1. HYD‐ES inverter Introduction The HYD‐ES hybrid inverter is used in PV system with battery storage. Energy produced by the PV system will be optimized for maximum self‐consumption. The HYD‐ES inverter can work in auto or time‐of‐use (TOU) mode, charge / discharge the battery when needed. In auto mode, the HYD‐ES inverter will charge surplus PV energy into the battery & discharge battery to supply power to local load when PV energy is not enough. In case of blackout, HYD‐ES inverter can work in Emergency Power Supply (EPS) mode. HYD‐ES inverter will utilize power from PV panels & energy stored in the battery to supply power to critical load. Fig. 1 HYD‐ES inverter schematic diagram 3 / 43 WWW.EVVOSOLAR.COM...
2. Safety Notes Before installation, please make sure you read & understand this manual. The HYD‐ES inverter strictly comply with safety rules of design and testing. During the installation, operation and maintenance, operators should abide by local safety regulations. Improper operation may cause an electric shock or damage the equipment and properties. 2.1. Safety Notes Electrical installation and maintenance must be carried out by competent electricians according to local regulations. HYD‐ES inverter can only be installed by qualified electrician, and only those who have appropriate accreditation, as required by local authority. Do NOT put explosives or flammable materials, e.g. gasoline, kerosene, diesel, oil, wood slab, cotton, or rag close to batteries or HYD‐ES inverter. Disconnect AC connection first, then disconnect battery & PV(PV1&PV2), then wait at least 5 minutes (discharge capacitors) before maintenance to prevent electric shock. HYD‐ES inverter shall be disconnected completely (BAT, PV & AC) while being maintained. HYD‐ES inverter can be very hot during working. Switch off HYD‐ES inverter & wait HYD‐ES inverter to cool down before maintenance. Keep children away from batteries & HYD‐ES inverter. ...
Battery maintenance operators shall have the knowledge and technical skill for battery maintenance; All batteries connected in parallel should be of the same model and have same firmware version. This is a design issue needs to be considered by designer/installer, particularly when replacing batteries or modifying an existing energy storage system. HYD‐ES inverter is transformer‐less, therefore the positive pole and negative pole of the PV array are NOT grounded. Otherwise it will cause inverter failure. In the PV system, all non‐current carrying metal parts (such as: PV module frame, PV rack, combiner box enclosure, inverter enclosure) should be connected to earth. Warning: Do not disassemble or break the battery. Its electrolyte can be toxic and damage your skin and eyes. Warning: follow the following rules during battery installation/maintenance. a) Take off your watch, ring, and other metal objects. b) Only use tools with insulated handles. c) Wear rubber gloves and shoes. d) Do not put tools or metals above the battery. e) Switch off HYD‐ES inverter & batteries before connecting / disconnecting battery terminals. f) Battery positive/negative poles should be isolated from ground. ...
Page 6
Earth terminal. Please read this manual before installing HYD‐ES inverter. This indicates the degree of protection of the equipment according to IEC standard 70‐1 (EN 60529 June 1997). Positive pole and negative pole of the DC voltage (PV & Battery). This side up, HYD‐ES inverter must always be transported, handled and stored in such a way that the arrows always point upwards. 6 / 43 WWW.EVVOSOLAR.COM...
3. Installation 3.1. Product Overview HYD‐ES inverter is 100% strictly inspected before package and delivery. It is forbidden to put the HYD‐ES inverter upside down during delivery. CAUTION Please check the product package and fittings carefully before installation. Fig. 2 HYD‐ES inverter overview 1 DC switch 6 Current transformer port 2 Battery input terminals 7 Load connection port 3 PV input terminals Grid connection port ...
3.4. Installation Tools The following tools shall be prepared before installation: No. Tool Model Function Hammer drill 1 Used to drill holes on the wall Recommend drill dia.6mm 2 Screwdriver wiring 3 Wire stripper Strip wire Turn the screw to connect rear panel 4 4mm Allen Key with inverter 5 Crimping tools Used to crimp power cables 6 Multi‐meter Used to check grounding 7 Marker pen Used to mark signs 8 Measuring tape Used to measure distances ...
11 Safety goggles Operators wear 12 Anti‐dust respirator Operators wear 3.5. Installation Position HYD‐ES inverter should be vertically mounted (to ensure fast heat dissipation), please choose a position without direct sunlight / snow accumulation to install HYD‐ES inverter. Please the installation position is well‐ventilated. Fig. 4 Installation Position of HYD‐ES inverter 10 / 43 WWW.EVVOSOLAR.COM...
3.6. Mount HYD‐ES inverter Step 1: Put the mounting bracket properly on the wall, mark these 8 drill holes using a marker pen. Drill 8 holes (drill bit 6mm) on the wall. Step 2: Insert the expansion screw vertically into the hole, note the insertion depth. (not too shallow or too deep) Step 3: Fix the mounting bracket on the wall using bolts & flat washers. Step 4: Put HYD‐ES inverter on the mounting bracket. Step 5: Earth HYD‐ES inverter using the grounding hole on the heat sink. Step 6: OPTIONAL: you can lock HYD‐ES inverter to the mounting bracket. Step 5 Step 6 11 / 43 WWW.EVVOSOLAR.COM...
4. Electrical Connection CAUTION High voltages in power conversion circuits. Lethal hazard of electric shock or serious burns. All work on the PV modules, inverters, and battery systems must be carried out by qualified personnel only. Wear rubber gloves and protective clothing (protective glasses and boots) when working on high voltage/high current systems such as INVERTER and battery systems. CAUTION HYD‐ES inverter is intended to be used in PV system with battery storage. If not used as intended, the protection provided by the equipment may be impaired. Fig. 5 Electrical connections 12 / 43 WWW.EVVOSOLAR.COM...
4.1. Battery Connection Fig. 6 Battery connection (Measure battery wires polarity/voltage before connection) Step 1: Loosen 4 screws (A) using a screwdriver (Fig. 6); Step 2: Remove the waterproof cover (B), loosen the cable gland (C), and then remove the stopper (G); Step 3: Route the battery wires (F) through the cable gland, then connect battery wires using OT terminal (E); tep 4: Fasten the waterproof cover using 4 screws. 4.2. PV Connection Recommended DC input cable specifications Cross‐Sectional Area (mm External Cable Diameter(mm ) Range Recommended Value 4.0~6.0 4.5~7.8 Procedure : Step 1 Prepare PV positive and negative power cables 1. Positive metal contact 2. Negative metal contact Fig. 7 prepare PV positive and negative power cables 13 / 43 WWW.EVVOSOLAR.COM...
Page 14
Step 2 Insert crimped PV positive and negative power cables into corresponding PV connectors 3. Positive connector 4. Negative connector Fig. 8 prepare PV positive and negative connectors Step 3 Make sure the DC voltage of each PV string is less than 600V DC and polarities of PV power cables are correct. Insert the positive and negative connectors into HYD‐ES inverter until you hear a "click" sound, as shown in Fig. 9. 1. Bayonet Fig. 9 Connect PV connectors CAUTION Before removing the PV positive and negative connectors, ensure that the DC SWITCH is OFF. Follow-up Procedure Use a MC4 wrench to disconnect PV connectors, as shown in Fig. 10. Fig. 10 Disconnect PV connectors 14 / 43 WWW.EVVOSOLAR.COM...
4.3. CT / CAN / RS485 / NTC connection CT (Current transformer) can measure the value and direction of AC current. Refer to Fig. 11 for the correct connection of CTa. Fig. 11 CTa connection Step 1: Refer to Fig. 11 for correct position of CTa. Wrap the CT around L wire of incoming mains, make sure that the CT arrow direction is “home → grid”. Step 2: You can use network cable & terminal caps to extend CT wires if necessary, the maximum CT cable length is 200m. CT wire Extension cable (network cable) HYD‐ES inverter Red Orange / white orange / brown / white brown CT+ Black Green / white green / blue / white blue CT‐ 15 / 43 WWW.EVVOSOLAR.COM...
Page 16
Fig. 12 CT / CAN / RS485 / NTC connection Step 3: Loosen 4 screws (part A) using a screwdriver (Fig. 12) Step 4: Remove the waterproof cover (part B), loosen the cable gland (part C), then remove the stopper (part G) Step 5: Route CT cable through the cable gland, connect CT cable to CT terminal, then insert CT terminal into corresponding ports. Step 6: One communication cable (between battery BMS & HYD‐ES inverter) is provided in the HYD‐ES inverter accessory bag. One inverter end, one BAT end. ...
4.5. Critical Load Connection (EPS function) Critical load: in case of grid outage, if EPS function is enabled, HYD‐ES inverter will work in EPS (Emergency Power Supply) mode, utilize the PV power & energy stored in the battery to supply power to critical load via LOAD connection port. LOAD connection port is only for critical load connection. The power of critical loads must be less than 3000VA. The connection procedure of LOAD port is the same as grid connection (Fig. 14). Change-over positions CAUTION The changeover switch is necessary. While checking/repairing critical load, make sure change‐over switch is at position 0. While checking/repairing HYD‐ES inverter, make sure change‐over switch is at position 0 & HYD‐ES inverter is disconnected from grid. Under normal conditions: change‐over switch is at position 1. HYD‐ES inverter can supply power to critical load in case of blackout. If the HYD‐ES inverter is faulty, manually change the switch to position 2. Grid will supply power to critical load. Fig. 15 Change‐over Switch connections 18 / 43 WWW.EVVOSOLAR.COM...
5. Buttons and indicator lights Fig 16. Buttons and indicator lights 5.1. Buttons: press “Back” to the previous screen or enter the main interface; press “Up” to the upper menu option or value plus 1; press “Down” to the lower menu option or value minus 1; Press “OK” to select the current menu option or switch to the next digit. 5.2. Indicator lights and status of HYD‐ES inverter On Grid Off‐Grid Alarm Status of HYD inverter Green light Green light Red light On‐grid Standby (On‐Grid) Flashing Off‐Grid ON Standby (Off‐Grid) Flashing ...
6. Operation 6.1. Double Check Please double check the following before operation. HYD‐ES inverter is firmly fastened to the mounting bracket on the wall; PV+/PV‐ wires are firmly connected, polarity and voltage are correct; BAT+/BAT‐ wires are firmly connected, polarity and voltage are correct; DC isolator is correctly connected between battery & HYD‐ES inverter, DC isolator: OFF; GRID / LOAD cables are firmly / correctly connected; AC circuit breaker is correctly connected between HYD‐ES inverter GRID port & GRID, circuit breaker: OFF; AC circuit breaker is correctly connected between HYD‐ES inverter LOAD port & critical load, circuit breaker: OFF; For lithium battery, please ensure that the communication cable has been correctly connected; For the lead‐acid battery, please ensure that the NTC wire has been correctly connected. 6.2. First Time Setup (IMPORTANT!) IMPORTANT: PLEASE FOLLOW THE FOLLOWING PROCEDURE to switch ON HYD‐ES inverter Make sure there’s no power generation in HYD‐ES inverter’s phase. Turn ON DC switch. Switch ON the battery. Turn ON DC isolator between battery & HYD‐ES inverter. Turn ON AC circuit breaker between the HYD‐ES inverter GRID port & GRID. Turn ON AC circuit breaker between the HYD‐ES inverter LOAD port & critical load. HYD‐ES inverter should start to operate now. You need to set the following parameters before HYD‐ES inverter starts to operate. 1)Set system time 8)*Set min discharge voltage 2)Set country 9)*Set max discharge current 3)Select battery type 10)*Set min protect voltage 4)*Set battery capacity 11)*Set discharge depth 5)*Set max charge voltage 12)*Set empty discharge voltage 6)*Set max charge current 13)*Set full charge voltage 7)*Set max protect voltage ...
Page 21
CAUTION It’s very important to make sure that you have selected the correct country code according to requirements of local authority. Please consult qualified electrical engineer or personnel from electrical safety authorities about this. EVVO SOLAR is not responsible for any consequences arising out of incorrect country code selection. 3)Select battery type Press “Up” or “Down” to select your battery type, then press “Ok” to complete the battery type setting. If you’re using “1. PYLON”, “2. DARFON”, “4. General Lithium”, “5. Alpha. ESS” or “6. SOLTARO” battery types, congratulations, inverter’s first‐time setup is complete. Please press “OK” to enter the main interface. ...
Page 22
Note: Please confirm with representative of PYLONTECH that your battery is compatible with HYD3000/4000/5000/6000‐ES 2. DARFON DARFON 14S31P ESS 3.DEFAULT LEAD ACID / LEAD CRYSTAL / AQUION battery 4. General Lithium All batteries that comply with EVVO’S BMS CAN communication protocol. 5. Alpha. ESS M48112‐P / SMILE‐BAT 6. SOLTARO SL‐3KWH / SL‐1KWH 4)*Set battery capacity (only for DEFAULT battery type) Press “Up” or “Down” to change the 1 digit, press “OK” to switch to next digit. After changing the battery capacity per your battery specification, press “Ok”, then “Set max charge voltage” will pop up. 5)*Set max charge voltage (only for DEFAULT battery type) Press “Up” or “Down” to change the 1 digit, press “OK” to switch to next digit. After changing max charge voltage per your battery specification, press “Ok”, then “Set max charge current” will pop up. 6)*Set max charge current (only for DEFAULT battery type) Press “Up” or “Down” to change the 1 digit, press “OK” to switch to next digit. After changing the max charge current per your battery specification, press “Ok”, then “Set max protect voltage” will pop up. 7)*Set max protect voltage (only for DEFAULT battery type) Press “Up” or “Down” to change the 1 digit, press “OK” to switch to next digit. After changing the max protect voltage per your battery specification, press “Ok”, then “Set min discharge voltage” will pop up. 8)*Set min discharge voltage (only for DEFAULT battery type) Press “Up” or “Down” to change the 1 digit, press “OK” to switch to next digit. After changing the min discharge voltage per your battery specification, press “Ok”, then “Set max discharge current” will pop up. 9)*Set max discharge current (only for DEFAULT battery type) Press “Up” or “Down” to change the 1 digit, press “OK” to switch to next digit. After changing the max discharge current per your battery specification, press “Ok”, then “Set min protect voltage” will pop up. 10)*Set min protect voltage (only for DEFAULT battery type) Press “Up” or “Down” to change the 1 digit, press “OK” to switch to next digit. After changing the min protect voltage ...
Press “Up” or “Down” to change the 1 digit, press “OK” to switch to next digit. After changing the empty discharge voltage per your battery specification, press “Ok”, then “Set full charge voltage” will pop up. 13)*Set full charge voltage (only for DEFAULT battery type) Press “Up” or “Down” to change the 1 digit, press “OK” to switch to next digit. After changing the full charge voltage per your battery specification, press “Ok”. Congratulations, HYD3000/4000/5000/6000‐ES’s first‐time setup is complete. Please press “OK” to enter the main interface. 6.3. Commissioning The main interface: Fig 17. Main interface If you didn’t change the work mode of HYD‐ES inverter, which means HYD‐ES inverter is working in “Auto Mode”: While “PV Production” > “Home Consumption” If the battery is not full. HYD‐ES inverter will charge the battery. While “PV Production” < “Home Consumption” If the battery is not flat. HYD‐ES inverter will discharge the battery. 6.4. Menu In the main interface, press “Down” button to enter grid/battery parameters page: Main Interface Press “Down” 1.Grid(V) 2.AC Current(A) 3.Frequency 23 / 43 WWW.EVVOSOLAR.COM...
4.Batt(V) 5.Batt Chrg Curr. 6.Batt DisChrg Curr. 7.State of Charge 8.Batt Cycles 9.Batt Temp. In the main interface, press “UP” button to enter PV parameters page: Main Interface Press “UP” 1.PV1 Voltage 2.PV1 Current 3.PV1 Power 4.PV2 Voltage 5.PV2 Current 6.PV2 Power 7.Inverter Temp. In the main interface, press “back” button to enter main menu. The main menu has the following five options: Main Interface Press “Back” 1.Basic Setting 2.Advanced Setting “Up” ↑ 3.Event List 4.System Information “Down”↓ 5.Energy Statistic 6.Software Update 6.4.1. Basic setting 1.Basic Setting Press “OK”...
Page 25
5.EPS Mode 6.Communication Addr. “Down”↓ 7.Auto Test 1. Set Language Select “1. Language”, press “OK”. Press “up” or “down” to select the language and press “OK”. Easier Way: press “Back” & “OK” at the same time to change system language. 2. Set Time Select “2. Time”, press “OK” to enter time setting interface, system time format is 20YY‐MM‐DD HH:MM:SS Press “Up” or “Down” to change the 1 digit, press “OK” to switch to next digit, after inputting the current time, press “OK”. 3. Energy Storage Mode Select “3. Energy Storage Mode”, press “OK” to enter energy storage mode setting interface. 3.Energy Storage mode 1. Self‐use Mode “Up” ↑ 2. Time‐of‐use Mode 3.Timing Mode “Down”↓ 4. Passive Mode 1) Set Auto Mode Select “1. Set Auto Mode”, then press “OK”. In auto mode, HYD‐ES inverter will automatically charge & discharge the battery. If PV generation = LOAD consumption ( Δ...
Page 26
If the battery is full(or already at Max Charge Power), If PV generation < LOAD consumption, it will excess power will be exported to the grid. discharge the battery to supply power to load. If PV generation + Battery < LOAD consumption, HYD‐ Press “DOWN” button to view current grid/battery ES inverter will import power from the grid. parameters, press “UP” to get back to main interface. 2) Set Time‐of‐use Mode Select “2. Set Time‐of‐use Mode”, and then press “OK” to enter Set Time‐of‐use mode interface. Set Time‐of‐use Mode Rules. 0: Enabled From To SOC Charge 02h00m ‐ 04h00m 070% 1000W Effective date Dec. 22 ‐ Mar. 21 Weekday select Mon. Tue. Wed. Thu. Fri. Sat. Sun. If electricity is more expensive in high demand time (peak rate) & electricity is much cheaper in low demand time (off‐...
Page 27
3) Set Timing Mode Select “3. Set Timing Mode”, and then press “OK” to enter Set Timing mode interface. The interface of Set Timing Mode is shown as below. You can select a charge time/power & discharge time/power in this mode. Charge Start 22 h 00 m Charge End 05 h 00 m Charge Power 2000 W Note: normally this mode is used to test whether HYD‐ES inverter can charge & discharge correctly or not. So basically, this mode is DisCharge Start 14 h 00m used for testing purposes only. DisCharge End 16 h 00m DisCharge Power 2500 W 4) Set Passive Mode Select “4. Set Passive Mode”, and then press “OK”. For more detailed information, please ask representative of EVVO to get a copy of passive mode communication protocol. 4. PV Input Mode PV input mode selection: HYD‐ES inverter has 2 MPPT channels. The 2 MPPT can operate independently, also can operate in parallel. If the PV strings are connected in parallel outside the inverter, you should choose the “in parallel mode”, otherwise use the default setting (independent mode). 5. EPS Mode 1.Enable EPS Mode 1.EPS Mode Control 2.Disable EPS Mode 5. Set EPS Mode ***S() 2.Set EPS Changeover Time(default 20ms) ...
Page 28
If PV generation > LOAD consumption ( Δ P > 100W), If PV generation = LOAD consumption, HYD‐ES inverter wont’ charge or discharge battery. HYD‐ES inverter will charge battery. 4) If PV generation is normal,but LOAD consumption=0, If PV generation < LOAD consumption ( Δ P > 100W), the surplus power will be stored in the battery. HYD‐ES inverter will discharge battery. 6. Communication Addr. Select “6. Set Communication Addr.”, press “OK”. Press “Up” or “Down” to change the 1 digit, press “OK” to switch to next digit, after changing the 485‐communication address (default :01), press “OK”. 7. Auto Test (ONLY for Italian Market) Select “7. Auto Test”, press “OK” to enter autotest interface. 7.Auto Test 1.Autotest Fast 2.Autotest STD “Up” ↑ 3.QF Time Setting 4.QV Time Setting “Down”↓ 5.Control 81.S1 28 / 43 ...
Page 29
1) Autotest Fast Select “1. Autotest Fast”, then press “OK” to start Auto test Fast. Start Autotest ↓ Press “Ok” to start Testing 59.S1... ↓ Wait Test 59.S1 OK! ↓ Wait Testing 59.S2... ↓ Wait Test 59.S2 OK! ↓ Wait Testing 27.S1... ↓ Wait Test 27.S1 OK! ↓ Wait Testing 27.S2... ↓ Wait Test 27.S2 OK! ↓ Wait Testing 81>S1... ↓ Wait Test 81>S1 OK! ↓ Wait Testing 81>S2… ↓ Wait Test 81>S2 OK! ...
Page 30
27.S1 threshold 195.5V 400ms ↓ Press “Down” 27.S1: 228V 408ms ↓ Press “Down” 27.S2 threshold 92V 200ms ↓ Press “Down” 27.S2: 227V 205ms ↓ Press “Down” 81>.S1 threshold 50.5Hz 100ms ↓ Press “Down” 81>.S1 49.9Hz 103ms ↓ Press “Down” 81>.S2 threshold 51.5Hz 100ms ↓ Press “Down” 81>.S2 49.9Hz 107ms ↓ Press “Down” 81<.S1 threshold 49.5Hz 100ms ↓ Press “Down” 81<.S1 50.0Hz 105ms ↓ Press “Down” 81<.S2 threshold 47.5Hz 100ms ↓ Press “Down” 81<.S2 50.1Hz 107ms 2) Autotest STD Select “2. Autotest STD”, then press “OK” to start Auto test STD. The test procedure is same as Autotest Fast, but it’s much more time consuming. ...
6.4.2. Advanced setting 2.Advanced Setting Input Password 0001 1.Battery Parameter 2.Clear Energy Data 3.Clear Events Up” ↑ 4.Country 5.Anti Reflux “Down”↓ 6.IV Curve Scan 7.Battery Active 8.DRMs0 Control 9.Safety Param. Select “2. Advanced Setting” and press “OK”, “input password” is shown. Input the password ”0001”, press “Up” or “Down” to change the 1 digit, press “OK” to switch to next digit, when “0001” is shown on the screen, press “OK” to enter “2. Advanced Setting” interface. If “Incorrect, Try Again!” is shown on the screen, press “Back” and input the password again. 1. Battery Parameter 1.Battery Parameter 1)Battery Type 7)Max Discharge (A) 2)*Battery Capacity 8)*Low (V) Protection “Up” ↑ 3)Discharge Depth 9)*Min Discharge (V) 4)Max Charge (A) 10)*Empty Discharged (V) “Down”↓ ...
Page 32
EPS Discharge Depth per battery specification. Press “OK”. For example: if Discharge Depth = 50% & EPS Discharge Depth = 80%. While grid is connected: HYD‐ES inverter won’t discharge the battery when its SOC is less than 50%. In case of blackout: HYD‐ES inverter will work in EPS mode (if EPS mode is enabled) & keep discharging the battery till battery SOC is less than 20%. 4) Max. Charge (A) Select “4. Max. Charge (A)” and press “OK”. Press “up” or “down” to change the 1 digit, press “ok” to switch to next digit. Input the value of Max. Charge (A) per battery specification. Press “OK”. 5) *Over (V) Protection (only for DEFAULT battery type) Select “5. Over (V) Protection” and press “OK. Press “up” or “down” to change the 1 digit, press “ok” to switch to next digit. Input the value of Over (V) Protection per battery specification. Press “OK”. 6) *Max. Charge (V) (only for DEFAULT battery type) Select “6. Max. Charge (V)” and press “OK”. Press “up” or “down” to change the 1st digit, press “ok” to switch to next digit. Input the value of Max. Charge (V) per battery specification. Press “OK”. 7) Max. Discharge (A) Select “7. Max. Discharge (A)” and press “OK”. Press “up” or “down” to change the 1 digit, press “ok” to switch to next digit. Input the value of Max. Discharge (A) per battery specification. Press “OK”. 8) *Low (V) Protection (only for DEFAULT battery type) Select “8. Low (V) Protection” and press “OK”. Press “up” or “down” to change the 1 digit, press “ok” to switch to next digit. Input the value of Low (V) Protection per battery specification. Press “OK”. 9) *Min. Discharge (V) (only for DEFAULT battery type) Select “9. Min. Discharge (V)” and press “OK”. Press “up” or “down” to change the 1 digit, press “ok” to switch to next digit. Input the value of Min. Discharge (V) per battery specification. Press “OK”. 10) * Empty Discharged (V) (only for DEFAULT battery type) Select “10. Empty Discharged (V)” and press “OK”. Press “up” or “down” to change the 1 digit, press “ok” to switch to next digit. Input the value of Empty Discharged Voltage per battery specification. Press “OK”. 11) * Full Charged (V) (only for DEFAULT battery type) ...
Page 33
Select “4. Country”, press “OK”, current country setting is shown, input new country code & press “OK” 5. Anti Reflux 5.Anti Reflux Control 1.Anti Reflux Control Enable “Up” ↑ Disable 2.Reflux Power “Down”↓ ***KW The user can enable “Anti Reflux Control” to limit the max export power to grid. Select “2. Reflux Power” to input desired max export power to grid. 6. IV Curve Scan 6.IV Curve Scan 1.Scan Control Enable “Up” ↑ Disable 2.Scan Period ***min “Down”↓ 3.Force Scan The user can enable “IV Curve Scan” (MPPT scan) to make HYD‐ES inverter to find the global max power point periodically to deliver max power from a partially shaded PV array. ...
Select “9. Safety Param.”, press “OK”, press “up” or “down” to select “1. Set START Parameters”, “2. Set Safety Voltage”, “3. Set Safety Frequency” or “4.Set Insulation”, then press “OK”. Please contact EVVO technical support for more information. 6.4.3. Event List 3.Event List 1.Current Event List “Up” ↑ 2.History Event List “D ”↓ Event list of HYD‐ES inverter, including current event list and history event list. 1) Current Event List Select “1. Current Event List”, press “OK” to check the current events. 2) History Event List Select “2. History Event List”, press “OK” to check the historical events. Press “up” or “down” to check all historical events if there’re more than 1 page of events. 6.4.4. System information interface 4.System Information 1.Inverter Info Inverter Info (1) Product SN Software Version Hardware Version Power Level Inverter Info(2) Country ...
Discharge ***KWH Charge ***KWH Discharge ***KWH Select “5. Energy Statistic”, press “OK” to enter Energy Statistic interface, it shows the energy generation and consumption within a certain range of time. Press “Up” or “Down” to check the daily / weekly / monthly / yearly / lifetime energy statistics. 6.4.6. Software upgrade Copy the firmware folder to the root directory of SD card. Select “6. Software Update”, press “OK”, “input password” is shown. Input the password (”0715”), press “Up” or “Down” to change the 1 digit, press “OK” to switch to next digit, when “0715” is shown on the screen, press “OK”. ...
7. Technical Data Model HYD 3000-ES HYD 3600-ES HYD 4000-ES HYD 5000-ES HYD 6000-ES Battery Parameters Battery Type Lead‐acid, Lithium‐ion Nominal battery voltage 48V Battery voltage range 42 ‐ 58V Lithium:(according to BMS), General 46.0V Min discharge voltage Lead acid: 44.0V Lithium‐ion:(according to BMS), Max 58V Max charge voltage Lead acid: 58V Recommended battery capacity 200Ah (100 – 500 Ah optional) Recommended storage capacity 9.6 kWh Max charge current Charge current range 0 – 65A programmable Charge curve 3 ‐ stage adaptive with maintenance Max discharge current 0 – 70A programmable Battery protection Over voltage protection / Over current protection / Over temperature protection Depth of discharge Lithium: 0 – 80% DOD adjustable Lead acid: 0 – 50% DOD adjustable PV parameters ...
Page 38
Max output power 3000W 3680W 4000W 5000W 6000W Max output current 13.7A 16A 18.2A 22.8A 27.3A Output current protection(Ipeak) 29.2A 33.6A 33.6A 47.1A 54.5A Nominal grid voltage & frequency 220V,230V,240V, 44 – 55Hz or 54 – 66Hz AC voltage range 180 – 276V (according to local authority requirements) THD <3% Power factor 1default (+ / ‐ 0.8 adjustable) Inrush current 0.8A / 1us Max output fault current 100A / 1us System parameters Max efficiency Charge: 94.1% / discharge 94.3% Standby losses < 5W (PV SPS) Topology High frequency isolation(for bat) ...
If yes, please check the AC circuit breaker and AC wiring of the HYD‐ES inverter. If the grid voltage/frequency is NOT within the acceptable range and AC wiring is correct, but the ID03 GridOFP The grid frequency is too high alarm occurs repeatedly, contact EVVO technical support to change the grid over‐voltage, under‐ voltage, over‐frequency, under‐frequency protection points after obtaining approval from the ID04 GridUFP ...
Page 40
OFF HYD‐ES inverter, wait for 5 minutes, protection then switch ON HYD‐ES inverter. Check whether the The grid current is too high problem is solved. ID15 HwAcOCP and has triggered hardware If no, please contact EVVO technical support. protection Check the PV input mode (parallel mode/ ID16 IpvUnbalance Input current is not balanced independent mode) setting of HYD‐ES inverter. If it’s ...
Page 41
OFF HYD‐ES inverter, wait for 5 minutes, consistent then switch ON HYD‐ES inverter. Check whether the The grid frequency sampling problem is solved. value between the master ID50 ConsistentFault_Fgrid If no, please contact EVVO technical support. DSP and slave DSP is not consistent The Dci sampling value ID51 ConsistentFault_DCI between the master DSP and slave DSP is not consistent Make sure the battery you’re using is compatible ...
Page 42
ID70‐ID73 are internal faults of HYD‐ES inverter, ID70 unrecoverOCPInstant and has cause unrecoverable switch OFF HYD‐ES inverter, wait for 5 minutes, fault then switch ON HYD‐ES inverter. Check whether the The input current is too high, problem is solved. ID73 UnrecoverIPVInstant and has triggered If no, please contact EVVO technical support. unrecoverable fault Check the PV input mode (parallel mode/ UnrecoverPvConfigSet ID74 Incorrect input mode independent mode) setting of HYD‐ES inverter. If it’s Wrong incorrect, change the PV input mode. Unrecoverable EEPROM ID75 ...
Page 43
ID85 is present. ID85 or Or this is an indication of low battery voltage. HYD‐ Battery voltage is low ES inverter won’t discharge battery in this case to ensure long battery cycle life. Software version is Contact EVVO technical support to ID94 not consistent upgrade software. ID95‐ID96 are internal faults of HYD‐ES inverter, The Communication board ID95 CommEEPROMFault switch OFF HYD‐ES inverter, wait for 5 minutes, ...