status Indoor unit fan operation status (Setting prohibited) - 44 -...
  • Page 49: 12-2.Custom Code Setting For Wireless Remote Controller

    12-2. Custom code setting for wireless remote controller To interconnect the air conditioner and the wireless remote controller, assignment of the custom code for the wireless remote controller is required. NOTE: Air conditioner cannot receive a signal if the air conditioner has not been set for the custom code.
  • Page 50: Accessories

    13. Accessories 13-1. Models: ASEH07KMCG, ASEH09KMCG, ASEH12KMCG, ASEH14KMCG, ASEH07KMCG-B, ASEH09KMCG-B, ASEH12KMCG-B, and ASEH14KMCG-B Part name Exterior Part name Exterior Operation manual Cloth tape Self-tapping screw Installation manual (large) Self-tapping screw Remote controller (small) Battery Wall hook bracket Remote controller Filter holder holder Installation spacer Air cleaning filters...
  • Page 51: Optional Parts

    14. Optional parts 14-1. Controllers Exterior Part name Model name Summary Remote controller that provides the functions you need in a sleek design that uniquely transforms itself to blend Wired Remote with any interior. Controller UTY-RVRY Wire type: Non-polar 2-wire (Touch Panel) Optional Communication Kit is necessary for installation.
  • Page 52: 14-2.Others

    14-2. Others Exterior Part name Model name Summary Air Cleaning Filter can be mounted to Air Cleaning UTR-FA16-5 the indoor unit. Filter (For antibacterial) Use to connect with various peripheral devices and air conditioner PCB. External UTY-XWZX Connect Kit Connecting point: CN46 and CN47 on Main PCB Required when external device is connected.
  • Page 53: Part 2. Outdoor Unit

    Part 2. OUTDOOR UNIT SINGLE TYPE: AOEH07KMCG AOEH09KMCG AOEH12KMCG AOEH14KMCG...
  • Page 54: Specifications

    1. Specifications Type Inverter, Heat pump Model name AOEH07KMCG AOEH09KMCG AOEH12KMCG AOEH14KMCG Power supply 230 V~ 50 Hz Power supply intake Outdoor unit Available voltage range 198—264 V Starting current Cooling 1,650 1,700 1,680 Airflow rate Heating 1,450 1,470 1,580 Type ×...
  • Page 55: Dimensions

    2. Dimensions 2-1. Models: AOEH07KMCG, AOEH09KMCG, and AOEH12KMCG Unit: mm 4-M10 hole Pitch of bolts for installation Top view Side view Front view Side view Airflow Drain port Ø42 Bottom view Side view (Valve part) - 51 - 2-1. Models: AOEH07KMCG, AOEH09KMCG, and AOEH12KMCG 2.
  • Page 56: Model: Aoeh14Kmcg

    2-2. Model: AOEH14KMCG Unit: mm 4-M10 hole Pitch of bolts for installation Top view Side view Front view Side view Airflow Drain port Ø42 Bottom view Side view (Valve part) - 52 - 2-2. Model: AOEH14KMCG 2. Dimensions...
  • Page 57: Installation Space

    3. Installation space 3-1. Models: AOEH07KMCG, AOEH09KMCG, AOEH12KMCG, and AOEH14KMCG ¢ Space requirement Provide sufficient installation space for product safety. CAUTION Keep the space shown in the installation examples. If the installation is not performed accordingly, it could cause a short circuit and result in a lack of operating performance.
  • Page 58: Multiple Outdoor Unit Installation

     Multiple outdoor unit installation • Provide at least 250 mm of space between the outdoor units if multiple units are installed. • When routing the piping from the side of an outdoor unit, provide space for piping. • No more than 3 units must be installed side by side. When 4 units or more are arranged in a line, provide the space as shown in the following ex- ample “When an obstruction in the upper space:”.
  • Page 59: Outdoor Units Installation In Multi-Row

     Outdoor units installation in multi-row Unit: mm Single parallel unit arrangement Multiple parallel unit arrangement 100 or more 200 or more 1,000 or more 2,000 or more 200 or more 400 or more 500 or more 1,000 or more 200 or more 250 or more 1,000 or more...
  • Page 60: Refrigerant Circuit

    4. Refrigerant circuit 4-1. Models: AOEH07KMCG, AOEH09KMCG, and AOEH12KMCG Heat exchanger 3-way 2-way (INDOOR) valve valve Muffler 4-way valve Strainer Expansion valve Heat exchanger Strainer (OUTDOOR) Cooling Heating : Thermistor (Discharge temperature) : Thermistor (Outdoor temperature) : Thermistor (Heat exchanger out temperature) : Thermistor (Pipe temperature) : Thermistor (Room temperature) - 56 -...
  • Page 61: Model: Aoeh14Kmcg

    4-2. Model: AOEH14KMCG Heat exchanger 3-way 2-way (INDOOR) valve valve Muffler Muffler 4-way valve Strainer Expansion valve Heat exchanger Strainer (OUTDOOR) Cooling Heating : Thermistor (Discharge temperature) : Thermistor (Outdoor temperature) : Thermistor (Heat exchanger out temperature) : Thermistor (Pipe temperature) : Thermistor (Room temperature) - 57 - 4-2.
  • Page 62: Wiring Diagrams

    5. Wiring diagrams 5-1. Models: AOEH07KMCG, AOEH09KMCG, AOEH12KMCG, and AOEH14KMCG - 58 - 5-1. Models: AOEH07KMCG, AOEH09KMCG, AOEH12KMCG, and AOEH14KMCG 5. Wiring diagrams...
  • Page 63: Capacity Compensation Rate For Pipe Length And Height Difference

    6. Capacity compensation rate for pipe length and height difference Height difference H Indoor unit is higher than outdoor unit Indoor unit is lower than outdoor unit Outdoor unit Indoor unit Outdoor unit Indoor unit Connection pipe Connection pipe 6-1. Models: AOEH07KMCG and AOEH09KMCG NOTE: Values mentioned in the table are calculated based on the maximum capacity.
  • Page 64: Model: Aoeh12Kmcg

    6-2. Model: AOEH12KMCG NOTE: Values mentioned in the table are calculated based on the maximum capacity. Pipe length (m) COOLING — — — 0.858 0.868 — — 0.929 0.872 0.882 Indoor unit is higher than outdoor unit *1 — 0.960 0.933 0.876 0.885...
  • Page 65: Model: Aoeh12Kmcg

    7. Additional charge calculation 7-1. Models: AOEH07KMCG and AOEH09KMCG Refrigerant type Factory charge amount ¢ Refrigerant charge Total pipe length 15 or less 20 (Max.) 20 g/m Additional charge amount 7-2. Model: AOEH12KMCG Refrigerant type Factory charge amount ¢ Refrigerant charge Total pipe length 15 or less 20 (Max.)
  • Page 66: Airflow

    8. Airflow 8-1. Model: AOEH07KMCG  Cooling 1,650  Heating 1,450 8-2. Model: AOEH09KMCG  Cooling 1,650  Heating 1,450 8-3. Model: AOEH12KMCG  Cooling 1,700 1,001  Heating 1,470 - 62 - 8-1. Model: AOEH07KMCG 8. Airflow...
  • Page 67: Model: Aoeh14Kmcg

    8-4. Model: AOEH14KMCG  Cooling 1,680  Heating 1,580 - 63 - 8-4. Model: AOEH14KMCG 8. Airflow...
  • Page 68: Operation Noise (Sound Pressure)

    9. Operation noise (sound pressure) 9-1. Noise level curve ¢ AOEH07KMCG  Cooling  Heating NC-65 NC-65 NC-60 NC-60 NC-55 NC-55 NC-50 NC-50 NC-45 NC-45 NC-40 NC-40 NC-35 NC-35 NC-30 NC-30 NC-25 NC-25 NC-20 NC-20 NC-15 NC-15 1,000 2,000 4,000 8,000 1,000 2,000...
  • Page 69 ¢ AOEH12KMCG  Cooling  Heating NC-65 NC-65 NC-60 NC-60 NC-55 NC-55 NC-50 NC-50 NC-45 NC-45 NC-40 NC-40 NC-35 NC-35 NC-30 NC-30 NC-25 NC-25 NC-20 NC-20 NC-15 NC-15 1,000 2,000 4,000 8,000 1,000 2,000 4,000 8,000 Octave band center frequency, Hz Octave band center frequency, Hz ¢...
  • Page 70: Sound Level Check Point

    9-2. Sound level check point Rear Microphone Microphone Airflow Side view Rear view NOTE: Detailed shape of the actual outdoor unit might be slightly different from the one illustrated above. - 66 - 9-2. Sound level check point 9. Operation noise (sound pressure)
  • Page 71: Electrical Characteristics

    10. Electrical characteristics Model name AOEH07KMCG AOEH09KMCG AOEH12KMCG AOEH14KMCG Voltage 230~ Power supply Frequency Max operating current * Starting current Circuit breaker current Power cable Cross- Wiring sectional spec. * Connection area cable * Limited wiring length NOTES: • *1: Maximum operating current is the total current of the indoor unit and the outdoor unit. •...
  • Page 72: Safety Devices

    11. Safety devices Model Type of Protection form AOEH07KM AOEH09KM AOEH12KM AOEH14KM protection 250 V, 20 A Circuit protection Current fuse (Main PCB*) 250 V, 5 A 100 ±15°C Activate Fan motor stop Fan motor Thermal protection protection 95 ±10°C Reset Fan motor restart 110°C...
  • Page 73: Accessories

    12. Accessories 12-1. Models: AOEH07KMCG, AOEH09KMCG, AOEH12KMCG, and AOEH14KMCG Part name Exterior Part name Exterior Installation manual Drain pipe - 69 - 12-1. Models: AOEH07KMCG, AOEH09KMCG, AOEH12KMCG, and AOEH14KMCG 12. Accessories...

Table of Contents

Save PDF