INSTALLATION MANUAL VRF Slim DC Inverter (MCSX-B) Original English Instructions...
Page 2
OUTDOOR MODELS COOL/HEAT INDOOR UNITS MCSX220D312B 22.4 kW / 25.0 kW MCSX280D317B 28.0 kW / 31.5 kW Installation training is available from Seeley International for qualified and licensed installers; please contact your local office for training dates. VRF Slim DC Inverter...
WARNING! FAILURE TO INSTALL AND COMMISSION THE PRODUCT IN COMPLIANCE WITH THESE INSTRUCTIONS, OR FAILURE TO DO THE JOB PROPERLY AND COMPETENTLY, MAY VOID THE CUSTOMER’S WARRANTY. FURTHER, IT COULD EXPOSE THE INSTALLER AND/OR THE RETAILER TO SERIOUS LIABILITY. SEELEY INTERNATIONAL - INSTALLATION MANUAL |...
SAFETY Before installing the appliance, Before using the appliance, read Before repairing the appliance, read the installation manual first. the owner’s manual first. read the service manual first. BEFORE INSTALLATION The installer should read all instructions carefully prior to installation, and ensure that every step described in this manual is understood and taken into account before starting installation.
Page 5
Before using the recovery machine, check that it is in satisfactory working order, has been properly maintained and that any associated electrical components are sealed to prevent ignition in the event of a refrigerant release. Consult Seeley International if in doubt.
Page 6
MOST COMMON CAUSES OF POOR COOLING PERFORMANCE Issue Cause & Description Page No. Ductwork Incorrectly sized or poorly designed duct can have a disastrous effect on the cooling and heating performance. Whilst it is best to keep duct runs as short as possible, it is also advisable to have at least 3m* of duct connected to any grille or diffuser.
OUTDOOR UNIT INSTALLATION PARTS PROVIDED Parts for Outdoor Unit Name Appearance Remark User Manual — Wiring (match with Must be connected to the last IDU of resistance) communication connection This part is included in the following Liquid side models: connection pipe MCSX220D312B This part is included in the following Gas side connection...
Refer below for a guide on the maximum number of indoor units that can be connected to each outdoor total, and the maximum of each indoor that can be connected to any one outdoor. CAPACITY MAXIMUM NO. OF OUTDOOR MODELS COOL/HEAT INDOOR UNITS MCSX220D312B 22.4 kW / 25.0 kW MCSX280D317B 28.0 kW / 31.5 kW SEELEY INTERNATIONAL - INSTALLATION MANUAL |...
(m) Equivalent length 150m From the 1 branch to the farthest indoor pipe L2+L3+d ODU at upper side Height difference between ODU and IDU ODU at lower side Height difference between IDUs Table 05 SEELEY INTERNATIONAL - INSTALLATION MANUAL |...
PIPE WORK - cont. DIMENSION OF PIPE (MAIN PIPE) FROM ODU TO THE 1 INDOOR BRANCH Dimension of pipe from ODU to the 1st indoor branch will be determined by the dimension of outdoor connection pipe. Fig. 06 Pipe Dimension Basic Module Connection method Gas pipe (mm)
16.0 < C ≤ 28.0 Ø22.2 Ø9.52 Table 09 NOTE: If the distance between IDU and its nearest branch is over 10m, then the liquid pipe of IDU (rated capacity ≤5.0kW) shall be enlarged. SEELEY INTERNATIONAL - INSTALLATION MANUAL |...
PIPE WORK - cont. INSTALLATION OF CONNECTION PIPE Precautions for the Installation of Connection Pipe Conform to the following principles during pipe connection: Connection pipe should be as short as possible, and the height difference between indoor and outdoor units should be kept to a minimum. Keep the number of bends as little as possible. Radius of curvature should be as large as possible.
PIPE WORK - cont. OUTDOOR PIPE CONNECTION During engineering installation, the connection pipe inside the unit must be wrapped by insulation sleeve. Pipe connection for MCSX220D312B: As shown in Fig.15 and Fig.16, open the outermost soundproof cotton and place a fire barrier between compressor and straight pipe.
Page 17
1 (liquid pipe) and then weld connection pipe 2 (gas pipe). During welding, it’s necessary to use wet gauze to wrap up the filter near connection pipe 2 and the two cut-off valves. Make sure the flame won’t burn the soundproof cotton or other components. Fig. 17 Fig. 18 SEELEY INTERNATIONAL - INSTALLATION MANUAL |...
PIPE WORK - cont. INSTALLATION OF Y-TYPE BRANCH Y-type Branch. Fig. 19 Y-type branch has several pipe sections with different dimension, which facilitates to match with various copper pipes. Use pipe cutter to cut in the middle of the pipe section that is of proper dimension and remove burrs as well. See Fig.20.
Additional refrigerant is required and determined by the length and size of installed field liquid pipes. Refer to adding refrigerant table for correct calculation iii. Please record the amount of refrigerant added to the system, on the additional sticker located on the outdoor unit. SEELEY INTERNATIONAL - INSTALLATION MANUAL |...
Page 20
VACUUM PUMPING, REFRIGERANT ADDING - cont. Calculation of the amount of additional refrigerant. Calculation method of the quantity of additional refrigerant (based on liquid pipe). Quantity of additional refrigerant = ∑length of liquid pipe × quantity of additional refrigerant per meter. Quantity of additional refrigerant per meter for liquid pipe(kg/m) Ø22.2 Ø19.05...
D1/D2 communication wire must start at the outdoor unit and finish at the last indoor unit, connecting each indoor unit, one after another. Failure to wire the D1/D2 communication wires in this method will cause system failure. NOTE: Optional central control connected to G1/G2 at outdoor unit. SEELEY INTERNATIONAL - INSTALLATION MANUAL |...
ELECTRICAL WIRING - cont. Selection of circuit breaker and power cable. Circuit Breaker (Number of power cable + Number of Model Power Supply Capacity (A) ground wire) × Min sectional area (mm (4 + 1) x 2.5 MCSX224D312B 380-415V 3N~ 50/60Hz (4 + 1) x 2.5 MCSX280D317B 380-415V 3N~ 50/60Hz...
Before test operation, make sure unit is power on and compressor has been preheated for more than 8 hours. Touch the unit to check whether it’s normally preheated. If yes, start test operation. Otherwise, compressor might be damaged. SEELEY INTERNATIONAL - INSTALLATION MANUAL |...
COMMISSIONING AND DEBUGGING - cont. TEST OPERATION AND DEBUGGING Description of test operation procedures and main board display of ODU. Description of each stage of debugging progress Debugging — Progress code Status code code LED1 LED2 LED3 Code meaning and operation method Progress Display Display...
Page 25
01 (NOTE: Before re-charging before refrigerant, unit must be power off in case startup system starts progress 10 automatically). Refrigerant is normal and unit will display as in the left for 2s. Then next step starts. SEELEY INTERNATIONAL - INSTALLATION MANUAL |...
Page 26
COMMISSIONING AND DEBUGGING - cont. Description of each stage of debugging progress Debugging — Progress code Status code code LED1 LED2 LED3 Code meaning and operation method Progress Display Display Display Code Code Code status status status Valves of ODU are being inspected. Compressor will start operation for 2min or so and then stop.
Page 27
EXV In heat mode, the opening degree of indoor EXV varies within 70~480PLS. Communication Communication Number of IDUs detected by software is the same — parameters data with the actual number. No communication error. SEELEY INTERNATIONAL - INSTALLATION MANUAL |...
Reduce the thermal source room The filter is dirty and blocked Clean the filter NOTE: If problem cannot be solved after checking above items, please contact Seeley International service centre and mention the issue along with the model number. VRF Slim DC Inverter...
Malfunction of low-pressure sensor Malfunction of discharge temperature Low-pressure protection sensor of compressor 1 High discharge temperature protection of Malfunction of DC motor compressor High discharge temperature protection of Malfunction of outdoor ambient compressor 1 temperature sensor SEELEY INTERNATIONAL - INSTALLATION MANUAL |...
Page 30
ERROR INDICATION - cont. Error Code Content Error Code Content Drop protection of discharge temperature Malfunction of defrosting temperature sensor of compressor 1 sensor 1 Malfunction of liquid temperature sensor Over-current protection of compressor 1 of sub-cooler Malfunction of gas temperature sensor of Gas-mixing protection of 4-way valve sub-cooler Malfunction of inlet tube temperature...
After selecting relevant functions, press SW7 to confirm and start setting this function. Main board of outdoor unit will display as below: LED1 LED2 LED3 Function code Display Current progress Display Current status Display Blink Blink Blink Blink Blink Blink SEELEY INTERNATIONAL - INSTALLATION MANUAL |...
AFTER-SALES SERVICE In case the air-conditioning unit you bought has any quality problem or you have any inquiry, please contact the local after-sales service agency designated by Seeley International. Warranty should meet the folowing requirements: First run of the unit should be operated by professional personnel from Seeley appointed service centre.
Please draw out the schematics on the following page based on the number of indoor units, and write down the liquid pipe size and length on the respective branch. Indoor unit #1 Indoor unit #2 Indoor unit #3 SEELEY INTERNATIONAL - INSTALLATION MANUAL |...
Asked the home owner/user if they have any questions about how to use or maintain the Braemar Refrigerated Air Conditioning unit. Customer Signature ..............Date ..............Installer Signature ............... Date ..............System design notes: Zone details: please provide room details Cooling mode: Heating mode: ................................. SEELEY INTERNATIONAL - INSTALLATION MANUAL |...
MAINTENANCE SCHEDULE Installation Date: Installer: Items to be done by the Home Owner/User (please sign in the places indicated) Monthly Annually Year 1 Year 2 Year 3 Year 4 Year 5 Air filter cleaning Air filter replacement Maintain required clearance around Outdoor unit Items to be done by a Quali ed Licensed Technician (Home owner/user must ensure that the technician signs and dates in the places indicated)
Warranty conditions are subject to property access and industry Safety Standards. Seeley International strives for continuous product improvements, therefore specifications are subject to change without notice. Unit colour may vary slightly from that depicted in this booklet. Installation and commissioning of this system to the manufacturer’s specification, compliance with industry standards, and local, state and national regulatory codes are the responsibility of the installer.
NOTES ....................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................VRF Slim DC Inverter...
Page 39
....................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................SEELEY INTERNATIONAL - INSTALLATION MANUAL |...
Page 40
Warranty Service Australia 1300 650 644 It is the policy of Seeley International to introduce continuous product improvement. Accordingly, specifications are subject to change without notice. Please consult with your dealer to confirm the specifications of the model selected. seeleyinternational.com...