10.1........................25 ECHNICAL PARAMETERS 10.1.1. Common parameters ............................. 25 10.1.2. H0430 - temperature regulator ........................26 10.1.3. H3430 - relative humidity and temperature regulator .................. 26 10.1.4. H3431(P) - temperature and humidity regulator ..................26 10.1.5. H3433 - relative humidity and temperature regulator .................. 27 10.1.6.
Page 3
Models marked HxxxxZ are non-standard versions of the devices. Description is not included in this manual. Copyright: COMET SYSTEM, s.r.o. It is prohibited to copy and edit this instruction manual and make any changes at all without explicit agreement of COMET SYSTEM, s.r.o. All rights reserved.
Modbus communication protocol. The device communicates via link RS485. Type Temperature Humidity Pressure Computed value Binary inputs ✓ H0430 ✓ ✓ ✓ H3430 ✓ ✓ ✓ H3431 ✓...
Page 5
response time to relative humidity change. If water condensation occurs for longer time it can cause sensor damage. Similar effect can occur under water aerosol conditions. External temperature probe connectable to H4531 must be type of “two wires with shielding”. The probe cable length and size of conductor affects measurement accuracy.
5. Description of device function and setting Information from regulator is available directly through LCD or you can read them with one of next communication protocols (Modbus RTU, Advantech-ADAM). 5.1. Device setting from the manufacturer If special setting was not required in the order, regulator is set from the manufacturer to the following parameters: communication protocol: Modbus RTU...
external sensors and detectors. Visualization of binary inputs is done by three LED diodes placed on the left side from LCD. Green one represents input Binary 1, yellow input binary 2 and red input binary 3. If binary input is not connected or is without any signal, then binary input is interpreted as „1“, when input contact is closed (connected input), then binary input is interpreted as „0“.
If “far condition” is assigned to output relay, then there is possible to change the output relay status by Modbus communication protocol only. See chapter 6.1.4 at page 20. 5.4.2. When close output relay High limit „HI“ – the relay closes when measured value exceeds preset „high limit” for longer time than preset „delay time“.
5.4.3. Regulator address setting Regulator address for preset communication protocol RS485 network regulator address 5.5. Regulator setting change 5.5.1. Setting with PC and TSensor software User’s software TSensor provides setting of all regulator parameters. The program is available free to download at web page www.cometsystem.com. Run the TSensor program and follow the program instructions.
5.5.3. Setting with using of Modbus communication protocol See chapter 6.1.5 “Output relay alarm condition configuration with using of Modbus ” at page 21. communication protocol 5.6. Extended setting mode During regulator operation it is possible to change parameters available through “Actual regulator preset”...
Page 14
Acoustic alarm deactivation activated acoustic alarm is possible to acoustic alarm is still activated for all time and deactivate by pressing „ “ key it is impossible to deactivate it Relay response for error Regulator continuously checks its state during operation. In case error of assigned value measurement is found then output Relay1 (Relay2): stays unchanged (in previous status)
Page 15
Regulator address setting Regulator address for preset communication protocol RS485 network regulator address Communication speed Communication speed for preset communication protocol communication speed setting Visualization of binary inputs Visualization of inputs is done by three LED diodes. This option defines at which binary input status should LED diode indication lights –...
Page 16
Barometric pressure unit choice It is possible to measure barometric pressure at hPa, PSI, inHg, mBar, oz/in , mmHg, inH and kPa. There is shown preset unit. It is possible to change it after „SET“ key pressing. preset to hPa preset to PSI preset to inHg preset to mBar...
Page 17
Show relative humidity at LCD display This item provides to choice if actual measured relative humidity may be displayed at LCD display or not. It is possible to change it after „SET“ key pressing. don’t show value on LCD show value on LCD Show computed value at LCD display This item provides to choice if actual computed value may be displayed at LCD display or not.
specific enthalpy 5.7. Restore to „Factory default“ This item provides regulator restoring to factory setting. Press „SET“ key, select „YES“ and confirm it by pressing of „SET“ key. It reset regulator parameters to following values: communication protocol: Modbus RTU regulator address: communication speed: 9600Bd, no parity, 2 stop bits value assigned to Relay1 and Relay2:...
6.1. Modbus RTU Control units communicate on master-slave principle in half-duplex operation. Only master can send request and only addressed device responds. During sending of request no other slave station should respond. During communication, data transfer proceeds in binary format. Each Byte is sent as eight bit data word in format: 1 start bit, data word 8 bit (LSB first), 2 stop bits , without parity.
Then there is possible to change relay status by Modbus communication protocol command by requested value writing to following addresses: Address Address Function Description Status [hex] [dec] 0 ... Relay1 open Far condition for Relay1 0x0042 1 ... Relay1 closed 0 ...
Address Address Function Unit Description Status [hex] [dec] 0 ... Off 1 ... temperature 2 ... relative humidity Value 3 ... atmospheric pressure assigned to 4 ... computed value 0x004A output value 5 ... binary input 1 Relay2 6 ... binary input 2 7 ...
Page 23
• If jumper is closed during device operation, device temporarily changes its address to 00h, it will communicate in the same communication speed as before closing jumper and will communicate without check sum. After jumper is opened setting of address and check sum is reset in accordance with values stored in the device.
7. Error States of the device Device continuously checks its state during operation. In case error is found LCD displays corresponding error code: Error 0 - first line of LCD displays „Err0“. Check sum error of stored setting inside device’s memory.
8. Readings on LCD display °C, °F reading next to this symbol is measured temperature or error state of value %RH reading next to this symbol is measured relative humidity or error state of value hPa, PSI, inHg reading next to this symbol is measured pressure or error state of value. If selected pressure unit is mBar or oz/in or mmHg or inH O or kPa, there is shown only value...
500 mA Cable for input signal wiring: shielded, max. 10 m long, cable should not be led in parallel along power cabling. EMC: EN 61326-1, EN 55011 10.1.2. H0430 - temperature regulator Temperature: ±0,4 °C (±0,7 °F) Accuracy: -30 to +80 °C (-22 to 176 °F)
10.1.5. H3433 - relative humidity and temperature regulator Temperature: ± 0,4 °C (±0,7 °F) Accuracy: -30 to +125 °C (-22 to 257 °F) Range: 0,1 °C (0,2 °F) Resolution: Relative humidity: (reading is temperature compensated at entire temperature range) ± 2,5 %RH from 5 to 95 %RH at 23 °C (73,4 °F) Accuracy: Range: 0 to 100 %RH...
10.1.9. Value computed from measured relative humidity and temperature Dew point temperature -60 to +80 °C (-76 to 176 °F) Range: ±1,5°C (±2,7°F) at ambient temperature T<25°C (77°F) and relative Accuracy: humidity RH >30%, for more details see graphs below Absolute humidity Range: 0 to 400 g/m...
Specific humidity ±2g/kg at ambient temperature T < 35°C (95 °F) Accuracy: Range: 0 to 550 g/kg Mixing ratio ±2g/kg at ambient temperature T < 35°C (95 °F) Accuracy: Range: 0 to 995 g/kg Specific enthalpy ± 3kJ/kg at ambient temperature T < 25°C (77 °F) Accuracy: Range: 0 to 995 kJ/kg...
Air flow velocity (H3431P probe): up to 25 m/s at a pressure of 1bar (1m/s at a pressure of 25 bar) Protection: H0430, H4431 ..IP65 H7430, H7431 ..IP54, sensors are located in cover with IP40 protection H3430, H3433 .
Page 31
11. Appendix A Connection of transmitters with RS485 output to the PC The ELO E214 converter is an optional accessory for connection of transmitter with RS485 interface to the PC via USB port. Link RS485 is connected across pin 9 A(+) and pin 8 B(-). The pull up, pull down and termination resistors are part of the transmitter.
Page 32
12. Appendix B The probe for measuring the moisture of compressed air should be placed directly on the pressure pipelines to achieve higher measurement accuracy and fast response times. But they are cases where such placement is not possible. The reason is the high air speed, high temperature, high pollution, small diameter pipes, etc.
Page 33
13. Appendix C This chapter contains basic information about connection of the detectors (optional accessories) to binary inputs of regulator. The detectors install in accordance with the attached instructions for use. SP008 power detector AC voltage presence sensor with optical indicator (green LED). input voltage : 230Vac/50Hz power plug...
Page 34
14. Appendix D Wiring diagram of relay contacts for devices with serial number lower than 16981000. IE-HGS-HX43X-13...