(including EVVO 3000TLG2 , EVVO 3600TLG2 , EVVO 4000TLG2 , EVVO 4600TLG2 , EVVO 5000TLG2 , software, etc.), and no reproduction or distribution of it in any form or by any means. All EVVO 6000TLG2 rights reserved.
This unit, can install this inverter. EVOLVE ENERGY GROUP CO., LIMITED does not take It’s forbidden to remove the tamper evident label, or open the inverter. any responsibility for the property destruction and personal injury because of any incorrect Otherwise EVVO will not provide warranty or maintenance! use. Note...
Caution, hot surface. Comply with the Conformite European (CE) certification. Grounding point. Please read the user manual before installing the EVVO Inverter 1.2 Symbols and Signs Safety symbols This indicates the degree of protection of the equipment according to IEC standard 70-1 (EN 60529 June 1997).
2.1 Product dimensions Field of use EVVO 3000TLG2~EVVO 6000TLG2 is a Dual MPPT grid-tied PV inverter which converts the DC power generated by PV arrays into sine wave single-phase AC power and feeds it to the public electrical grid, AC circuit breaker (refer to Section 4.4) and DC switch used as disconnect device, and the disconnect device shall be easily accessible.
EVVO 3000TLG2~ 1 pcs EVVO 6000TLG2 Chapter Outline Rear panel 1 pcs This chapter explains how to install the EVVO 3000TLG2~EVVO 6000TLG2 inverter. Installation Notes PV+ input terminal 2 pcs Do NOT install the inverter on flammable material. PV-input terminal...
EVVO 3000TLG2~EVVO 6000TLG2 EVVO 3000TLG2~EVVO 6000TLG2 Tool Model Function Description Quantity Pictures Multi-meter Used to check grounding AC output terminal 1PCS Marker Used to mark signs 485 terminal (2pin) 1PCS Measuring tape Used to measure distances Level Used to ensure that the rear panel is properly installed 0-180º...
EVVO 3000TLG2~EVVO 6000TLG2 inverter Installation of multiple EVVO 3000TLG2~EVVO 6000TLG2 inverters Step 2 Lift the EVVO 3000TLG2~EVVO 6000TLG2 from the packing case and move it to the installation position. To prevent device damage and personal injury, keep balance when moving the inverter because the inverter is heavy.
4.6KVA and max output of PV system is 13.8KVA. rear panel to ensure safety. EVVO 3000TLG2~EVVO 6000TLG2 has 2 MPP trackers, all PV modules Step 5 You can secure the inverter to the rear panel and protect it from stealing by...
EVVO 3000TLG2~EVVO 6000TLG2 EVVO 3000TLG2~EVVO 6000TLG2 4.2 Connecting PGND Cables Figure4-4 Ground terminal composition Connect the inverter to the grounding electrode using protection ground (PGND) cables for grounding purposes. The inverter is transformer-less, not required the positive pole and negative pole of the PV array are NOT grounded.
Step 6 Reinstall cable glands on positive and negative connectors and rotate them against the insulation covers. Connect the EVVO 3000TLG2~EVVO 6000TLG2 to the AC power distribution frame (PDF) or Step 7 Insert the positive and negative connectors into corresponding DC input terminals of power grid using AC output power cables.
Page 14
EVVO 3000TLG2~EVVO 6000TLG2 EVVO 3000TLG2~EVVO 6000TLG2 AC wire connections procedure: Table4-2 Recommended AC output cable specifications Step 1 Select appropriate cables according to Table 4-2, Remove the insulation layer of the AC EVVO EVVO EVVO EVVO EVVO EVVO output cable using a wire stripper according to the figure shown below: A: 30~50mm B:...
EVVO 3000TLG2~EVVO 6000TLG2 EVVO 3000TLG2~EVVO 6000TLG2 Step 4 Secure the locking cable gland clockwise, shown as below: make sure that all the wires Step 2 Unlock the waterproof cable gland, remove the stopper in the waterproof connector; are securely connected;...
EVVO 3000TLG2~EVVO 6000TLG2 EVVO 3000TLG2~EVVO 6000TLG2 Figure 4-27 4.6 Communication method EVVO 3000TLG2~EVVO 6000TLG2 gird-connected inverters offer RS485 (standard) and Wi-Fi (optional) communication modes: Radio ripple Publlc Grid control receiver A. Communication between one inverter and one PC: 1. RS485 Refer to the figure shown below, connect the TX+ and TX- of the inverter to the TX+ and TX- of the RS485→...
EVVO 3000TLG2~EVVO 6000TLG2 EVVO 3000TLG2~EVVO 6000TLG2 Commissioning of inverter Operation interface 5.1 Safety inspection before commissioning Outlines of this chapter This section introduces the display, operation, buttons and LED indicator lights of EVVO 3000TLG2~EVVO 6000TLG2 Inverter. Ensure that DC and AC voltages are within the acceptable range of the inverter.
EVVO 3000TLG2~EVVO 6000TLG2 EVVO 3000TLG2~EVVO 6000TLG2 6.2 Standard Interface When power-on, LCD interface displays INITIALIZING, refer below picture. Initializing… when control board successfully connected with communication board, the LCD display the current state of the inverter display as shown in the figure below.
EVVO 3000TLG2~EVVO 6000TLG2 EVVO 3000TLG2~EVVO 6000TLG2 Inverter states includes: wait、check、normal、fault and permanent Wait : Inverter is waiting to Check State at the end of reconnection time. In this state, grid 1.Enter Setting voltage value is between the max and min limits and so on; If not, Inverter will go to Fault State or Permanent State.
Page 21
EVVO 3000TLG2~EVVO 6000TLG2 EVVO 3000TLG2~EVVO 6000TLG2 4. Set Country 6. Enable Set Country Users press “Back” button to enter “1. Enter setting” interface, Press OK button to enter Users press Back button to enter “1. Enter setting” interface, Press OK button to enter main setting interface.
Page 22
EVVO 3000TLG2~EVVO 6000TLG2 EVVO 3000TLG2~EVVO 6000TLG2 Users press Back button to enter “1.Enter setting” interface, Press OK button to enter main Set Reactive setting interface. Enter “11. Set Start Parameter” by pressing “Up” button Or “Down” button, Users press “Back” button to enter “1.Enter Setting” interface, Press “OK” button to enter press “OK”...
Page 23
EVVO 3000TLG2~EVVO 6000TLG2 EVVO 3000TLG2~EVVO 6000TLG2 Set Power Ratio (The country is set at 10) (C) “SystemInfo” Interface as below: Users press Back button to enter “1.Enter setting” interface, Press OK button to 3.SystemInfo enter main setting interface. Enter “20.Set Power Ratio” by pressing “Up” button Or “Down”...
EVVO 3000TLG2~EVVO 6000TLG2 EVVO 3000TLG2~EVVO 6000TLG2 7. Input Mode 6.4 Update Software online Press “Back” button and “Up” or “Down” button to enter “3. System Info” interface, then Press “OK” button to enter into system information checking interface, then press “Up” or The inverters offer software upgrade via SD card to maximize inverter performance and avoid “Down”...
Page 25
Step 3 The SD card reader must be ready by the users, so that SD card so easy to establish the connection with the computer. Step 4 EVVO will send the Software code to the user who needs to update. After user receive the file, please decompressing file and cover the original file in SD card.
EVVO 3000TLG2~EVVO 6000TLG2 EVVO 3000TLG2~EVVO 6000TLG2 Check whether too few PV modules are series ID05 PVUVP The input voltage is too low connected in a PV string, thus the voltage(Vmp) of the PV string is lower than the minimum operating voltage of inverter.
Page 27
EVVO 3000TLG2~EVVO 6000TLG2 EVVO 3000TLG2~EVVO 6000TLG2 ID66 UnrecoverBusOVP ID26 ID26-ID27 are internal faults of inverter, turn OFF The bus voltage is too BusOVP The bus voltage Is too high the “DC switch”, wait for 5 minutes, then turn ON the h i g h , a n d h a s c a u s e “DC switch”.
OFF. Wait at least for 5 minutes before the cleaning. Outlines of this chapter This topic lists the technical specifications for all EVVO 3000TLG2~EVVO 6000TLG2 inverters. Inverter cleaning 8.1 Input parameters (DC) Please clean the inverter with an air blower, a dry & soft cloth or a soft bristle brush. Do NOT clean the inverter with water, corrosive chemicals, detergent, etc.
Extension warranty can be DC switch Optional purchased for extra 5, 7, 10 or 12 years. For more details please check with EVVO service Safety protection Anti islanding, RCMU, Ground fault monitoring team.