Comet H0430 Instruction Manual

Temperature, humidity and pressure regulator with rs485 serial output
Table of Contents

Advertisement

Quick Links

Temperature, humidity and pressure regulator
with RS485 serial output
H0430
H3430
H3431
H3431P
H3433
H4431
H7430
H7431
Instruction Manual

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the H0430 and is the answer not in the manual?

Questions and answers

Summary of Contents for Comet H0430

  • Page 1 Temperature, humidity and pressure regulator with RS485 serial output H0430 H3430 H3431 H3431P H3433 H4431 H7430 H7431 Instruction Manual...
  • Page 2: Table Of Contents

    10.1........................25 ECHNICAL PARAMETERS 10.1.1. Common parameters ............................. 25 10.1.2. H0430 - temperature regulator ........................26 10.1.3. H3430 - relative humidity and temperature regulator .................. 26 10.1.4. H3431(P) - temperature and humidity regulator ..................26 10.1.5. H3433 - relative humidity and temperature regulator .................. 27 10.1.6.
  • Page 3 Models marked HxxxxZ are non-standard versions of the devices. Description is not included in this manual. Copyright: COMET SYSTEM, s.r.o. It is prohibited to copy and edit this instruction manual and make any changes at all without explicit agreement of COMET SYSTEM, s.r.o. All rights reserved.
  • Page 4: General Description

    Modbus communication protocol. The device communicates via link RS485. Type Temperature Humidity Pressure Computed value Binary inputs ✓ H0430 ✓ ✓ ✓ H3430 ✓ ✓ ✓ H3431 ✓...
  • Page 5 response time to relative humidity change. If water condensation occurs for longer time it can cause sensor damage. Similar effect can occur under water aerosol conditions. External temperature probe connectable to H4531 must be type of “two wires with shielding”. The probe cable length and size of conductor affects measurement accuracy.
  • Page 6: Typical Application Wiring, Connection Of Terminals

    3. Typical application wiring, connection of terminals 4. Dimensions H0430 IE-HGS-HX43X-13...
  • Page 7 H3433 H3430 H7430 IE-HGS-HX43X-13...
  • Page 8 H4431 H3431(P) H7431 Probe for compressed air measurement IE-HGS-HX43X-13...
  • Page 9: Description Of Device Function And Setting

    5. Description of device function and setting Information from regulator is available directly through LCD or you can read them with one of next communication protocols (Modbus RTU, Advantech-ADAM). 5.1. Device setting from the manufacturer If special setting was not required in the order, regulator is set from the manufacturer to the following parameters: communication protocol: Modbus RTU...
  • Page 10: Actual Regulator Preset

    external sensors and detectors. Visualization of binary inputs is done by three LED diodes placed on the left side from LCD. Green one represents input Binary 1, yellow input binary 2 and red input binary 3. If binary input is not connected or is without any signal, then binary input is interpreted as „1“, when input contact is closed (connected input), then binary input is interpreted as „0“.
  • Page 11: When Close Output Relay

    If “far condition” is assigned to output relay, then there is possible to change the output relay status by Modbus communication protocol only. See chapter 6.1.4 at page 20. 5.4.2. When close output relay High limit „HI“ – the relay closes when measured value exceeds preset „high limit” for longer time than preset „delay time“.
  • Page 12: Regulator Address Setting

    5.4.3. Regulator address setting Regulator address for preset communication protocol RS485 network regulator address 5.5. Regulator setting change 5.5.1. Setting with PC and TSensor software User’s software TSensor provides setting of all regulator parameters. The program is available free to download at web page www.cometsystem.com. Run the TSensor program and follow the program instructions.
  • Page 13: Setting With Using Of Modbus Communication Protocol

    5.5.3. Setting with using of Modbus communication protocol See chapter 6.1.5 “Output relay alarm condition configuration with using of Modbus ” at page 21. communication protocol 5.6. Extended setting mode During regulator operation it is possible to change parameters available through “Actual regulator preset”...
  • Page 14 Acoustic alarm deactivation activated acoustic alarm is possible to acoustic alarm is still activated for all time and deactivate by pressing „ “ key it is impossible to deactivate it Relay response for error Regulator continuously checks its state during operation. In case error of assigned value measurement is found then output Relay1 (Relay2): stays unchanged (in previous status)
  • Page 15 Regulator address setting Regulator address for preset communication protocol RS485 network regulator address Communication speed Communication speed for preset communication protocol communication speed setting Visualization of binary inputs Visualization of inputs is done by three LED diodes. This option defines at which binary input status should LED diode indication lights –...
  • Page 16 Barometric pressure unit choice It is possible to measure barometric pressure at hPa, PSI, inHg, mBar, oz/in , mmHg, inH and kPa. There is shown preset unit. It is possible to change it after „SET“ key pressing. preset to hPa preset to PSI preset to inHg preset to mBar...
  • Page 17 Show relative humidity at LCD display This item provides to choice if actual measured relative humidity may be displayed at LCD display or not. It is possible to change it after „SET“ key pressing. don’t show value on LCD show value on LCD Show computed value at LCD display This item provides to choice if actual computed value may be displayed at LCD display or not.
  • Page 18: Restore To „Factory Default

    specific enthalpy 5.7. Restore to „Factory default“ This item provides regulator restoring to factory setting. Press „SET“ key, select „YES“ and confirm it by pressing of „SET“ key. It reset regulator parameters to following values: communication protocol: Modbus RTU regulator address: communication speed: 9600Bd, no parity, 2 stop bits value assigned to Relay1 and Relay2:...
  • Page 19: Modbus Rtu

    6.1. Modbus RTU Control units communicate on master-slave principle in half-duplex operation. Only master can send request and only addressed device responds. During sending of request no other slave station should respond. During communication, data transfer proceeds in binary format. Each Byte is sent as eight bit data word in format: 1 start bit, data word 8 bit (LSB first), 2 stop bits , without parity.
  • Page 20: Far Controlling Of Output Relays Status

    Addition for H7430 and H7431 regulators with barometric pressure measurement: Address Address Variable Unit Format Size Status [hex] [dec] Int*10 Int*1000 inHg Int*100 mBar Int*10 barometric pressure 0x0034 BIN16 oz/in Int*10 mmHg Int*10 Int*10 Int*100 Legend: • * depends on device setting (by User´s software) •...
  • Page 21: Output Relay Alarm Condition Configuration With Using Of Modbus Communication Protocol

    Then there is possible to change relay status by Modbus communication protocol command by requested value writing to following addresses: Address Address Function Description Status [hex] [dec] 0 ... Relay1 open Far condition for Relay1 0x0042 1 ... Relay1 closed 0 ...
  • Page 22: Protocol Compatible With Advantech-Adam Standard

    Address Address Function Unit Description Status [hex] [dec] 0 ... Off 1 ... temperature 2 ... relative humidity Value 3 ... atmospheric pressure assigned to 4 ... computed value 0x004A output value 5 ... binary input 1 Relay2 6 ... binary input 2 7 ...
  • Page 23 • If jumper is closed during device operation, device temporarily changes its address to 00h, it will communicate in the same communication speed as before closing jumper and will communicate without check sum. After jumper is opened setting of address and check sum is reset in accordance with values stored in the device.
  • Page 24: Error States Of The Device

    7. Error States of the device Device continuously checks its state during operation. In case error is found LCD displays corresponding error code: Error 0 - first line of LCD displays „Err0“. Check sum error of stored setting inside device’s memory.
  • Page 25: Readings On Lcd Display

    8. Readings on LCD display °C, °F reading next to this symbol is measured temperature or error state of value %RH reading next to this symbol is measured relative humidity or error state of value hPa, PSI, inHg reading next to this symbol is measured pressure or error state of value. If selected pressure unit is mBar or oz/in or mmHg or inH O or kPa, there is shown only value...
  • Page 26: H0430 - Temperature Regulator

    500 mA Cable for input signal wiring: shielded, max. 10 m long, cable should not be led in parallel along power cabling. EMC: EN 61326-1, EN 55011 10.1.2. H0430 - temperature regulator Temperature: ±0,4 °C (±0,7 °F) Accuracy: -30 to +80 °C (-22 to 176 °F)
  • Page 27: H3433 - Relative Humidity And Temperature Regulator

    10.1.5. H3433 - relative humidity and temperature regulator Temperature: ± 0,4 °C (±0,7 °F) Accuracy: -30 to +125 °C (-22 to 257 °F) Range: 0,1 °C (0,2 °F) Resolution: Relative humidity: (reading is temperature compensated at entire temperature range) ± 2,5 %RH from 5 to 95 %RH at 23 °C (73,4 °F) Accuracy: Range: 0 to 100 %RH...
  • Page 28: Value Computed From Measured Relative Humidity And Temperature

    10.1.9. Value computed from measured relative humidity and temperature Dew point temperature -60 to +80 °C (-76 to 176 °F) Range: ±1,5°C (±2,7°F) at ambient temperature T<25°C (77°F) and relative Accuracy: humidity RH >30%, for more details see graphs below Absolute humidity Range: 0 to 400 g/m...
  • Page 29: Relative Humidity And Temperature Restriction

    Specific humidity ±2g/kg at ambient temperature T < 35°C (95 °F) Accuracy: Range: 0 to 550 g/kg Mixing ratio ±2g/kg at ambient temperature T < 35°C (95 °F) Accuracy: Range: 0 to 995 g/kg Specific enthalpy ± 3kJ/kg at ambient temperature T < 25°C (77 °F) Accuracy: Range: 0 to 995 kJ/kg...
  • Page 30: End Of Operation

    Air flow velocity (H3431P probe): up to 25 m/s at a pressure of 1bar (1m/s at a pressure of 25 bar) Protection: H0430, H4431 ..IP65 H7430, H7431 ..IP54, sensors are located in cover with IP40 protection H3430, H3433 .
  • Page 31 11. Appendix A Connection of transmitters with RS485 output to the PC The ELO E214 converter is an optional accessory for connection of transmitter with RS485 interface to the PC via USB port. Link RS485 is connected across pin 9 A(+) and pin 8 B(-). The pull up, pull down and termination resistors are part of the transmitter.
  • Page 32 12. Appendix B The probe for measuring the moisture of compressed air should be placed directly on the pressure pipelines to achieve higher measurement accuracy and fast response times. But they are cases where such placement is not possible. The reason is the high air speed, high temperature, high pollution, small diameter pipes, etc.
  • Page 33 13. Appendix C This chapter contains basic information about connection of the detectors (optional accessories) to binary inputs of regulator. The detectors install in accordance with the attached instructions for use. SP008 power detector AC voltage presence sensor with optical indicator (green LED). input voltage : 230Vac/50Hz power plug...
  • Page 34 14. Appendix D Wiring diagram of relay contacts for devices with serial number lower than 16981000. IE-HGS-HX43X-13...