Page 2
ENGLISH Code: EAAM045625EN Rev. 25 | Date: 16/01/2023 File name: EAAM045625EN _ GC315-GC400 Technical Manual _ Meccalte-Rebranded.docx Rev. 25 Date: 16/01/2023 ID Document: EAAM0456 Product: GC315xx + GC400xx Mecc Alte S.p.A. - Full or partial reproduction prohibited, if not authorized...
Page 3
Update paragraphs: 5.9.5, 5.17.4, 7.7.3.9, 7.7.3.10, 7.7.4.3, 7.7.4.10, 8.2.3, Added paragraph: 5.17.4.1 27/11/2019 Update to GC400 version 2.11 20/12/2019 Update to GC315 version 1.51 5.8.3, 8.7.9 24/09/2020 Update to GC315 version 1.54 7.7.3.1, 7.7.3.7, 7.7.3.8 Mecc Alte S.p.A. - Full or partial reproduction prohibited, if not authorized...
Page 4
Updated to GC315 version 1.70 and GC400 version 2.24 10.5 14/10/2022 Updated to GC315 version 1.73 7.4, 7.6.1, 7.7.3.1, 8.6.3.1, 9.8.007 16/01/2023 Updated to GC315 version 1.74 7.4, 8.1 Mecc Alte S.p.A. - Full or partial reproduction prohibited, if not authorized...
Engine rotational speed measurement (PICK-UP or W) JM-5, JM-6, JM-7 .. 73 5.10.1 Magnetic pick-up ..................73 5.10.2 W signal ....................74 5.10.3 Revolutions measurement from frequency ..........74 5.11 Analogue inputs (JM, JL) ................75 Mecc Alte S.p.A. - Full or partial reproduction prohibited, if not authorized...
Page 6
6.6.3 GNSS Receiver ..................118 “SMARTCLOUD” system .................. 119 Energy saving mode ..................121 Main functions ..................... 123 Front panel GC315x ..................123 Mains Mains+Link Front Panel GC400 and GC400 ............. 125 Mecc Alte S.p.A. - Full or partial reproduction prohibited, if not authorized...
Page 7
8.7.6 Switch ......................203 8.7.7 Switch management ................... 203 8.7.8 Automatic power delivery of the generator inhibited........203 8.7.9 MCB closure inhibition................204 8.7.10 Communication and events ..............204 Mecc Alte S.p.A. - Full or partial reproduction prohibited, if not authorized...
Page 8
42 – Minimum oil pressure (from ANALOGUE sensor) .......... 227 43 – Low oil pressure (from contact) ..............228 44 – Low oil pressure (from ANALOGUE sensor)..........228 45 – Maximum auxiliary current ................228 Mecc Alte S.p.A. - Full or partial reproduction prohibited, if not authorized...
Page 9
252 – CAN-BUS (EXBUS) expansion modules missing ........243 253 – CAN-BUS (EXBUS) missing measure ............244 254 – CAN-BUS (EXBUS) duplicate address ............244 255 - Connection with CAN-BUS (EXBUS) sensor timed out........ 244 Mecc Alte S.p.A. - Full or partial reproduction prohibited, if not authorized...
Page 10
Evaluation of the level ................270 10.11.4 Automatic management of the pump ............ 270 10.11.5 Manual management of the pump ............270 10.11.6 Protections .................... 270 10.11.7 Signalling ....................270 Mecc Alte S.p.A. - Full or partial reproduction prohibited, if not authorized...
[1] Mecc Alte EAAM0448xx Parameters Table GC315. [2] Mecc Alte EAAM0504xx Parameters Table GC400. [3] Mecc Alte EAAM0458xx Software Manual BoardPrg4. [4] Mecc Alte EAAS0341xx Serial Communication and SMS Protocol. Mecc Alte S.p.A. - Full or partial reproduction prohibited, if not authorized...
The cleaning of the front panel can be carried out exclusively with a soft cloth. Do not use abrasive products, detergents or solvents. Mecc Alte S.p.A. - Full or partial reproduction prohibited, if not authorized...
These documents should be considered integral part of this manual. The devices are supplied with a generic "default" configuration; is the responsibility of the installer to adjust the operating parameters to his/her specific application. CAUTION! Mecc Alte S.p.A. - Full or partial reproduction prohibited, if not authorized...
BoardPrg4 can be used on all the Mecc Alte devices; connection to the PC can be realized both directly, via the RS232 serial port, USB, or remotely via modem, RS485 serial port or ethernet network. To use the program, refer to document [3] .
Several parts of this manual refer to the controller's software revisions. These revisions are marked with the assigned Mecc Alte code (shown on the rear panel of the controller). Software code version has the following format: EB0250231XXYY, where "XX" is the main revision number and "YY" is the secondary revision number. Thus, the code EB02502310100 refers to the controller's software release "1.00".
Page 16
GC315 & GC400 Technical Manual Controller ENGLISH Code: EAAM045625EN GC315 & GC400 Rev. 25 | Date: 16/01/2023 ▪ EB0250231xxyy: GC315. ▪ EB0250248xxyy: GC400. Mecc Alte S.p.A. - Full or partial reproduction prohibited, if not authorized...
GC315 & GC400 Technical Manual Controller ENGLISH Code: EAAM045625EN GC315 & GC400 Rev. 25 | Date: 16/01/2023 2. Views of the device Front GC315 Mecc Alte S.p.A. - Full or partial reproduction prohibited, if not authorized...
Page 18
GC315 & GC400 Technical Manual Controller ENGLISH Code: EAAM045625EN GC315 & GC400 Rev. 25 | Date: 16/01/2023 Rear GC315 Mecc Alte S.p.A. - Full or partial reproduction prohibited, if not authorized...
Page 19
GC315 & GC400 Technical Manual Controller ENGLISH Code: EAAM045625EN GC315 & GC400 Rev. 25 | Date: 16/01/2023 Plus Rear GC315 Link Rear GC315 Mecc Alte S.p.A. - Full or partial reproduction prohibited, if not authorized...
Page 20
GC315 & GC400 Technical Manual Controller ENGLISH Code: EAAM045625EN GC315 & GC400 Rev. 25 | Date: 16/01/2023 Mains Front GC400 Mains Rear GC400 Mecc Alte S.p.A. - Full or partial reproduction prohibited, if not authorized...
Page 21
GC315 & GC400 Technical Manual Controller ENGLISH Code: EAAM045625EN GC315 & GC400 Rev. 25 | Date: 16/01/2023 Link Mains+Link Rear GC400 and GC400 Mecc Alte S.p.A. - Full or partial reproduction prohibited, if not authorized...
When the internal battery is low, the maximum power consumption in stand-by mode is: Link Link Mains+Link GC315 , GC400 and GC400 about 650mA @ Vbatt=13.5VDC internal battery in charge about 350mA @ Vbatt=27 VDC internal battery in charge Mecc Alte S.p.A. - Full or partial reproduction prohibited, if not authorized...
Page 23
Max 354* Vac for measures L-N Max 613* Vac for measures L-L *with voltage N-GND = 0 Vac Max tension in Common-Mode from Max 100 Vrms @ 440Vac L-L Mecc Alte S.p.A. - Full or partial reproduction prohibited, if not authorized...
Page 24
50 or 60Hz nominal frequencies measured by L1 phase voltages, for both the mains and the genset. Frequency minimum sensitivity on 35Vrms L-N @ 50Hz mains voltage inputs Mecc Alte S.p.A. - Full or partial reproduction prohibited, if not authorized...
Page 25
They can be used as starter motor (START) and fuel solenoid valve (FUEL). All relay outputs are adjustable by parameter. Rated supply Max. 3A @ 30Vdc for each output Protections Surge protection diodes incorporated. Mecc Alte S.p.A. - Full or partial reproduction prohibited, if not authorized...
Page 26
12 bit Pick-up input for the measurement of the engine speed Filtered for DC currents blocking. Minimum voltage 1,3Vac @ 3kHz Maximum voltage 60Vac Frequency range 1Hz – 10000Hz Mecc Alte S.p.A. - Full or partial reproduction prohibited, if not authorized...
Page 27
57600, 115200 bps Parity: None , Even, Odd Stop bit: 1 Default Setting Type of transmission Modbus RTU Slave , Modbus RTU Master (for connection to ECU CUMMINS) Default Setting Mecc Alte S.p.A. - Full or partial reproduction prohibited, if not authorized...
Page 28
Compliant IEE802.3/802.3u (Fast ethernet) Compliant ISO802-3/IEEE802.3 (10BASE-T) Insulation voltage 1500VRMS Display Type of display Transflective graphic monochrome LCD with backlight illumination with white leds. Resolution 128 x 64 Mecc Alte S.p.A. - Full or partial reproduction prohibited, if not authorized...
Page 29
750g with optional internal battery GC400 Mains 650g Mains/Link GC400 750g with optional internal battery Protection degree IP55 with gasket for the front panel IP20 for the panel interior Mecc Alte S.p.A. - Full or partial reproduction prohibited, if not authorized...
< 2.5m About 6h with complete unloaded battery; the time depends Optional internal battery recharge also on the level of the GSM/GPRS signal and on the data transmission interval Mecc Alte S.p.A. - Full or partial reproduction prohibited, if not authorized...
LINK LTE Protocol stack 3GPP Release 13 LTE Cat. M1 LTE Cat. NB-IoT Band: B1/B2/B3/B4/B5/B8/B12/B13/B18/B17/B19/B20/B26/B28/B39* Radio Access Technology (RAT) *B39 Supported only with LTE Category M1 GSMGPRS/EDGE Band: 850/900/1800/1900Mhz Mecc Alte S.p.A. - Full or partial reproduction prohibited, if not authorized...
Page 32
The plug of the Link device provides automatically the power supply required (Max 35mA@3,3Vdc). 3D Accelerometer: Linear acceleration measurement range: ±2 g/±4 g/±8 g/±16 g Inertial motion sensors features Linear acceleration sensitivity FS = ±2 g 1 mg/digit Mecc Alte S.p.A. - Full or partial reproduction prohibited, if not authorized...
Be careful not to overtighten the screws to avoid damaging the coupling slots on the casing of the device. Mecc Alte S.p.A. - Full or partial reproduction prohibited, if not authorized...
The device can operate in CAT.III or CAT.IV only if the supply minus terminal of the device and the neutral terminal of the generator are connected to the protective earth. 5. Connections and IN/OUT configuration NAME DESCRIPTION CONNECTOR USB B Power supply 2 poles x2.5mm Screw terminal Mecc Alte S.p.A. - Full or partial reproduction prohibited, if not authorized...
DRIVE – only engine: the controller does not manage a generator set, but only an engine (motor pump or other). The selection is done through parameter P.0802 P.0802 = 0 SPM plants. P.0802 = 1 SSB plants (default configuration) P.0802 = 11 DRIVE plants Mecc Alte S.p.A. - Full or partial reproduction prohibited, if not authorized...
GC400x provides all the other functions required for the parallel between gensets and/or the grid). The selection is made using parameter P.0802 • P.0802 = 0 for SPM plants. • P.0802 = 1 for SSB plants. Mecc Alte S.p.A. - Full or partial reproduction prohibited, if not authorized...
Page 37
If several inputs are active at the same time, the controller uses the one with the smaller "DIF" function. To select a different plant, you must: • Stop the engine and wait for stopping. Mecc Alte S.p.A. - Full or partial reproduction prohibited, if not authorized...
DIF.2151…DIF.2154, and activate them with the proper AND/OR logic, using the internal states listed above. 5.3 Basic Diagram (GC315x, GC400x in SPM plants) Mecc Alte S.p.A. - Full or partial reproduction prohibited, if not authorized...
(which must be grounded) next to the JC or to a grounding line, using, in any case, the shortest cable possible. Mecc Alte S.p.A. - Full or partial reproduction prohibited, if not authorized...
In addition to the 8 JN inputs, if not used as measurement inputs, you can also use the JM ANALOGUE inputs as digital inputs (refer to par. 5.11) and, with different methods, also terminal JL-4 (signal +D, refer to par. 5.11.22). Mecc Alte S.p.A. - Full or partial reproduction prohibited, if not authorized...
GC315). In this case it is recommended to separate the inputs with diodes, as shown in the figure below. This is to prevent the false activation of the input when one of the devices is being turned off. GCxxx GCxxx JN-x JN-x Mecc Alte S.p.A. - Full or partial reproduction prohibited, if not authorized...
In addition to the 8 digital physical inputs and the 32 of the DITEL module, the controller also operates 16 virtual digital inputs. The same are operated by the controller just as if they were physical inputs (with no limitation), but the status Mecc Alte S.p.A. - Full or partial reproduction prohibited, if not authorized...
The table below shows when they are used. NOTE: in BoardPrg4 the boxes for the delay and for the message are always displayed, even if they are not used by the controller. Mecc Alte S.p.A. - Full or partial reproduction prohibited, if not authorized...
Page 44
If the input is active, the controller status changes from AUTO to DIF.2031 Request for TEST mode. TEST (controller should be at rest in AUTO mode). When it becomes inactive, the status changes back to AUTO. Mecc Alte S.p.A. - Full or partial reproduction prohibited, if not authorized...
Page 45
Only GC400x. Local BASE LOAD. the parameter P.0880 is set as SYSTEM BASE LOAD. Used in “load management”. See document [12]. DIF.2121 Only GC400x. Select the master genset. Mecc Alte S.p.A. - Full or partial reproduction prohibited, if not authorized...
Page 46
It is used in the “load management”. See document [12]. DIF.2332 load function. Only GC400x. Select power reserve #3 for the It is used in the “load management”. See document [12]. DIF.2333 load function. Mecc Alte S.p.A. - Full or partial reproduction prohibited, if not authorized...
Page 47
If this input exists but it’s not active, the protection for the parallel DIF.2713 Only GC400x. Enable protection 27Q (PPR). with the mains “27U< & Q” is disabled. Mecc Alte S.p.A. - Full or partial reproduction prohibited, if not authorized...
Page 48
If the related input is “active”, the controller will show the text DIF.3205 Generic status (page 3). defined by the related text parameter on page S.10 of the display. Mecc Alte S.p.A. - Full or partial reproduction prohibited, if not authorized...
Page 49
If the input is “active” and the output command for the fuel solenoid DIF.4031 Warning (if FUEL is enabled). is active (JL_03), a warning is issued. The message shown is the one set by means the related “text” parameter. Mecc Alte S.p.A. - Full or partial reproduction prohibited, if not authorized...
Page 50
If the input is “active”, a warning with a fixed description (language- DIF.4212 Low fuel level dependant) is activated. This function can be also used for the “Fuel pump management” (see par. 10.1). Mecc Alte S.p.A. - Full or partial reproduction prohibited, if not authorized...
DITEL 16 IN, each managing up to two relay modules DITEL 8 OUT, for a total of 32 additional outputs other than the one included in the controller. 5.9.1 Engine commands (JL) Basic diagram for switching off when de-energizing Mecc Alte S.p.A. - Full or partial reproduction prohibited, if not authorized...
Page 52
If this command is not necessary (for example with CAN-BUS interface engines), the output can be configured for other purposes by means of the parameter P.3005, refer to par. 5.9.4 and [1] [2]. Mecc Alte S.p.A. - Full or partial reproduction prohibited, if not authorized...
Page 53
With stationary engine and alternator, the alternator +D terminal is practically a short circuit to the battery minus and the voltage at its ends is close to 0V. During and after engine starting, as well as under normal operating conditions, Mecc Alte S.p.A. - Full or partial reproduction prohibited, if not authorized...
Page 54
Using parameters P.0230 and P.0231 it is possible to enable/disable the acknowledgement of engine started by D+ signal; by using the parameter P.0349 it is possible to disable the AL.005 anomaly (“A005 – Broken belt”) (see document [1] [2]). Mecc Alte S.p.A. - Full or partial reproduction prohibited, if not authorized...
DOF.2004 – “MCB stable opening command” JI-1 DOF.2034 – “GCB stable closing command” The outputs functions included in the GC400x controller are the following: Terminal Function JI-4 DOF.2032 – “GCB impulsive opening command” Mecc Alte S.p.A. - Full or partial reproduction prohibited, if not authorized...
If there is only one circuit breaker, the MCB output (terminals 4... 6 of the JI) is not used, therefore it can be associated to a different function (see par. 5.9.4). 5.9.3 Auxiliary outputs (JE) Mecc Alte S.p.A. - Full or partial reproduction prohibited, if not authorized...
A one-bit means that the output is normally operating and goes on standby when the related function requires it. The mapping of the outputs on the controller is: Value Output Mecc Alte S.p.A. - Full or partial reproduction prohibited, if not authorized...
Page 58
The digital outputs can be used directly as command for devices outside the controller, or for reporting certain operating conditions. The following two functions, not directly linked to the operation sequences of the controller, are selectable for any digital output: Mecc Alte S.p.A. - Full or partial reproduction prohibited, if not authorized...
Page 59
Solenoid for AdBlue pump See 10.11 DOF.2001 MCB (NC) under voltage coil. See par. 8.7.1 DOF.2002 MCB opening coil. See par. 8.7.1 DOF.2003 MCB closing coil. See par. 8.7.1 Mecc Alte S.p.A. - Full or partial reproduction prohibited, if not authorized...
Page 60
This output is activated when the mains status allows the closing of the GCB circuit allowed breaker and the parallel with the mains. DOF.3061 Engine running. Active after detection of the engine running status, even when it is started manually. Mecc Alte S.p.A. - Full or partial reproduction prohibited, if not authorized...
Page 61
It is activated in presence of warnings DOF.4002 Only GC400x. Unloads It is activated in presence of unloads DOF.4003 Deactivations. It is activated in presence of deactivations (GC400x and from version 1.44 of GC315x) Mecc Alte S.p.A. - Full or partial reproduction prohibited, if not authorized...
Page 62
052: Generator’s voltages unbalance. 053: Currents unbalance. 055: Wrong phases sequence. 056: Low generator voltage. 058: Low generator frequency. 059: High generator voltage. 060: High generator frequency. 061: Excitation loss. Mecc Alte S.p.A. - Full or partial reproduction prohibited, if not authorized...
Page 63
041: Minimum oil pressure (from contact). ▪ 042: Minimum oil pressure (from analogue sensor) ▪ 043: Low oil pressure (from contact). ▪ 044: Low oil pressure (from analogue sensor) Mecc Alte S.p.A. - Full or partial reproduction prohibited, if not authorized...
Page 64
011: Power reverse. ▪ 017: Overspeed (from contact) ▪ 018: Overspeed (from pick-up). ▪ 019: Overspeed (from frequency). ▪ 060: High generator frequency. ▪ 118: Overspeed from Can-Bus. Mecc Alte S.p.A. - Full or partial reproduction prohibited, if not authorized...
DO_XXX: logic states of all the digital outputs. • AL_XXX: warnings/locks present. • ST.XXX: internal states of the controller. • AT_XXX: states concerning the thresholds on ANALOGUE measures Mecc Alte S.p.A. - Full or partial reproduction prohibited, if not authorized...
Page 66
REMOTE START ST.006 Identification ongoing anomalies ST.007 Reset ongoing anomalies ST.008 Warnings cumulative ST.009 Only GC400x. Unloads cumulative ST.010 Deactivations cumulative. ST.011 Locks cumulative ST.012 Unacknowledged warnings cumulative Mecc Alte S.p.A. - Full or partial reproduction prohibited, if not authorized...
Page 67
Only GC400x. Protection ROCOF active ST.058 Only GC400x. Protection VECTOR JUMP active ST.059 Only GC400x. Protection 27 active (U<<, 2° threshold) ST.060 Only GC400x. Protection 59 active (U>>, 2° threshold) Mecc Alte S.p.A. - Full or partial reproduction prohibited, if not authorized...
Page 68
Only GC400x. Synchronised ST.100 Only GC400x. Load ramp ST.101 Only GC400x. Unload ramp ST.102 Only GC400x. Supply in parallel with the mains ST.103 Only GC400x. Supply in parallel among gensets Mecc Alte S.p.A. - Full or partial reproduction prohibited, if not authorized...
Page 69
Only GC400x. GCB closed on genset 08 ST.152 Only GC400x. GCB closed on genset 09 ST.153 Only GC400x. GCB closed on genset 10 ST.154 Only GC400x. GCB closed on genset 11 Mecc Alte S.p.A. - Full or partial reproduction prohibited, if not authorized...
Page 70
ST.258 CAN 0 ERR-ACTIVE ST.259 No communication on CAN 0 ST.260 Only GC400x. CAN 1 BUS-OFF ST.261 Only GC400x. CAN 1 ERR-PASSIVE ST.262 Only GC400x. CAN 1 ERR-ACTIVE Mecc Alte S.p.A. - Full or partial reproduction prohibited, if not authorized...
Page 71
Status 14 from engine management by file ST.334 Status 15 from engine management by file ST.335 Status 16 from engine management by file ST.336 Application type: SPM ST.337 Application type: SSB Mecc Alte S.p.A. - Full or partial reproduction prohibited, if not authorized...
Page 72
OR, which checks that the virtual digital input #1 or the digital input #3 are active. In practice, the virtual digital input #1 is used as “support” for the AND condition. In this case you need not associate a function to the virtual digital input. Mecc Alte S.p.A. - Full or partial reproduction prohibited, if not authorized...
Usually, you can use a single pick-up, connected either to a controller or to another device, such as a speed regulator, but paying attention to the polarity of the connections. Check also that the signal amplitude is sufficient. Mecc Alte S.p.A. - Full or partial reproduction prohibited, if not authorized...
To use this feature, the following settings are needed: ▪ Set P.0110 to 0 (disables pick-up). ▪ Set P.0111 to 0 (disables W). ▪ Set P.0127 to the right ratio. Mecc Alte S.p.A. - Full or partial reproduction prohibited, if not authorized...
If it is configured as digital input, its status is displayed on page S.11 (0=input not active, 1=input active). Mecc Alte S.p.A. - Full or partial reproduction prohibited, if not authorized...
Bit 7. If this bit is “ON”, the controller issues a deactivation command if the measure is “out of threshold”. • Bit 8. If this bit is “ON”, the controller issues a lock command if the measure is “out of threshold”. Mecc Alte S.p.A. - Full or partial reproduction prohibited, if not authorized...
Page 78
So, with the previous programming, the controller activates the internal status related to the ANALOGUE input when the measure is greater than 50.5 Hz for 0,5 seconds; it deactivates the internal status when the measure is less than 50.3 Hz for 0,5 seconds. Mecc Alte S.p.A. - Full or partial reproduction prohibited, if not authorized...
Page 79
AIF.2003 Generic sensor (page 2) AIF.2005 Generic sensor (page 3) AIF.2051 Generic sensor The following table shows the list of functions that can be associated to the GC400x ANALOGUE inputs: Mecc Alte S.p.A. - Full or partial reproduction prohibited, if not authorized...
Page 80
AIF.2103 External Synchronizer AIF.2105 MCB External Synchronizer AIF.2107 GCB External Synchronizer AIF.2109 External load sharing AIF.2111 Frequency Setpoint AIF.2201 Voltage offset AIF.2211 Voltage Setpoint AIF.2301 Local BASE LOAD Setpoint Mecc Alte S.p.A. - Full or partial reproduction prohibited, if not authorized...
Through the parameter “function” of every virtual ANALOGUE input, it is possible to “copy” one of the internal measurements available in the ANALOGUE input: • AVF.4001 - "Genset frequency" • AVF.4006 - "Genset voltage L1-L2" Mecc Alte S.p.A. - Full or partial reproduction prohibited, if not authorized...
Page 82
AVF.4088 - "Speed" • AVF.4091 - "Oil level" • AVF.4092 - "Coolant level" • AVF.4093 - "Fuel level" • AVF.4094 - "Fuel level in litre" • AVF.4096 - "Immediate consumption" Mecc Alte S.p.A. - Full or partial reproduction prohibited, if not authorized...
Page 83
The purpose of the virtual ANALOGUE inputs is double: • Allowing to enable warning/blocks related to the internal measurements available. • Enabling digital outputs according to the value of the internal measurements available. Mecc Alte S.p.A. - Full or partial reproduction prohibited, if not authorized...
45Hz or lower, and at 90% for a frequency of 55 Hz or higher; for frequency values ranging between 45 Hz and 55 Hz, the output will have a value between 10% and 90%. Mecc Alte S.p.A. - Full or partial reproduction prohibited, if not authorized...
(without conversion curves) to reduce the output variation: • AOF.1000 Function: use parameters P.0856 and P.0857. • AOF.1002 Function: use parameters P.0862 and P.0863. Mecc Alte S.p.A. - Full or partial reproduction prohibited, if not authorized...
Only GC400x. Voltage regulator AOF.1003 Only GC400x. Voltage regulator (generic) AOF.3001 Engine speed AOF.3011 Oil pressure AOF.3013 Oil temperature AOF.3015 Oil level AOF.3023 Coolant temperature AOF.3025 Coolant level Mecc Alte S.p.A. - Full or partial reproduction prohibited, if not authorized...
P.0142 The number of DITEMP modules (i.e., DITHERM or DIGRIN) (max 2) P.0143 The number of DIVIT modules (max 1) P.0144 The number of DANOUT modules (max 1) Mecc Alte S.p.A. - Full or partial reproduction prohibited, if not authorized...
5.14 Connection to the public electric mains/parallel bars (JH) The connection to the public electric mains is made through the connector JH of the controller board. Mecc Alte S.p.A. - Full or partial reproduction prohibited, if not authorized...
The values of the V1-N, V2-N and V3-N phase voltages and the VN voltage of the neutral in relation to GND for the mains are displayed on page M.03. Mecc Alte S.p.A. - Full or partial reproduction prohibited, if not authorized...
It is optionally possible to order a version of the device with max 100Vac (phase-phase) voltage inputs to be used with TV with 100V secondary ones. In this case it is necessary to configure P.0151 parameter for 100V working. Mecc Alte S.p.A. - Full or partial reproduction prohibited, if not authorized...
The setting 2 allows the controller to calculate the genset current differential protection (see 5.16.1.1). Settings 2 and 3 allow to set a threshold (par. P.0377 and P.0378) on the differential current: when exceeding it, an alarm is activated. Mecc Alte S.p.A. - Full or partial reproduction prohibited, if not authorized...
RJ45 connector for connection to Ethernet networks 10/100 (GC315ETH version). For details concerning the communications see the specific paragraphs and the document [4]. For the CAN-BUS connections see documents [6] [1] and [9]. Mecc Alte S.p.A. - Full or partial reproduction prohibited, if not authorized...
Use of serial port 1 P.0452 Modbus address serial port 1 P.0453 Baud rate serial port 1 P.0454 Settings, serial port 1 P.0470 Modbus registers order, serial port 1 Mecc Alte S.p.A. - Full or partial reproduction prohibited, if not authorized...
The length of the connection should be no more than 1200m; however, it depends on the transmission baudrate set. A specific shielded cable should be used (see 4.2) with grounded shielding mesh. Mecc Alte S.p.A. - Full or partial reproduction prohibited, if not authorized...
Page 96
• P.0700 184: for CUMMINS QSX15 185: for CUMMINS QSK2323/45/60/78 186: for CUMMINS QST30 Use the traditional commands for the start-up, the stop and the engine speed regulation. Mecc Alte S.p.A. - Full or partial reproduction prohibited, if not authorized...
Parameter’s programming Loading/replacing the firmware of the device is a specific operation of Mecc Alte; in addition to the operating FW to be loaded, it requires a particular procedure and specific programs and normally this procedure must not be carried out by the person who performs the installation, except in specific situations previously agreed on with Mecc Alte.
You can connect the device to a LAN network, or directly to a PC (point to point connection). The connection allows for the use of the Mecc Alte SS3 SWs, configuration of the BoardPrg4 and of all the available features using the TCP/IP protocol.
Page 99
Once the controller has valid values for the parameters P500, P501 and P.502, it can be contacted through TCP-Modbus protocol on the configured IP address and on the configured port with P.053, i.e., with the supervision SW (Mecc Alte SS3) and configuration SW (BoardPrg4).
Page 100
1. MANAGER: is the management system (e.g., supervisory system or expires on PC); 2. AGENT: is the device that responds to SNMP queries (e.g., Mecc Alte controller); 3. MIB (Management Information Base): is a fixed file used to provide the manager with instructions to collect the information contained in the device.
NOTE: the MIB files (Meccalte_GC315_v2B.mib for GC315 e Meccalte_GC400_v2B.mib for GC400) are available on the Mecc Alte web site www.meccalte.com 5.18 CAN-BUS connections For the below described connections, use a cable suitable for the CAN-BUS (see docs [1] [9]). Mecc Alte S.p.A. - Full or partial reproduction prohibited, if not authorized...
Connect the shielding mesh of the shielded cable to the protective earth or to signal on both sides make sure that interior, panel and the engine frame are kept at the same potential). Mecc Alte S.p.A. - Full or partial reproduction prohibited, if not authorized...
This CAN-BUS interface is only available for GC400x and must only be used for plants composed by more than one generator (MPM). It is useful to connect all Mecc Alte genset controllers to each other (not necessarily only GC400x): through this communication channel (PMBC – Power Management Communication Bus) the controllers exchange all necessary data to manage the parallel functions (see doc.
To receive SMS messages in case of alarms or information about the plant status To send commands to the plant through SMS messages To possibly update the FW remotely when using the Mecc Alte SS3 program To receive messages of status indication via e-mail through the SMARTCLOUD system.
Mecc Alte is not responsible for any problem or disagreement resulting by the choice of an inopportune telephone fare or by a wrong configuration of the device.
Insert the SIM into the rails of the upper part of the SIM holder; replace the upper part and push it gently upwards until it snaps: Mecc Alte S.p.A. - Full or partial reproduction prohibited, if not authorized...
Tighten the connectors by hand without using wrenches or pincers. We recommend you use a EAD FCPG35177-SM-SM-3K combined antenna able to receive both GPS and GPS/GPRS Link signals. You can directly ask Mecc Alte to supply it together with the controllers. 6.2.3...
ATTENTION! With a completely discharged battery it might take a few minutes of charge before the modem is able to send or receive messages or connect to “SMARTCLOUD” system. Mecc Alte S.p.A. - Full or partial reproduction prohibited, if not authorized...
The system can be used for different purposes • For using the Mecc Alte SMARTCLOUD system • To remotely connect to the device via internet, i.e., using the Mecc Alte SS3 program • To enter the programming of the remote parameter via internet •...
Remove the access cover that encloses the SIM holder, the antenna connectors and the battery switch. Insert a small screwdriver in the little retention hooks and make a slight leverage to remove the panel. Mecc Alte S.p.A. - Full or partial reproduction prohibited, if not authorized...
SIM insertion (Only Link LTE Pull back the upper cover, it clicks as it unlocks. (fig.1). Open the SIM card holder, it hinges towards you (fig.2). Fig.1 Fig.2 Mecc Alte S.p.A. - Full or partial reproduction prohibited, if not authorized...
Connect the antennas when the device is off; let the cable pass through the lid holes paying attention not to invert the two convectors between themselves. Tighten the connectors by hand without using wrenches or pincers. (fig.5) Mecc Alte S.p.A. - Full or partial reproduction prohibited, if not authorized...
Page 113
A separation distance of at least 30 cm (11.81 inches) between the GSM/LTE antenna and the body of the user and other persons must be maintained at all times. Mecc Alte S.p.A. - Full or partial reproduction prohibited, if not authorized...
The internal battery can be recharged only when the controller temperature is between 0°C and +50°C. The internal battery is lithium ions type and has a small level of self-discharge but present though. Mecc Alte S.p.A. - Full or partial reproduction prohibited, if not authorized...
Page 115
➢ Sending and receiving SMS* message ➢ The GNSS geo-location ➢ The RS232 serial port ➢ The display LCD (with lamp off) ➢ The accelerometer and a gyroscope ➢ The keys Mecc Alte S.p.A. - Full or partial reproduction prohibited, if not authorized...
It is important that you deactivate the PIN code check: insert the SIM in a phone and deactivate the PIN code before using it in the Link and Link LTE devices. Mecc Alte S.p.A. - Full or partial reproduction prohibited, if not authorized...
IP address given to the controller by the mobile data network. If you are using the Mecc Alte SS3, it is possible to connect to the plant in any moment by setting the section dedicated to the connection between the “SMARTCLOUD”...
If you use the GNSS module, it is possible to configure the controller to send messages to “SMARTCLOUD” server if any movement is detected: Mecc Alte S.p.A. - Full or partial reproduction prohibited, if not authorized...
BoardPrg4xx and also through the web service in the appropriate configuration page of the device. In details: Mecc Alte S.p.A. - Full or partial reproduction prohibited, if not authorized...
Page 120
Status: indicates the status, the date and the time of the last connection (which is of the last data sent/received by the server) and the time left before the next data issue. The status can be: Mecc Alte S.p.A. - Full or partial reproduction prohibited, if not authorized...
The display is turned off and the electronic of the controller, the modem and the GNSS receiver work with reduced modalities. Mecc Alte S.p.A. - Full or partial reproduction prohibited, if not authorized...
Page 122
2. the movement set in parameter P.0583 has been exceeded 5. If no other movement has been detected by the internal motion sensor (Accelerometer), the controller returns to the Energy Saving state initially described. Mecc Alte S.p.A. - Full or partial reproduction prohibited, if not authorized...
7.1 Front panel GC315x Fig. 1 – Front Panel GC315x 1 - Pushbuttons 2 - Indicators The controls consist of 12 buttons (1a, 1b, 1c, 1d, 1e, 1f). Mecc Alte S.p.A. - Full or partial reproduction prohibited, if not authorized...
Page 124
GC315 & GC400 Technical Manual Controller ENGLISH Code: EAAM045625EN GC315 & GC400 Rev. 25 | Date: 16/01/2023 The front panel also has some luminous indicators (2a, 2b, 2c). Mecc Alte S.p.A. - Full or partial reproduction prohibited, if not authorized...
1 - Pushbuttons 2 - Indicators The controls consist of 11 buttons (1a, 1b, 1c, 1d, 1e, 1f). The front panel also has 10 luminous indicators (2a, 2b, 2c). Mecc Alte S.p.A. - Full or partial reproduction prohibited, if not authorized...
Esc/SHIFT When pressed in any menu, it displays on the upper line the engine status. Ref. 1b Mecc Alte S.p.A. - Full or partial reproduction prohibited, if not authorized...
Page 127
In “MAN” it is used to open and/or close the mains contactor to the utilities. To open the mains switch MCB, with the engine idle, press and hold the “MCB” button for at least 5 seconds. Ref. 1f Mecc Alte S.p.A. - Full or partial reproduction prohibited, if not authorized...
Page 128
DOF.3153, allowing the test of the lamps on the control panel as well. When the genset control module is activated, keeping it pressed at the same time as the START button allows access to the special functions. Mecc Alte S.p.A. - Full or partial reproduction prohibited, if not authorized...
INTERFACE Flashing at 75% ON signals a COM error (J1939 or MTU): the port is in BUS-OFF mode. Ref. 2a Indicates that the CAN-BUS is disabled. Mecc Alte S.p.A. - Full or partial reproduction prohibited, if not authorized...
Page 130
The MCB switch is opened. MCB (only GC315x and The MCB switch is closed. Mains GC400 /GC40 Mains+Link Flashes at 25% ON if open after a closing command. Mecc Alte S.p.A. - Full or partial reproduction prohibited, if not authorized...
(P.492) if no buttons are pressed in the meantime. Press any button to switch the lamp ON again, (we recommend using the Esc/SHIFT button as it has no function when used alone). This function can be disabled by setting parameter P.492 to 0. Mecc Alte S.p.A. - Full or partial reproduction prohibited, if not authorized...
Pages about parallel functions B.XX HISTORY History logs H.XX Generally, navigation between modes takes place via buttons UP Rif. 1c and DOWN Ref. 1c Fig. 2 - Mode navigation Mecc Alte S.p.A. - Full or partial reproduction prohibited, if not authorized...
KEY: 1a - Mode identifier E.02 ENGINE 1b - Page identifier 1c - Page title 2 – System status Fig. 5 – Display of the top status bar Mecc Alte S.p.A. - Full or partial reproduction prohibited, if not authorized...
1.2 Engine 2/06 1 - Status bar 2 - Current menu 3 - Current parameter 0133-Nominal speed 4 - Parameter value engine (primary) [1500] Fig. 6 display areas Mecc Alte S.p.A. - Full or partial reproduction prohibited, if not authorized...
Page 135
When this time has expired, a new password has to be requested to Mecc Alte. To obtain the password, the operator will have to ask for it to Mecc Alte indicating the serial number (“Cod. ID”) of the controller together with the “Internal Code”...
Page 136
As no password is associated to End User and Installer, programming the relevant parameters is allowed without entering anything in “P.0000-Access code”. To modify the parameters associated to Manufacturer, simply enter “CCC” in “P.0000-Access code”. Example 6: P.0001=0 P.0002=”III” P.0003=0 Mecc Alte S.p.A. - Full or partial reproduction prohibited, if not authorized...
Page 137
However, this general rule provides some exceptions. Refer to the chapter on faults, par. 0, which describes, for each of the faults, the method to disable it. Mecc Alte S.p.A. - Full or partial reproduction prohibited, if not authorized...
Page 138
Use the ▲ e ▼ buttons to cyclically scroll through the menu to the lower and upper index items (i.e., pressing the ▲ allows to directly cycle from the first item to the last one and vice versa). Press the ENTER button to enable the Mecc Alte S.p.A. - Full or partial reproduction prohibited, if not authorized...
Page 139
Numeric selected in a pre-defined list (for example the number of phases of the generator): same goes for the numeric parameters, considering that the UP ▲ and/or DOWN▼ buttons allow for passing to the fallowing/previous value Mecc Alte S.p.A. - Full or partial reproduction prohibited, if not authorized...
7.6.2 Status information (S.xx) In this way, information on the system status is provided. You can scroll through the various pages using the LEFT and RIGHT buttons. Mecc Alte S.p.A. - Full or partial reproduction prohibited, if not authorized...
Page 141
• Press the ENTER key • Use the ▲▼ keys to scroll the anomalies • Press EXIT to leave the mode Mecc Alte S.p.A. - Full or partial reproduction prohibited, if not authorized...
Page 142
The unambiguous serial number of the controller board (called ID CODE). ▪ The code of the software currently loaded on the controller board (see par. 1.9). ▪ Only for GC400x: the internal code necessary to obtain a Mecc Alte level temporary password (see 7.6.1.2). 7.6.2.4 S.04 SERIAL COMMUNICATION This page is dedicated to the serial communication towards the serial ports and through USB.
Page 143
IP address is shown the DNS name of the server). It also shows the status of the communication with the server: • “Stand-by”. • “In course”. • “Error”. • “No answer”. Mecc Alte S.p.A. - Full or partial reproduction prohibited, if not authorized...
Page 144
DITEL modules. If a DITEL module does not communicate correctly, the controller displays some dashes instead of the status of the inputs. Pressing the digit ACK/ENTER it is possible to display the turning inputs in two different ways: Mecc Alte S.p.A. - Full or partial reproduction prohibited, if not authorized...
Page 145
“+OVER”: if the module indicates that the input signal has a too high value, symptom of failure. • “-OVER”: if the module indicates that the input signal has a too low value, symptom of failure. Mecc Alte S.p.A. - Full or partial reproduction prohibited, if not authorized...
The generator. The symbol of the generator is in “reverse” if the engine is started and if the generator is powered. On GC315, if parameter P.0802 is set to "11-Drive", the generator symbol is replaced by the engine symbol. Mecc Alte S.p.A. - Full or partial reproduction prohibited, if not authorized...
Page 147
This page shows the Phase-to-Phase concatenated voltages and the frequency of the generator, in addition to the rotation direction of the phases (clockwise or counter clockwise). For three-phase systems, the phase-to-phase voltages Mecc Alte S.p.A. - Full or partial reproduction prohibited, if not authorized...
Page 148
2 and 3 are replaced by dashes). At the right bottom corner, the generator or mains icon is displayed, to indicate which powers you are looking at (see note in 7.6.3.8). Mecc Alte S.p.A. - Full or partial reproduction prohibited, if not authorized...
Page 149
At the bottom to the right, the display shows an icon which identifies the mains, so as to allow you to easily distinguish this page from the previous, which has an identical structure. This page is hidden on GC315 if parameter P.0802 is set to “11-Drive”. Mecc Alte S.p.A. - Full or partial reproduction prohibited, if not authorized...
Page 150
(see previous paragraph). In this way, it is possible to perform a manual synchronization. Mecc Alte S.p.A. - Full or partial reproduction prohibited, if not authorized...
Page 151
Active power and cosfi setpoints for the SYSTEM BASE LOAD mode. • Active power setpoint for the LOCAL BASE LOAD mode. • Cosfi setpoint for the LOCAL BASE LOAD mode. Mecc Alte S.p.A. - Full or partial reproduction prohibited, if not authorized...
Page 152
2521 - Load type L3 (0=leading, 1=lagging) • spn 2468 - Exported active energy • spn 2469 - Imported active energy • spn 3380 - Excitation voltage Mecc Alte S.p.A. - Full or partial reproduction prohibited, if not authorized...
(AIF.1601 function in the configuration of the analogue inputs). • turbocharger pressure (AIF.1641 function in the configuration of the analogue inputs). • exhaust gas temperature (left bank) (AIF.1603 function in the configuration of the analogue inputs). Mecc Alte S.p.A. - Full or partial reproduction prohibited, if not authorized...
Page 154
Press the ENTER button: the square brackets between which the current mode is displayed start flashing. • Use the vertical scrolling buttons UP and DOWN to select the desired mode. Mecc Alte S.p.A. - Full or partial reproduction prohibited, if not authorized...
Page 155
SPN 623 (“RED STOP LAMP”). The engine control unit (or the voltage regulator) is signalling on the CANBUS the presence of a diagnostic code (therefore a problem) that prevents its operation Mecc Alte S.p.A. - Full or partial reproduction prohibited, if not authorized...
Page 156
• The time (in hours) that this diagnostic code has been active in the past. • The remaining time (in hours) to the derating of the engine performances. Mecc Alte S.p.A. - Full or partial reproduction prohibited, if not authorized...
Page 157
513: Actual Engine - Percent Torque. ▪ spn 514: Nominal Friction - Percent Torque. ▪ spn 515: Engine's Desired Operating Speed. ▪ spn 544: Engine Reference Torque Mecc Alte S.p.A. - Full or partial reproduction prohibited, if not authorized...
Page 158
The parameter can be modified directly from page E.24. As an alternative to the parameter, it is possible to use two digital inputs configured with the following functions: Mecc Alte S.p.A. - Full or partial reproduction prohibited, if not authorized...
Page 159
SPN 3714 (“DIESEL PARTICULATE FILTER ACTIVE REGENERATION INHIBITED DUE TO TEMPORARY SYSTEM LOCKOUT”) SPN 3715 (“DIESEL PARTICULATE FILTER ACTIVE REGENERATION INHIBITED DUE TO PERMANENT SYSTEM LOCKOUT”) SPN 3716 (“DIESEL PARTICULATE FILTER ACTIVE REGENERATION INHIBITED DUE TO ENGINE NOT WARMED UP”) Mecc Alte S.p.A. - Full or partial reproduction prohibited, if not authorized...
Page 160
SPN 5963 ("AFTERTREATMENT 1 TOTAL DIESEL EXHAUST FLUID USED") • SPN 6563 ("AFTERTREATMENT TRIP DIESEL EXHAUST FLUID") • SPN 4360 ("AFTERTREATMENT 1 SCR INTAKE TEMPERATURE") • SPN 4363 ("AFTERTREATMENT 1 SCR OUTLET TEMPERATURE") Mecc Alte S.p.A. - Full or partial reproduction prohibited, if not authorized...
Page 161
Attention: since the descriptions are defined in the external file, they do not fit the language selected on the controller (typically they are in English). Mecc Alte S.p.A. - Full or partial reproduction prohibited, if not authorized...
Measures from CAN-BUS PMCB (only for GC400x) (B.xx), In this mode are shown the measures and the status acquired by the CAN-BUS PMCB, which connects all Mecc Alte devices among them. All pages of this mode are only shown only if the CAN-BUS PMCB is enabled (P.0800 <> 0).
The history logs can be accessed in any controller working status. To access archive visualization, press the ▲ and ▼ buttons till the HISTORY LOGS (H.01) page is displayed. Mecc Alte S.p.A. - Full or partial reproduction prohibited, if not authorized...
Page 164
Bits management: Hexadecimal Firmware Description value P.0441 version 01.02 Controller modes. 01.02 Mains status. 01.02 Generator status. 01.02 Engine status. 01.02 Switches status. 01.02 Switches controls. 01.02 Start/stop requests. Mecc Alte S.p.A. - Full or partial reproduction prohibited, if not authorized...
Page 165
MCB closed (from digital input) EVT.1038 01.02 MCB open (from digital input) EVT.1040 01.02 Engine stopped EVT.1041 01.02 Starting cycle EVT.1042 01.02 Engine running EVT.1043 01.02 Cooling cycle Mecc Alte S.p.A. - Full or partial reproduction prohibited, if not authorized...
Page 166
Change-over inhibition active (from the loads on the generator). EVT.1081 01.02 Change-over inhibition not active (from the loads on the generator). EVT.1082 01.02 Engine protections override on EVT.1083 01.02 Engine protections override off Mecc Alte S.p.A. - Full or partial reproduction prohibited, if not authorized...
Page 167
Power setpoint limitation for high voltage disabled EVT.1135 02.19 GC400 Start of power setpoint limitation for high voltage EVT.1136 02.19 GC400 End of power setpoint limitation for high voltage Mecc Alte S.p.A. - Full or partial reproduction prohibited, if not authorized...
Page 168
SPtM e MPtM plants). EVT.1225 01.30 GC400 “Automatic intervention inhibition” active (for GCB not open). EVT.1226 01.30 GC400 “Automatic intervention inhibition” not active (for GCB not open). Mecc Alte S.p.A. - Full or partial reproduction prohibited, if not authorized...
Page 169
The anomalies are themselves saves as events. They are registered with their own alarm code with in addition: 2000: if they are pre-alarms 3000: if they are downloads (only GC400x) Mecc Alte S.p.A. - Full or partial reproduction prohibited, if not authorized...
Page 170
The controller records the ANALOGUE magnitudes described below (with engine On or Off); the recording frequency is configured with the parameter P.0442 (seconds) and P.0443 (minutes): ▪ Mains phase-to-phase voltages and frequency. Mecc Alte S.p.A. - Full or partial reproduction prohibited, if not authorized...
Page 171
60 seconds. This archive provides a total storage capability of 42 (engine-On and engine-Off) records. Every following record overwrites the older one. The controller records the ANALOGUE values described in par. 7.6.6.3. Mecc Alte S.p.A. - Full or partial reproduction prohibited, if not authorized...
Page 172
The fourth line shows a description of the peak recording currently displayed: • Maximum power • Maximum current. (L1) • Maximum current. (L2) • Maximum current. (L3) • Maximum coolant temperature Mecc Alte S.p.A. - Full or partial reproduction prohibited, if not authorized...
Page 173
In addition, if the combination of the SPN and FMI codes (or the DTC code) is known to the controller, a text description of the problem is displayed. Mecc Alte S.p.A. - Full or partial reproduction prohibited, if not authorized...
English and Portuguese. The others can be transferred to the controller (one at a time) through the BoardPrg4 software. See 7.6.2.3 for language selection procedure. Mecc Alte S.p.A. - Full or partial reproduction prohibited, if not authorized...
When one of these inputs is active, the operating mode of the controller is forced and you can no longer use the buttons on the panel, nor the controls of the serial ports to change it (the first line of the display shows a key-shaped icon). Mecc Alte S.p.A. - Full or partial reproduction prohibited, if not authorized...
Page 176
From a PC connected to a serial port (with Modbus RTU protocol). The controller shifts to TEST after receiving the command from the serial port, then, returns to AUTO after receiving the opposite command or when it detects an Mecc Alte S.p.A. - Full or partial reproduction prohibited, if not authorized...
Page 177
(within 5 seconds): ▪ HOLDING REGISTER 101: enter the password configured with the parameter P.0004. ▪ HOLDING REGISTER 102: enter the value: ▪ “13” to require REMOTE START mode. Mecc Alte S.p.A. - Full or partial reproduction prohibited, if not authorized...
The mains must be connected to the JH connector. On a three-phase system, ensure to connect the three phases and the neutral; on a single-phase system, ensure to connect the L phase on connector 3 and the neutral on 4. Mecc Alte S.p.A. - Full or partial reproduction prohibited, if not authorized...
These checks are individually described (with examples) below: please, remember that disabling both voltages and frequency checks is not possible (in this case, mains is always considered not present). Mecc Alte S.p.A. - Full or partial reproduction prohibited, if not authorized...
Page 180
“C” band and is now within the “D” band, it is anyway considered “In tolerance”. On the other hand, in case the frequency was within the “C” band, and now is within “D” band, it is considered “Low”. Mecc Alte S.p.A. - Full or partial reproduction prohibited, if not authorized...
Page 181
These values define the following bands: A band: absent 70 (80-10) V B band: hysteresis C band: low D band: hysteresis 330 (320+10) E band: in tolerance 430 (440-10) F band: hysteresis Mecc Alte S.p.A. - Full or partial reproduction prohibited, if not authorized...
Page 182
In case the status of all existing voltages (1 or 3) and the frequency are “Absent”, also the global status is “Absent”. • In case the status of all existing voltages (1 or 3) and the frequency is “In tolerance”, also the global status is “In tolerance”. Mecc Alte S.p.A. - Full or partial reproduction prohibited, if not authorized...
The use of the “mains presence delay” (configured with parameter P.0205) depends on the presence of one or more generators supplying the loads, and on the configuration of parameter P.0250. It is a bit-managed parameter. At the moment two bits are defined: Mecc Alte S.p.A. - Full or partial reproduction prohibited, if not authorized...
(the percentage values are calculated with respect to the rated engine speed - P.0133 or P.0134). • Set parameters P.0333 and P.0334 correctly (over-speed protection). Mecc Alte S.p.A. - Full or partial reproduction prohibited, if not authorized...
• P.0331: maximum frequency threshold (percentage of P.0105); over this threshold, the engine must be stopped due to risk of damage to both the engine and the alternator. Mecc Alte S.p.A. - Full or partial reproduction prohibited, if not authorized...
Page 186
P.0305+hysteresis and P.0305-hysteresis, otherwise it maintains the previous status. A band: absent B band: hysteresis C band: minimum D band: low E band: in tolerance F band: high G band: Maximum Band H: Overspeed Mecc Alte S.p.A. - Full or partial reproduction prohibited, if not authorized...
17.5 % to voltage P.0227 Started engine threshold due to 20.0 % voltage P.0301 Minimum voltage threshold 75.0 % P.0303 Maximum voltage threshold 112.5 % P.0202 Hysteresis 2.5 % Mecc Alte S.p.A. - Full or partial reproduction prohibited, if not authorized...
8.3.3 Overview For general management purposes, generator operation can be described in three steps: Mecc Alte S.p.A. - Full or partial reproduction prohibited, if not authorized...
When there is an inhibition active, a flashing lock is displayed in the top right corner of the display. Note: the inhibition status does not affect TEST and REMOTE START modes. Mecc Alte S.p.A. - Full or partial reproduction prohibited, if not authorized...
Engine running/stopped status acknowledgement There are three engine status: Stopped: the activation of the command is allowed for starter motor. In movement: the engine is not considered running, therefore: Mecc Alte S.p.A. - Full or partial reproduction prohibited, if not authorized...
Page 191
P.0227 has to be major than P.0226 (otherwise this check is disabled). • The instantaneous status of the engine is: Stopped if the voltages measured on all generator phases are lower than P.0226. Mecc Alte S.p.A. - Full or partial reproduction prohibited, if not authorized...
P.3016 (menu 1 System, 1.7 digital Inputs/Outputs, 1.7.3 digital Outputs, 1.7.3.1 digital Outputs) using the following values: • DOF.1001: glow-plugs preheating (PREHEAT). • DOF.1002: engine control unit enable (ENABLE ENGINE) Mecc Alte S.p.A. - Full or partial reproduction prohibited, if not authorized...
If REMOTE STARTING is activated (see the paragraph that describes the controller operation mode). If an automatic starting is required and no inhibition to the starting is activated (see 8.4). Mecc Alte S.p.A. - Full or partial reproduction prohibited, if not authorized...
Page 194
In this state the engine has to be checked for a maximum time of 10 seconds to check if it starts. PRE-LUBRICATION, FUEL, ENGINE ENABLING, GAS and IDLE (if requested) are active, to facilitate the eventual Mecc Alte S.p.A. - Full or partial reproduction prohibited, if not authorized...
Page 195
• Output “select battery 1” activated, output “select battery 2” deactivated • Wait 2 seconds (it can be increased with the glow plug pre-heating) • First starting attempt Mecc Alte S.p.A. - Full or partial reproduction prohibited, if not authorized...
Page 196
With emergency procedure. Such procedure provides the immediate stop of the engine, without cooling cycle. It applies The controller is forced in OFF_RESET. Mecc Alte S.p.A. - Full or partial reproduction prohibited, if not authorized...
Page 197
By setting P.0240 to "0", the board can always run the cooling cycle. Mecc Alte S.p.A. - Full or partial reproduction prohibited, if not authorized...
The controller records any change of the start/stop requests in the events log, if it is enabled with bit 6 of the P.0441 parameter: • EVT.1050: Manual start command • EVT.1051: Manual stop command • EVT.1052: Auto start command • EVT.1053: Auto stop command Mecc Alte S.p.A. - Full or partial reproduction prohibited, if not authorized...
(for example, for the snap of its protections), it is possible to configure a delay between the opening of the breaker and the activation of this (P.0246, set to zero as per default): this function is useful for some breakers of small Mecc Alte S.p.A. - Full or partial reproduction prohibited, if not authorized...
It is also used to detect the status of the circuit breaker when it is commanded by external devices. • To show the status of the circuit breakers on the front panel LEDs. Mecc Alte S.p.A. - Full or partial reproduction prohibited, if not authorized...
Note: if MCB is configured as “supplied by mains” (P.0847 different from zero) and the mains lacks, the controller never tries to command the MCB closure, not even in OFF/RESET. Mecc Alte S.p.A. - Full or partial reproduction prohibited, if not authorized...
“33” to close the GCB. ▪ “41” to open the MCB. ▪ “43” to close the MCB. For a detailed sequence corresponding to each single type of plant, see doc. [12]. Mecc Alte S.p.A. - Full or partial reproduction prohibited, if not authorized...
(oil pump or other). In these conditions, it is possible to prevent the closure of the GCB breakers of the other generators (P.0804), and also Mecc Alte S.p.A. - Full or partial reproduction prohibited, if not authorized...
ST.068 - “GCB steady closing command”. • ST.069 - "Stable close command for MCB" • ST.070 - "GCB under voltage coil command" • ST.071 - "Impulse open command for GCB” Mecc Alte S.p.A. - Full or partial reproduction prohibited, if not authorized...
An alarm can be activated only if no other alarms are already active (there are some exceptions to this rule and will be underlined in the rest of the paragraph). Discharges, deactivations and early warnings can be present. Mecc Alte S.p.A. - Full or partial reproduction prohibited, if not authorized...
By using a command from the serial port. The commands can be password protected (P.0004) which has to be sent before any command and can be disabled through a digital input (DIF.2706). To send the command you need to write in sequence (within 5 seconds): Mecc Alte S.p.A. - Full or partial reproduction prohibited, if not authorized...
By using a command from the serial port. To send the command you need to write in sequence (within 5 seconds): ▪ HOLDING REGISTER 101: enter the password configured with the parameter P.0004. ▪ HOLDING REGISTER 102: enter the value “53”. Mecc Alte S.p.A. - Full or partial reproduction prohibited, if not authorized...
ST.010 - "Deactivations cumulative" • ST.011 - "Interlocks cumulative" • ST.012 - "Unacknowledged warnings cumulative" • ST.013: The output is active if there is at least one not acknowledged downloading. Mecc Alte S.p.A. - Full or partial reproduction prohibited, if not authorized...
ST.015 - "Unacknowledged interlocks cumulative" 9.5 Protection OVERRIDE WARNING: the use of these functions can bring the engine to serious damages. Mecc Alte cannot be considered responsible for any malfunction or damages to persons and/or things occurred following to the use OVERRIDE functions.
DIF.4041, DIF.4042, DIF.4043, DIF.4044. The anomaly can be activated only if the GAS electro-valve is open (GAS, see 8.6.2). The controller activates these anomalies if the digital input remains active consecutively for the time configured (P.2002). Mecc Alte S.p.A. - Full or partial reproduction prohibited, if not authorized...
“Enabling an anomaly” means having the minimum conditions necessary in order for the controller to observe the cause. “Activation of an anomaly” means having the cause, after the happened enabling. 01 – Minimum generator voltage Deactivation Mecc Alte S.p.A. - Full or partial reproduction prohibited, if not authorized...
This protection is only enabled if the engine has been started by the controller (if the command for the fuel solenoid is activated) It is enabled the first time (from engine start) the generator's frequency and voltages enter the tolerance Mecc Alte S.p.A. - Full or partial reproduction prohibited, if not authorized...
P.0102 Generator rated voltage P.0106 Generator rated output P.0309 Maximum current threshold P.0310 Maximum current delay P.0323 Action for maximum current and short circuit P.0324 Protections enabling 50V-51V Mecc Alte S.p.A. - Full or partial reproduction prohibited, if not authorized...
Page 214
The following graph shows the curve used for enabling protection, with a value of P.0310 set to 60 seconds (I is the maximum current): Mecc Alte S.p.A. - Full or partial reproduction prohibited, if not authorized...
Page 215
If the generator voltage is less or equal to 20% of the rated, the current threshold becomes 20% of the one set. • If the generator voltage is between 20% and 80% of the rated, the current threshold is reduced in percentage. Mecc Alte S.p.A. - Full or partial reproduction prohibited, if not authorized...
SMS, while in AUTO, TEST or REMOTE START mode. 08 – Operating conditions failure Type: Alarm Category: Generic Related parameters: P.0217 Maximum time for operating conditions To disable: P.0217=0 Enabled in: AUTO, TEST, REMOTE START Mecc Alte S.p.A. - Full or partial reproduction prohibited, if not authorized...
Related parameters: P.2001 Feature of the input 1 or equivalent for the other inputs P.2002 Delay for the input 1 or equivalent for the other inputs To disable: P.2002 =0 Mecc Alte S.p.A. - Full or partial reproduction prohibited, if not authorized...
(see anomaly description “06 – Maximum current”). To activate protection “51V” instead of “51”, you need to set parameter P.0324 to 1 or 3. Mecc Alte S.p.A. - Full or partial reproduction prohibited, if not authorized...
Related parameters: P.0105 Rated frequency (Hz) P.0331 Maximum speed threshold (frequency) (expressed in %) P.0332 Maximum speed delay (frequency) To disable: P.0332 =0 Enabled in: MAN, AUTO, TEST, REMOTE START Mecc Alte S.p.A. - Full or partial reproduction prohibited, if not authorized...
(parameter P.2002). It activates only when MCB is commanded to open (relay operating) and the status acquired is continuously “active” (closed) for the time set. In auto mode it activates after three consecutive attempts. It can be: Mecc Alte S.p.A. - Full or partial reproduction prohibited, if not authorized...
Category: Generic Related parameters: P.2001 Feature of the input 1 or equivalent for the other inputs P.2002 Delay for the input 1 or equivalent for the other inputs Mecc Alte S.p.A. - Full or partial reproduction prohibited, if not authorized...
P.2001 or equivalent for the other inputs) and if a time other than zero has been set for said input (parameter P.2002 or equivalent). Active if the configured input remains continuously active for the associated time. Mecc Alte S.p.A. - Full or partial reproduction prohibited, if not authorized...
It activates if the level measure remains continuously above or equal to threshold P.0343 (in percentage) for time P.0344. 31 – High coolant temperature (from contact) Type: Warning Mecc Alte S.p.A. - Full or partial reproduction prohibited, if not authorized...
P.0216 (oil mask) from engine start has elapsed (this is to allow you to start the engine idle, to cool it off) Mecc Alte S.p.A. - Full or partial reproduction prohibited, if not authorized...
Remark: if engine’s protections override function is enabled, this anomaly becomes a warning. 37 – Starter battery voltage, low Type: Warning Category: Battery protection Related parameters: P.0362 Low battery voltage threshold (%) P.0363 Low battery voltage delay Mecc Alte S.p.A. - Full or partial reproduction prohibited, if not authorized...
Note: if engine’s protections override function is enabled, this anomaly becomes a warning. 40 – Service required (second counter) Type: Configurable (Warning/Alarm/Unload/Deactivation) Mecc Alte S.p.A. - Full or partial reproduction prohibited, if not authorized...
This protection is enabled only if the controller acquires the measure of the engine lubrication oil pressure. It can acquire it from its input (JM_03, P.4017 suitably configured) or from CAN-BUS (P.0700 other than zero). It is only enabled if the Mecc Alte S.p.A. - Full or partial reproduction prohibited, if not authorized...
45 – Maximum auxiliary current Type: Alarm Category: Generic Related parameters: P.0108 Primary of the CT for the auxiliary current P.0140 Secondary of the CT for the auxiliary current Mecc Alte S.p.A. - Full or partial reproduction prohibited, if not authorized...
This protection is disabled in the engine start/arrest phases. It activates if the system total active power is positive and remains continuously over the threshold P.0350 for time P.0351. With parameter P.0352 it is possible to select the protection to be activated (warning, deactivation, alarm). Mecc Alte S.p.A. - Full or partial reproduction prohibited, if not authorized...
P.0102 Generator rated voltage P.0106 Generator rated output P.0317 Current asymmetry threshold (% rated current) P.0318 Current asymmetry delay To disable: P.0318 =0 Enabled in: MAN, AUTO, TEST, REMOTE START Mecc Alte S.p.A. - Full or partial reproduction prohibited, if not authorized...
0.5 seconds filter time. When activated, it acts as warning, deactivation or alarm as configured with P.0320. 56 – Low generator voltage Type: Warning Mecc Alte S.p.A. - Full or partial reproduction prohibited, if not authorized...
In addition, the generator voltages and frequency must be within the tolerance range and the load must be changed-overt to the generator. Threshold P.0395 is expressed as a Mecc Alte S.p.A. - Full or partial reproduction prohibited, if not authorized...
The protection activates when the generator frequency rises continuously over threshold P.0397 for time P.0398. 61 – Lost Excitation Type: Alarm Category: Generator protection Mecc Alte S.p.A. - Full or partial reproduction prohibited, if not authorized...
Warning Category: Generic Related parameters: P.4025 Function of the ANALOGUE input 4 (CT) P.0353 Low coolant temperature threshold P.0354 Low coolant temperature delay P.0700 Low coolant temperature delay Mecc Alte S.p.A. - Full or partial reproduction prohibited, if not authorized...
Configurable (Warning/Alarm/Unload/Deactivation) Category: Generic Related parameters: P.1700 Voltage regulator (AVR) type P.1706 Communication timeout with AVR (s) P.1707 Action for communication failure with AVR To disable: P.1706 = 0 Mecc Alte S.p.A. - Full or partial reproduction prohibited, if not authorized...
(P.0133). 100 – Maximum differential current Type: Alarm Category: Generic Related parameters: P.0377 Maximum differential current threshold (Aac) P.0378 Maximum current differential delay Mecc Alte S.p.A. - Full or partial reproduction prohibited, if not authorized...
This protection is enabled only if the board is connected to the engine via the CAN BUS (P.0700 different from zero). It is activated when the engine signals the overspeed state over the CAN BUS. 132 – High coolant temperature from CAN-BUS Type: Warning Mecc Alte S.p.A. - Full or partial reproduction prohibited, if not authorized...
Warning Category: Engine protection Related parameters: P.0700 Engine type P.0704 Can-Bus anomalies disable mask To disable: bit 6 of P.0704 on Enabled in: MAN, AUTO, TEST, REMOTE START Mecc Alte S.p.A. - Full or partial reproduction prohibited, if not authorized...
CAN BUS. 158 – High oil temperature from CAN BUS Type: Warning Category: Engine protection Related parameters: P.0700 Engine type P.0704 Can-Bus anomalies disable mask Mecc Alte S.p.A. - Full or partial reproduction prohibited, if not authorized...
CAN BUS. 199 – Alarms cumulative – Red lamp (from CAN-BUS) Type: Configurable (Warning/Interlock) Mecc Alte S.p.A. - Full or partial reproduction prohibited, if not authorized...
Related parameters: P.0800 bus mode PMCB P.0803 number of gensets on bus PMCB To disable: P.0803 =0 Enabled in: MAN, AUTO, TEST, REMOTE START The protection activates if the CAN-BUS is activated (P.0800). Mecc Alte S.p.A. - Full or partial reproduction prohibited, if not authorized...
It activates if the breaker remains open for the time related to the feedback input, in presence of the opening command. 206 – Failure to open NECB switch (only GC400x) Type: Adjustable Mecc Alte S.p.A. - Full or partial reproduction prohibited, if not authorized...
Note: the parameter is aimed just to allow the operation of old plants in case of a firmware update. In new plants, it should be left at zero. 252 – CAN-BUS (EXBUS) expansion modules missing Type: Warning Category: Generic Mecc Alte S.p.A. - Full or partial reproduction prohibited, if not authorized...
255 - Connection with CAN-BUS (EXBUS) sensor timed out. Type: Warning Category: Generic Related parameters: P.0142 Number of DITEMP modules P.0143 Number of DIVIT modules To disable: P.0142=0 e P.0143=0 Mecc Alte S.p.A. - Full or partial reproduction prohibited, if not authorized...
274 – Sectioned auto production line (only GC400x) Type: Deactivation Related parameters: P.2001 Function of address 1 or equivalent for other inputs. P.2002 Delay for input 1 or equivalent for other inputs. Mecc Alte S.p.A. - Full or partial reproduction prohibited, if not authorized...
The warning is normally a pre-alarm. It becomes a deactivation (only in automatic modes) after 60 seconds if the controller does not need to close the GCB. Mecc Alte S.p.A. - Full or partial reproduction prohibited, if not authorized...
The controller keeps the pump off if the selected source is not available (maintaining the selected operation mode though). With the controller in OFF_RESET the pump is always stopped. Mecc Alte S.p.A. - Full or partial reproduction prohibited, if not authorized...
Low level contact (input with feature DIF.4212): closed if the level is below the low-level threshold. • Start-up contact (input with feature DIF.3301) closed if the level is below the pump start-up threshold. Mecc Alte S.p.A. - Full or partial reproduction prohibited, if not authorized...
If the input remains active for the time configured, the controller issues a warning (the text of which will be the one configured) and stops the pump (without changing its operating mode). Mecc Alte S.p.A. - Full or partial reproduction prohibited, if not authorized...
In these cases, if the unit is controlling mains loads closing, but acquires an MCB open status (continuously for the time associated to the input), it will perform the following: • It activates the warning W272 “Mains reverse synchronization failure” • GCB open Mecc Alte S.p.A. - Full or partial reproduction prohibited, if not authorized...
In the same way, the output is disabled if the power rises above the upper threshold for the set time. These thresholds and delays are set with following parameters: Mecc Alte S.p.A. - Full or partial reproduction prohibited, if not authorized...
P.0107: CT primary for generator/load. • P.0108: CT primary for auxiliary current. • P.0109: Transformer type for auxiliary current. • P.0116: Mains nominal voltage • P.0117: Mains VT primary voltage. Mecc Alte S.p.A. - Full or partial reproduction prohibited, if not authorized...
Page 253
This function is usually used with multiple-voltage and/or multiple-frequency panels: wiring the cams of a selector to the panel on the inputs of the controller, you can manually switch voltages and frequency without having to use the parameters of the controller. Mecc Alte S.p.A. - Full or partial reproduction prohibited, if not authorized...
But in this phase, the “Change-over sequence disabling” input is no longer skipped, and, being it active (connected on contact NC), it prevents the loads change-over on generator. When signal B activates, the “Change-over sequence disabling” input deactivates, thus allowing the load change-over on generator. Mecc Alte S.p.A. - Full or partial reproduction prohibited, if not authorized...
In this way, also powering the controller off, signalling is not lost and cannot be reset. Mecc Alte S.p.A. - Full or partial reproduction prohibited, if not authorized...
Therefore, a counter may not be immediately saved as its value changes; consequently, before powering the controller off, ensure to know when and how the counters were saved. Mecc Alte S.p.A. - Full or partial reproduction prohibited, if not authorized...
In case the controller is equipped with an Ethernet connection, the controller clock can be automatically updated through the connection towards the server “SMARTCLOUD” or towards a NTP server (see par. 5.17.4). The controller Mecc Alte S.p.A. - Full or partial reproduction prohibited, if not authorized...
The value for the parameter is the sum of the “value” fields in the following table related to the days you are interested in. Hexadecimal value Sunday Monday Tuesday Mecc Alte S.p.A. - Full or partial reproduction prohibited, if not authorized...
P.0422 refers to the days selected with P.0421, while the time set with P.0423 refers to the following days. Mecc Alte S.p.A. - Full or partial reproduction prohibited, if not authorized...
All calendars are identical: calendars 15 and 16, however, can be used for the activation/deactivation of the daylight save time (if parameter P.0409 is set to “3”). Each calendar can be individually selected as “monthly” or “weekly”: Mecc Alte S.p.A. - Full or partial reproduction prohibited, if not authorized...
Page 261
Value Hexadecimal Calendar 0001 Calendar 1 0002 Calendar 2 0004 Calendar 3 0008 Calendar 4 0010 Calendar 5 0020 Calendar 6 0040 Calendar 7 0080 Calendar 8 Mecc Alte S.p.A. - Full or partial reproduction prohibited, if not authorized...
Page 262
Using the parameters of the controller, this selection is done by means parameter P.1902 (for the calendar 1 or equivalent for other calendars). This is also a bit-field parameter: Value Hexadecimal Day of month Mecc Alte S.p.A. - Full or partial reproduction prohibited, if not authorized...
Page 263
131072 00020000 262144 00040000 524288 00080000 1048576 00100000 2097152 00200000 4194304 00400000 8388608 00800000 16777216 01000000 33554432 02000000 67108864 04000000 134217728 08000000 268435456 10000000 536870912 20000000 1073741824 40000000 Mecc Alte S.p.A. - Full or partial reproduction prohibited, if not authorized...
Page 264
Using the parameters of the controller, the time-slot can be selected by means P.1903 and P.1904 (for the calendar 1 or equivalent for other calendars). If those Mecc Alte S.p.A. - Full or partial reproduction prohibited, if not authorized...
The controller provides 4 generic timers fully configurable, that can be used inside the AND/OR logics to create complex sequential logics. Each timer, in fact, activates/deactivates an internal bit that can be used by the AND/OR logics. The four timers are identical. Mecc Alte S.p.A. - Full or partial reproduction prohibited, if not authorized...
Page 266
(“0 – Seconds”, “1 – Minutes”, “2 – Hours”) and the delay value. Each timer can work in four different modes, selectable by means parameter P.2901 (for the timer 1 or equivalent for the other timers): Mecc Alte S.p.A. - Full or partial reproduction prohibited, if not authorized...
Page 267
The internal bit keeps its previous status if the “activation condition” is false and the “reset condition” is false. The following example manages a digital output related to the internal bit of the timer 1: Mecc Alte S.p.A. - Full or partial reproduction prohibited, if not authorized...
• MAN-OFF: the pump is always off, even when the daily tank is empty. The operating mode can be selected in two ways: Mecc Alte S.p.A. - Full or partial reproduction prohibited, if not authorized...
Start contact (input with function DIF.3311): closed when the level is below the starting threshold of the pump. • Stop contact (input with function DIF.3312): closed if the level is below the pump stop threshold. Mecc Alte S.p.A. - Full or partial reproduction prohibited, if not authorized...
In addition, the activation and deactivation of the pump are recorded in the event log (if bit 7 of parameter P.0441 is active): • EVT.1072: pump activation. • EVT.1073: pump deactivation. Mecc Alte S.p.A. - Full or partial reproduction prohibited, if not authorized...
Page 271
GC315 & GC400 Technical Manual This Page Intentionally Left Blank ENGLISH Code: EAAM045625EN Rev. 25 | Date: 16/01/2023 Mecc Alte S.p.A. - Full or partial reproduction prohibited, if not authorized...
Page 272
UNITED KINGDOM SPAIN CHINA INDIA Mecc Alte U.K. LTD Mecc Alte España S.A. Mecc Alte Alternator Mecc Alte India PVT LTD 6 Lands’ End Way C/ Rio Taibilla, 2 (Nantong) Ltd Plot NO: 1, Talegaon Oakham Polig. Ind. Los Valeros 755 Nanhai East Rd Dhamdhere S.O.