Index Multi-Function Burner Display Information And General Warnings General Warnings ..............3 General Information .
Page 3
Index Multi-Function Burner Display QuickStart Guide- Setting Up Control Mode QuickStart Guide- Setting Up Solo Mode ..........27 QuickStart Guide- Setting Up Piccolo Mode .
Massimo Solo System and hardware configuration Piccolo 2 System and hardware configuration Introduction The Multi-Function Burner Display is included in kits de- fined in section 2.2 that can selected as 4.3" or 7" displays with LMV3 and LMV5 controls. 2.2 Burner touch screen kits BOM 2.2.1 4.3" touch screen kit (LMV3) - 20107665 4.3"...
Massimo Solo System and hardware configuration Piccolo 2.2.3 7" touch screen kit (LMV5) - 20179829 7" kit (20179829) Components list Description Part Number DB9 to wire 20143749 7" touch screen 20164159 Wire (beldon,white, red , green, black) 120AC/24 VDC power 20138550 supply Din rail C5311121 OCI412.10 C5360140 Light and Light button M6 Threaded rivet...
System and hardware configuration Factory integrated components Burner integration kit installed and tested. ► 4.3” HMI (LMV3/LMV5) ► 7.0” HMI (LMV5) Protocol gateway (optional) 2.4 Standard features In order to handle a wide variety of systems, the touch- Pumps/Valve setup ► Boiler circulator pump off delay screen is configurable. Please note that most of these features will not appear in certain modes.
System and hardware configuration Communication 2.5.1 Touch screen communication for burner control The burner touchscreen utilizes Modbus/TCP for commu- For an LMV5, the AZL module communicates using Mod- For an LMV5, the AZL module communicates using Mod- nications to 1 other burner (Piccolo option) or to Massimo bus RTU over RS232.
Page 9
System and hardware configuration Communication 2.5.3 Changing the COM2 address (MFBD modbus settings) 4. Scroll at the bottom tabs using the arrows until you find "COM port", select the tab and click the blue arrow pointing down to access more information on COM2 port. 5. To change the address, it is located in COM2 tab as "HMI Station No.:" If you are using MFBD with Piccolo or Solo system, change the address for all touchscreens.
System and hardware configuration 2.5.3 Changing the COM2 address (MFBD modbus settings) 6. You are now done. To go back to the main menu touchscreen page, click the home button located in the top right side and select the icon in the reference picture below: System overview 2.6.1 & 2.6.2 Solo & Piccolo system overview Piccolo (2.6.2)
System and hardware configuration 2.7 Navigation BURNER Lead/Lag Info (Piccolo Configuration) INFO ERROR HISTORY LEAD/LAG LEAD/LAG LEAD/LAG LEAD/LAG CONFIG 2 CONFIG 3 CONFIG 4 CONFIG 1 ALARM & SYSTEM WARNINGS OVERVIEW PICCO- LO MODE LEAD/LAG CONTROL PAGE Main Menu MEDIA/ COMMS DISPLAY NIGHT STANDBY CONFIG CONFIG. UNITS SE- SETBACK LECTION CONFIG GENEAL INPUTS...
System and hardware configuration 2.7 Navigation 2.7.1 Solo wiring: LMV3x, 4.3" touchscreen Please note: Use the wiring diagrams as reference only. 2.7.2 Solo wiring: LMV5x, 4.3"/ 7" touchscreen Please note: Use the wiring diagrams as reference only. DOC-0214190 - 04/2024...
System and hardware configuration 2.7.3 Piccolo wiring: LMV3x, 4.3" touchscreen Please note: Use the wiring diagrams as reference only. 2.7.4 Piccolo wiring: LMV5x, 4.3"/7" touchscreen Please note: Use the wiring diagrams as reference only. DOC0214190 - 04/2024...
Massimo Solo User interface Piccolo User interface The MFBD has features common to different modes. To keep it simple please use the following legend, as it applies to relevant functionality: Burner view The following will be dis- The following will be dis- played depending on the played depending on the mode selected:...
Massimo Solo User interface Piccolo Burner Mode Standalone (Solo): The burner will use local or remote Remote Modulation: The burner will run at the specified setpoint to modulate and maintain the process value (PV), load received from the BMS system. Load requests from the without any external intervention.
Massimo Solo User interface Piccolo 3.5 Media/ Units selection Specific Default Range Parameters Value Type of Media Choose Steam Steam - Water between Steam or Hot Water. °F °F - °C Unit display - Select proper temperature unit to be displayed. 3.6 Inputs info and configuration When using Burner with LMV3 and RWF55 Help screens are available to assist the technican properly set up the...
Massimo Solo User interface Remote Piccolo Modulation 3.7 Remote Setpoint Source & Remote Modulation Source Refer to 3.6 Refer to 3.6 A remote modulation signal can be sent to the burner via A remote setpoint can be sent to the burner via 0-20ma/4- 0-20ma/4-20ma/0-10vd hardwired or bus signal. 20ma/0-10vd hardwired or bus signal.
Massimo Solo User interface Piccolo 3.8.1 Cold Start Configuration Refer to 3.8.2 Refer to 3.6 Specific Default Range Parameters Value Disabled Enabled Cold start Disabled Enable/Disable the cold start routine. Dependent on system 1 - 400 °F/°C Release Target temperature/pressure setpoint 1 - 400 PSI for the cold start.
Massimo Solo User interface Piccolo 3.9 Pump/Valve Configuration 3.10 Night Setback Night setback can be set for any range of time any day of the week. Night setback setpoint will take priority over local or remote setpoint. DOC-0214190 - 04/2024...
Massimo Solo User interface Piccolo 3.11 Ethernet Configuration ►Massimo mode: Select "Massimo N# config", sets the actual position of how the boiler will be displayed in the Massimo Touchscreen to match the order of how the boilers are installed in the mechanical room. Also in the bottom right side select the buttom to give the desired name (number) to this boiler.
To connect the touchscreen to a gateway, please refer to configured in "BMS communication". The S3 dip switch has Riello Gateway N54 Manual or Riello Gateway N34 & N35 to be in the off position. Manual. Scan the QR code to view the gateway manual on section 2.2.
Massimo Solo User interface Piccolo 3.14 System setup examples The "Setup system examples" gives an overview view of the control flow for the MFBD. Examples are included as a guide to setting up RWF55. 3.15 2 Stages Control Setup This page displays all the settings for 2 stage setup with When burner is operating in second stage, the burner will Piccolo &...
Massimo Solo User interface Piccolo 3.16 Alarms & Warnings page Error screens gives the user plenty of information about each error occuring at the burner, including what the burner failure is, when it occured and also a translation of what the error means.
Massimo Solo User interface Piccolo 3.17 Burner Refer to 3.16 This page displays details of the burner such as: ► Run hours ► Call for heat indicator ► Number of Starts ► Low fuel pressure ► Air Servomotor ► Error code ►...
User interface 3.18 Automatic Fuel Change Over The automatic fuel changeover function is an optional Specific Default Range function for both LMV3X and LMV5X. Parameters Value (LMV3X requires additional hardware). Automatic fuel changeover The parameters are programmable to suit your application OFF - ON Enable/Disable the function.
QuickStart Guide - Setting up control mode QuickStart Guide - Setting up control mode 4.1 QuickStart Guide - Setting up Solo mode For Solo mode functionality. See below for setting up touch screen in Solo mode. Set for LMV3x or Select "Standalone (Solo)" LMV5x After selection, click done and power cycle the touchscreen. After completion your main screen will display "Standalone Mode selected"...
QuickStart Guide- Setting up control mode Step 2: Selecting boiler number for Piccolo mode Select "Piccolo IP config". After selecting boiler number, power After power cycle is done, on the cycle the touchscreen. main screen you will see THIS IS VERY IMPORTANT! "Piccolo B(x)" displayed. Step 3: Piccolo configurations This page displays lead/lag information and the actual configurations.
QuickStart Guide- Setting up control mode Step 4: Piccolo configurations (Lead/Lag) Specific Parameters Default Range Value Start Lag - Point 60 % 50 to 99 % where the lag boiler will be started. Stop Lag - Point 30 % 20 to 40 % where the lag boiler will be stopped. Specific Parameters Default Range Value Start Delay - Delay for...
4.3 QuickStart Guide- Setting up Massimo See below for lead/lag functionality. See below for setting up touchscreen in Massimo mode. Step 1: Selecting Massimo mode Set for LMV3x or Select "Lead/lag Massimo (2+ LMV5x boilers)" Step 2: Selecting boiler number Select "Massimo N# config". After the power cycle, on the main After selecting the position of the boiler screen you will see "Massimo N(x)
LAN2 Audio 5.2 Setting up VNC Viewer application Connect to the Riello touchscreen through a third party Recommended software for the VNC is "VNC CONNECT VNC software by entering the IP of the touchscreen. by RealVNC" (VNC Viewer) See link below for download: The IP of the burner touchscreens is set up and accessed https://www.realvnc.com/en/connect/download/viewer/...
Multi-function display version update Introduction The multi-function display is designed and programmed inhouse. Continuous improvements are being made to the system. For latest version please send a request to Riello for newest version (if available). 6.1 Unpacking the software Unzip "vX.XX_loader" into a separate folder you...
BMS setpoint (W) 100 (U16) Holding Reg. No units ** For gateway points list for all other available protocols see "Riello Gateway N34 & N35 Manual" or "Riello Gateway N54 Manual". ** Means - Unit range depends on the unit selected on the burner control (F,C & PSI). All units are scaled and within acceptable range of the variable. (W) - Means Writable Points.
Page 35
RIELLO BURNERS NORTH AMERICA 35 Pond Park Road 2165 Meadowpine Blvd. 1(800)4-RIELLO Hingham, Massachusetts Mississauga, Ontario USA 02043 Canada L5N 6H6 1(800)474-3556 www.riello.ca DOC-0214190 - 04/2024...