Tech Note 58500012A: Replacing Thyro-S...1 with Thyro-S...3
Introduction
This procedure provides additional instruction for the
installation and setup of a Thyro-S...3 to replace an
existing Thyro-S...1
Thyro-S...1
The Thyro-S...1 series exist as 1S...H1 or 1S...HRL1.
The manual and brochures for this series can be found
here:
http://www.advanced-energy.com/en/THYRO_S_H1.html
The Thyro-S...3 series exist as ...S...H3 or
...S...HRLP3. The manual and brochures for this series
can be found here:
http://www.advanced-energy.com/en/THYRO_S_H3.html
This Tech-Note does not replace the manual of the units
and does not contain the safety information. In any case
the original manuals are required for the operation and
handling of our devices.
Setup and Installation
The units are configured by using the dip-switches
behind the front cover. If the Thyro-S 1S...1 was
operated in factory setting, the Thyro-S 1S...3 can be
operated in factory settings, too.
If the Thyro-S 1S...1 settings of the dip switches differs
from the factory settings or the load fault potentiometer
is not in the factory setting position (fixed by glue),
additional parts are required to read the existing
settings.
Load fault potentiometer in factory setting (Sealed)
58500012A July 2017
Thyro-S...3
The product manual can explain the switch settings. The
switch and potentiometer settings can be read out by
using our optional PC-software Thyro-Tool and our PC-
Interface-RS232 or a USB cable.
Dip Switch settings
PCB
Thyro-S...1
S1. 1
0 full output
2
0 if setpoint "1"
3
0 No TTool-mode
4
0 resistive load
AO not available
I/O Connections
Thyro-S...1
1
Thyro-S...3
S1.
1
1 full output
2
0 if setpoint "1"
3
0 No TTool-mode
4
0 AO function:
5
0 Uload*
6
0 Not used
7
1
8
1
9
0 AO "Live zero"*
10
1 AO "10V range"*
* = HRLP3 only