TI_Unit_ZX_A2L_03_EN_Rev01
Copeland ZX*Y refrigeration units
Quick installation guide
1. Install the refrigeration unit according to Application Guidelines AGL_Unit_ZX_A2L_A1_EN "Copeland outdoor
refrigeration units – ZX*Y range".
2. Prefill the unit with refrigerant and set all valves into operating position.
3. Set up the unit controller (XCM25D) for the required application.
NOTE: If a room thermostat is used to control the solenoid valve, only parameters C01 and C02 (cut-
in/cut-out pressures) must be adjusted to perform a pumpdown. The value of parameter D29 must be
lower than C02 to avoid a low-pressure alarm.
The XCM25D controller provides 2 programming levels:
▪ Pr1 with direct access
▪ Pr2 protected with a password (intended for experts)
Explanation of LED functionalities
LED
Mode
Function
On
Compressor 1 enabled
Flashing
Anti-short cycle delay enabled
On
Condensing fans enabled
On
Bar display
Flashing
Programming mode
On
PSI display
Flashing
Programming mode
On
When browsing the service menu
Flashing
In fast access menu
How to program the "Pr1" parameters:
Access pre-
program level
Access
or
program level
Access Pr1
Select item
or
Show value
Modify
or
Confirm and
store
EXIT
When entering the programming level for the first time the display will show the rtC (real time clock) label.
▪ Press
to access parameters N01/02/03/04/05 and adjust time & date. For further details see the refrigeration
unit application guidelines, section 2.13 "Parameters level 1 – Required settings".
▪ Press
or
to move from the rtC label to the Par label, in order to access programming level 1.
▪ Press
: the parameters in programming level 1 can be changed.
Application Engineering Europe
Press simultaneously for about 3 seconds to access the pre-programming
level. The message rtC (real time clock) is displayed.
Press the Up or Down key until the message Par is displayed.
Press the SET button to enter the program level. First parameter C01 is
displayed.
Select the parameter or submenu using the arrows.
Press the SET button.
Use the arrows to modify the value.
Press the SET button: the value will blink for 3 seconds, then the display
will show the next parameter.
Press simultaneously to exit the programming mode or wait for
30 seconds without pressing any key.
1/4
TECHNICAL INFORMATION
LED
Mode
Function
On
When browsing the alarm menu
Flashing
A new alarm occurred
On
An alarm is occurring
On
Digital unloader solenoid On
On
In defrost
Evaporator fans - Liquid line
On
solenoid valve On

Advertisement

loading
Need help?

Need help?

Do you have a question about the ZX Y Series and is the answer not in the manual?

Questions and answers

Summary of Contents for Copeland ZX Y Series

  • Page 1 TI_Unit_ZX_A2L_03_EN_Rev01 Copeland ZX*Y refrigeration units Quick installation guide 1. Install the refrigeration unit according to Application Guidelines AGL_Unit_ZX_A2L_A1_EN "Copeland outdoor refrigeration units – ZX*Y range". 2. Prefill the unit with refrigerant and set all valves into operating position. 3. Set up the unit controller (XCM25D) for the required application.
  • Page 2 The following "Pr1" parameters must be verified before commissioning: Factory Parameter Description Unit Comments settings Compressor cut-in pressure setpoint bar* Not used for digital ZXDY Compressor cut-out pressure setpoint bar* Not used for digital ZXDY R454A, R454C, R455A, R1234yf, Refrigerant selection for regulation R454C R513A, R134a, R448A, R449A, R404A, R450A, R507A, R407A, R407C, R407F...
  • Page 3 Code Description Cause Action Reset The functions related to the current Automatically as soon as the probe Current sensor 2 error Probe out of range sensor are disabled restarts working. The functions related to the Automatically as soon as the probe Voltage sensor 1 error Probe out of range voltage sensor are disabled...
  • Page 4 QR code on page 1 of this guide. DISCLAIMER: Copeland Europe GmbH shall not be liable for errors in the stated capacities, dimensions, etc., as well as typographic errors. Products, specifications, assumptions, designs and technical data contained in this document are subject to modification by us without prior notice.