WATER LEVEL CONTROLLER
WLC 22
FEATURES
Trip Relay Indication
High & Low Level Indication Led
Compact & sleek design
Sensitivity Adjustable : 1K to 200K ohm
Pump protection from Dry run & Overflow
condition
Used for drain & fill control
Technical Specification
Model
WLC 22
Power Supply
100 - 270V AC,50/60 Hz,7VA
3 nos. prods
S1 : Common
Input Sensor
S2 : Low
S3 : High
LED 1 : Relay
Indications
LED 2 : High Level
LED 3 : Low Level
LED 4 : Mains
Sensitivity
1 to 200 Kilo ohms
Reset
Auto
Trip Delay
0.5 sec (Approx.)
Output
1 Relay,1C/O (NO-C-NC)
Output Rating
10Amp,230V AC
Dimension
90 x 22.5 x 67.5
Mounting
Din Rail Mounting
Mechanical Dimension
22.5
66.35
Terminal Connection
A1 15
Power Supply
(A1 & A2):
16 18
100 to 270V AC
WLC
Smps,
50/60Hz, 7 VA
Sensor Terminal
S1-Common
S1 S2
S2-Low
S3 A2
S3-High
NO
C
NC
Output :
1 Relay 1 C/O ,
18
15
16
5A 230V AC (Res.)
Connection Diagram
S3
S2
S1
Tank
Safety Precaution
!
All safety related codifications, symbols and instructions that
appear in this operating manual or on the equipment must be
strictly followed to ensure the safety of the operating personnel
as well as the instrument.
If all the equipment is not handled in a manner specified by
the manufacturer, it might impair the protection provided by the
equipment.
Read complete instructions prior to installation
and operation of the unit.
WARNING : Risk of electric shock.
Caution
Ensurements of your WLC 22.
1) Ensure the connection as per terminal diagram.
2) To be Handle by only authorized and person.
3) Not installed near any heat sources like burner, electric arc.
4) Installed as near to the starter as possible.
5) The sensor prods are suspended from the top opening of the
water tank in PVC conduct piping. Metal pipes should not be
used.
6) The sensor prods should not be wall mounted on metallic water
tank.
7) Adjust the sensitivity of water resistance given on front plate.
Logic Selection
WLC 22 can be operate either in SUCTION logic or in DELIVERY
logic using output relay contact terminal 15 & 18 (COM-NO),
15 & 16 (COM-NC) respectively.
Funcation Of Suction Logic
When you select SUCTION LOGIC using the relay contact terminals
15 & 18. Put sensor prods S1, S2 & S3 in water tank. The pump
motor will start automatically when the tank is full.
(i.e prod S1, S2 & S3 are under water )
and will stop automatically when the water tank is empty
(i.e prod S2,S3 out of water & S1 under water)
Funcation Of Delivery Logic
When you select DELIVERY LOGIC using the relay contact terminal
15 & 16. Put sensors prods S1, S2 & S3 in water tank. The pump
motor will start automatically when the tank is empty.
(i.e prod S1 is under water S2, S3 are out of water)
and pump motor will stop automatically when the water tank
is full (i.e S1, S2 & S3 are under water).
Sensitivity Setting
Refer below procedure for adjusting sensitivity according to
conductivity of water.
1) Keep all prods in water and set the pot at maximum
position. Now the relay becomes ON.
2) The turns the pot towards the minimum side till the relay
becomes OFF.
3) Now to adjust the pot above setting where the relay
becomes ON and does not chatter.
NOTE :
Position of potentiometer is adjusted according to
conductivity level of water, Do not disturb potentiometer
setting once fixed.
Page 1

Advertisement

loading
Need help?

Need help?

Do you have a question about the WLC 22 and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for MULTISPAN WLC 22

  • Page 1 Pump protection from Dry run & Overflow Logic Selection Smps, 50/60Hz, 7 VA condition WLC 22 can be operate either in SUCTION logic or in DELIVERY Sensor Terminal Used for drain & fill control logic using output relay contact terminal 15 & 18 (COM-NO), S1-Common S1 S2 15 &...
  • Page 2 Two Level Controller Two Level Controller For Both Tank One Level Controller (15-18)- SUCTION LOGIC (15-18)- SUCTION LOGIC (15-16)- DELIVERY LOGIC (15-16)- DELIVERY LOGIC Water Tank Water Tank Suction Tank Delivery Tank SR NO. RELAY OUTPUT SR NO. S1+S3 RELAY OUTPUT MOTOR OUTPUT S1+S3 Specifications are subject to change, since development is a...