TAVLIT TVD Series Operation And Maintenance Manual

Automatic disc filters

Advertisement

Quick Links

Automatic disc filters operation and maintenance manual
TVD and TAD Series
1

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the TVD Series and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for TAVLIT TVD Series

  • Page 1 Automatic disc filters operation and maintenance manual TVD and TAD Series...
  • Page 2: Table Of Contents

    Table of Contents 1. Main filter battery components Pg.3 2. Control tubing scheme Pg.4 3. Manual testing of DP Pg.5 3.1 Pressure meter connections 3.2 Testing controller DP device 4. Manual flushing of filter battery Pg.6 5. Manual activation of flushing cycle (testing DP performance) Pg.8 6.
  • Page 3: Main Filter Battery Components

    Main filters Battery components Filtration Head Flushing controller DP device Solenoid valves Flush valve Flush valve Control loop filter Main components • Filter heads • Flushing controller • Flush valves • DP device • Solenoid valves • Control loop filter...
  • Page 4: Control Tubing Scheme

    Control tubing scheme Filtration Head TAVLIT filtration system Talgil controller connection terminal Control loop filter GEMSOL= Soenoid and Galit Control tube 8 mm Hudraulic control system drain Control tube 8 mm Back flush valves Main components • Filter heads • DP device •...
  • Page 5: Manual Testing Of Dp

    Manual testing of DP -Point handle of the 3 way valve to B and read inlet pressure. -Point handle to A and read outlet pressure. The difference is the head loss (pressure loss) on the filter battery. Pressure Meter connections Pressure meter Filter Battery 3 Way Valve...
  • Page 6: Manual Flushing Of Filter Battery

    Manual flushing of the filter battery Manual flushing is performed one filter after the other. In order to perform manual flushing the user should change position of the Galit (the hydraulic relay connected to the solenoid valve), of the filter to be flushed. The user should manually change position of the Galit to "open"...
  • Page 7 Galit- "Close" position Back flush valve Filter Battery Contol tubes filter Manual Upstream pressure "close"position Galit close up Hydraulic control Galit "Automatic" position Back flush valve Filter Battery Contol tubes filter Upstream Automatic pressure position Galit close up Hydraulic control...
  • Page 8: Manual Activation Of Flushing Cycle (Testing Dp Performance)

    Manual activation of flushing cycle (testing DP performance) In order to create a pressure difference on the filter battery we use a manual valve ") connected to the downstream side of the control tube. Opening it partially to create a pressure difference that activates the DP and the controller preforms a flushing cycle.
  • Page 9: Proper Flushing Of Discs

    Proper flushing of discs It is recommended to clean the discs before and after irrigation season to ensure proper functioning of the filter for many years. Manual flushing is required when the filter is clogged and flushing process does not clean it properly. •...
  • Page 10 For complex deposits • In case the user is not sure about the type of the deposits he should run a test. • Put several discs in Sodium ypocloride solution and seveal in a Hydroclorite Acid solution, (prepare the solution as explained above). •...
  • Page 12: Maintenance Instructions Venturi Devices And Air Release Valves

    Maintenance instructions Venturi devices and Air release valves . Open filter cup and remove discs Separate the two parts of the spine by turning the bayonet screws. turn) (a quarter of a 3. Separate the lower part 4. Disaasembly of the venturi .
  • Page 13 Pressure testing point Air system Air flows through non return valve located at the bottom of the filter Ball push pin Venturi ball valve Ball seal Air entrance cup Non return assembly for inserting air during flushing Maintenanace: in case of leakage from the air entrance, release pressure, open the cup and clean the ball and o-ring.
  • Page 14: End Of Season Maintenanace

    End of season maintenanace • Proper end of season maintenanace will protect the filtration station and enable the system proper functioning the next season after the winter. • Perform a long flush 25-30 minutes to the system with the down stream closed. •...
  • Page 15: Air Release Valve Maintenanace

    Air release valve maintenance In case of leaks the user must disassemble the air release valve, flush all parts thoroughly and reassemble. If the leak continues please check the upper seal and replace if damaged.
  • Page 16: Filtron Controller Manual

    Filtron 1- 10 controller user's manual List of features The “FILTRON 1-10” is a modular backflushing controller for automatic filters of 1 to 10 stations. There exist DC and AC models. The DC model can be powered either by 6v DC or 12v DC and it activates 2 wired 12v DC latching solenoids.
  • Page 17 How to program the controller The controller is equipped with an LCD display and 4 keys as displayed below. When the unit is left untouched for a minute the display is switched off and the only life signal is given by a beep sound that can be heard every 20 seconds.
  • Page 18 The chain of editable fields Following is the chain of editable fields. The existence of the DP SET-POINT field depends on whether the system contains a built-in electronic DP or not. FLUSH DP SET- FLUSH TIME POINT MODE ACCUMULATIONS ACCUMULATIONS ACCUMULATIONS TIME MANUAL...
  • Page 19 OFF - no flushing will take place By time – In this case the flushing cycles will be repeated in a selected interval or will be triggered by the DP signal depending on what happens first. No matter how was the flushing cycle started the interval to the next cycle will start to be measured again after each ending of a flushing sequence.
  • Page 20 Main Valve (sustaining valve) - Yes/ No. When the answer is “Yes” the Pre Dwell delay between the Main Valve opening and the opening of Station No. 1 can be defined. The selectable delay steps are: 5, 10, 15, 20, 25, 30, 35, 40, 45, 50, 55 sec 1, 1.5, 2, 2.5, 3, 3.5, 4, 4.5, 5, 5.5, 6 min the delay between stations –...
  • Page 21 Handling Low pressure When a closed contact indication is received at the low pressure input of the controller, the symbol will start to appear blinking at the display. All activities will stop including the countdown to the next flushing cycle. If the low pressure happened while a flushing sequence was in progress, when the low pressure condition terminates the flushing sequence will start from the beginning rather than continue from the stop point.
  • Page 22 Timing Diagram Without Delay Valve Main valve Flush time Dwell Valve 1 Dwell time Valve 2 Valve 3 Valve 4 Including Delay Valve Main valve Dwell Valve 1 Dwell time Valve 2 Valve 3 Valve 4 Flush time Delay valve Valve Delay...
  • Page 23 Wiring Diagram DC MODEL The drawing below shows the wiring of the DC model of the controller. Notice that: The External DP sensor is optional and it is intended for use in cases there is no Embedded Electronic DP included. The powering of the unit can be either by 6v DC or 12v DC.
  • Page 24 AC MODEL The drawing below shows the wiring of the AC model of the controller. Notice that: The External DP sensor is optional and it is intended for use in cases there is no Embedded Electronic DP included. The powering of the unit is by 24VAC transformed from 220/110 VAC. The solenoids will be of 24VAC Make sure to DISCONNECT the POWER before inserting /...
  • Page 25 TECHNICAL DATA DC MODEL 6v supplied by 4 x 1.5 “D” size alkaline batteries. Power source: or 12v DC dry battery or 12v rechargeable battery with solar panel of 2 watts Outputs : 12v DC latching solenoids. Embedded electronic analog DP sensor or external dry contact DP sensor.
  • Page 26: Maintenance Instructions Flush Valves 3" - Link

    Maintenance instructions Flush valves 3"X3": https://www.bermad.com/wp-content/uploads/2016/05/IR_350- 3x3_Maintenance_IOM_English.pdf Maintenance instructions flush valves 2" x2": https://www.bermad.com/wp-content/uploads/2016/05/IR_350-A- 2x2_Maintenance_IOM_English.pdf...
  • Page 27: Parts List Tvd

    Parts list – TVD Parts list – TAD...
  • Page 28 Parts list TAD...
  • Page 29: Parts List Tadd

    Parts list – TADD...

This manual is also suitable for:

Tad series

Table of Contents