CHAPTER 1: INTRODUCTION GENERAL FEATURES DESCRIPTION: The PLUS100 THR system allows the user to control temperature and humidity in seasoning/preservation rooms and industrial processes. The system consists of the 100N MASTER THR unit to which all electrical connections are made and the PLUS100 THR control console, equipped with LCD display for fast, comprehensive monitoring of conditions inside the room.
CHAP. 1 - Introduction PLUS100 THR PRODUCT IDENTIFICATION CODE 200P100THR3 Temperature and humidity control for seasoning, preservation and industrial processes. Complete with display and 100N MASTER DIMENSIONS Dimensions in mm PLUS100 THR 100N MASTER THR IDENTIFICATION DATA The unit described in this manual has an ID plate on its side showing the relevant ID data: •...
1mm². The probes extension or shortening could alter the factory calibration; then check and calibrate through an external thermometer. STANDARD EQUIPMENT FOR ASSEMBLY AND USE PLUS100 THR electronic controller kit, for assembling and using, contains: • N° 2 temperature probes; • N° 1 fixing bracket;...
Page 7
Fig. 1: Position the 100N MASTER THR in the din guide and insert the four plugs to fix the box to the panel. Fig. 2: Disposition of console PLUS100 THR components. Fig. 3: Example of PLUS100THR installation. USE AND MAINTENANCE MANUAL Rel.
Page 8
CAP. 2 - Installation PLUS100 THR FUNCTIONS MANAGED BY PLUS100 THR • Display and adjustment of temperature and humidity settings (neutral zone). • Stand-by activation/deactivation. • Sensor alarms. • Air change parameter adjustment. • Defrost parameter adjustment. • Pauses parameter adjustment.
16A 250V (AC1) (see connection scheme) Dimensional Characteristics Dimensions of 100N MASTER 11.4cm x 6.9cm x 21.4cm (HxWxL) Dimensions of PLUS100 THR (housing) 9.8cm x 3.5cm x 18.0cm (HxWxL) Insulation and Mechanical Characteristics Display protection rate IP55 Box material Extinguishing ABS USE AND MAINTENANCE MANUAL Rel.
The intervention service in warranty can be refused when the equipment is modified or transformed. Under no circumstances Pego S.r.l. will be liable for any loss of data and information, costs of goods or substitute services, damage to property, people or animals, loss of sales...
CHAP. 5 - Parameters programming PLUS100 THR CHAPTER 5: PARAMETERS PROGRAMMING CONTROL PANEL FRONTAL KEYBOARD PROGRAM START/STOP (to press 5 seconds for selecting the program to run, to press 5 seconds for finishing a running program)
CHAP. 5 - Parameters programming PLUS100 THR DOWN / MUTE ALARM / FORCING AIR CHANGE COLD ROOM LIGHT DISPLAY LED PHASE 0 advancing/ Dripping / Day germination phase PHASE 1 advancing PHASE 2 advancing PHASE 3 advancing PHASE 4 advancing / Night germination phase...
Page 13
CHAP. 5 - Parameters programming PLUS100 THR PHASE 5 advancing Refreshment Ambient temperature value/ parameters Ambient relative humidity / parameters value / error codes Time / date / time parameters value / running program / timer Programming (the controller is in programming phase)
Stand-by GENERAL FEATURES For safety reasons and to simplify the operator’s work, the PLUS100 THR has two programming levels; the first level is used to modify SETPOINT parameters (i.e. those parameters that are changed frequently). The second level is for general parameter programming of the various board work modes.
Page 15
CHAP. 5 - Parameters programming PLUS100 THR FIRST LEVEL PROGRAMMING (User Level) To access the first programming level proceed as follows: 1. Press the () and () keys simultaneously and keep them pressed for a few seconds until the first programming variable appears on the display.
Page 16
CHAP. 5 - Parameters programming PLUS100 THR Fans pause after defrosting (minutes) Enables keeping the fans still for an F5 time after dripping. 0 ÷ 10 min 0 min This time starts from the end of dripping. If dripping is not set, at the end of defrosting the fans pause occurs directly.
Page 17
CHAP. 5 - Parameters programming PLUS100 THR SECOND LEVEL PROGRAMMING (Installer Level) To access the second programming level, press the UP () and DOWN () keys and the LIGHT key simultaneously for a few seconds. When the first programming variable appears the system automatically goes to stand-by.
Page 18
CHAP. 5 - Parameters programming PLUS100 THR Evaporator fans duration 0 ÷ 240 seconds 0:00:10 recirculation. Fans working time for F6 Fans speed during 0 = High speed seasoning/preservation The value of this variable is amended based 1 = Low speed...
Page 19
CHAP. 5 - Parameters programming PLUS100 THR Temperature differential referred Setpoint for COLD BLOCK. 0 ÷ 20 °C It constitutes the SET-btF limit below which cold call relay (3-4) 0 = Disabled dehumidification relay (25-26) are disabled. Temperature differential referred Setpoint for HOT BLOCK.
Page 20
CHAP. 5 - Parameters programming PLUS100 THR 0 = Total block. It’s possible to only see the temperature and humidity set point. 1 = Blocks access in 1st and level programmes. Blocks access in germination Password: type of protection. cycle amendment (Active when PA is different from 0).
Page 21
PLUS100 THR VARIABLES MEANING VALUES DEFAULT CIC=0 at the end of the last program phase (phase 5) it moves to manual. 0 = it ends the program and CIC=1 at the end of the last timed phase moves on to manual.
Page 22
CHAP. 5 - Parameters programming PLUS100 THR 0 = High speed Phase 3 evaporator fans speed. Amends 1 = Low speed the value of 2nd level variable (F8) (only if rin=1) 0:00...99:30 Phase 3 duration 0:00 (30 min steps) Phase 4 temperature setpoint -45,0 ÷...
Page 23
Temperature 2 SET. -45,0 ÷ +45,0 °C 0,0°C SWITCHING ON THE PLUS100 THR ELECTRONIC CONTROLLER 5.13 After having wired the electronic controller, apply voltage 230Vac; the control will immediately and simultaneously emit a sound for a few seconds and remain fully switched- on on the display.
Page 24
CHAP. 5 - Parameters programming PLUS100 THR Parameter C1 introduces a delay between a switch-off and the subsequent re-activation of the cold. Hot can be deactivated with parameter EnH (EnH=0 disables the hot relay in all conditions). HUMIDITY/DEHUMIDIFICATION: PRESERVATION OF AMBIENT HUMIDITY 5.15...
Page 25
CHAP. 5 - Parameters programming PLUS100 THR 2. Dehumidifies with the hot (the hot is called to dehumidify, the cold is added only to maintain ambient temperature) 3. Separate dehumidification (only the dehumidification output activates but hot and cold are not called) It is possible to give a maximum time for the dehumidification phase (parameter dEt) by signalling an alarm or forcing a refreshment (parameter dEo).
CHAP. 5 - Parameters programming PLUS100 THR PAUSE 5.18 The refreshment is a phase of the pause process of the temperature and humidity management. Refreshments are managed with parameters Pr and dr. Pr defines the interval between one refreshment and the following one, dr defines the duration of the refreshment.
CHAP. 5 - Parameters programming PLUS100 THR PASSWORD FUNCTION 5.21 The password function activates by setting a value different from 0 for parameter PA. See parameter P1 for the different protection levels. Protection is enabled automatically after approx. 2 minutes of inactivity on the keyboard.
Page 28
CHAP. 5 - Parameters programming PLUS100 THR • Temperature setpoint. • Humidity setpoint. • Refreshments enabling/disabling. • High or low fans speed. • Phase duration (maximum 99 hours with 30 min steps). For the dripping phase it is possible to exclude the humidity and the cold management.
Page 29
CHAP. 5 - Parameters programming PLUS100 THR DAY/NIGHT CYCLE FOR GERMINATION LIGHTS 5.23 By setting parameter Cg (Germination/seasoning cycle) at second programming level, it is possible to choose the use of the programmes or a special program suitable for day/night cycles: Cg = 0 (default) activates the automatic programmes management for seasoning.
CHAP. 6 - Options PLUS100 THR CHAPTER 6: OPTIONS TELENET MONITORING/SUPERVISION SYSTEM To insert the board in a TeleNET network, refer to the layout below. To configure the instrument, refer to the TeleNET manual. IMPORTANT: During configuration, select "Instrument PLUS 100 THR rel. 8 or higher"...
CHAPTER 7: DIAGNOSTIC DIAGNOSTIC In the event of a fault the PLUS100 THR controller warns the operator by displaying an alarm code and emitting a warning sound via the buzzer inside the control console. If alarm conditions arise, the display will show one of the following messages:...
THIS DECLARATION OF CONFORMITY IS ISSUED UNDER THE EXCLUSIVE RESPONSIBILITY OF THE MANUFACTURER: PEGO S.r.l. Via Piacentina 6/b, 45030 Occhiobello (RO) – Italy – Società soggetta all’attività di direzione e coordinamento di Castel S.r.l. DENOMINAZIONE DEL PRODOTTO IN OGGETTO / DENOMINATION OF THE PRODUCT IN OBJECT MOD.:...
Page 34
PLUS100 THR NOTES USE AND MAINTENANCE MANUAL Page 34 Rel. 01-22...
Page 35
Allegati PLUS100 THR USE AND MAINTENANCE MANUAL Rel. 01-22 Page 35...
Page 36
Tel. +39 0425 762906 e-mail: info@pego.it – www.pego.it AFTER-SALES ASSISTANCE SERVICE Tel. +39 0425 762906 e-mail: tecnico@pego.it Distributor: USE AND MAINTENANCE MANUAL Page 36 Rel. 01-22 PEGO s.r.l. reserves the right to make amendments to this user manual at any moment.
Need help?