Temperature switch for hygienic applications
monitoring of temperatures
in gases, vapors, liquids and dust (32 pages)
Summary of Contents for ACS KAK
Page 1
Technical manual BA 0424 KAK / KLK Filling level limit switch for conductive filling level supervision in electrically conductive liquids Detects up to two limit values Useable ▪ for filling level resp. limit value detection in liquid container ▪ as overflow protection in container ▪...
Function Measuring principle The filling level limit switch KAK resp. KLK is mounted in the wall of the container or of the pipe by using the respective process connection or installed over the filling liquid by using a suitable mount.
• Not exposed to corrosive media • Protected against solar radiation • Avoiding mechanical shock and vibration • Storage and transport temperature -20…+85°C • Relative humidity 20…85% __________________________________________________________________________________________________________________ Page 4 of 20 ACS Control-System GmbH | www.acs-controlsystem.de | info@acs-controlsystem.de | Eggenfelden | Germany...
The tightening of the thread process connection may only be done at the hexagon by a suitable spanner at most with the maximum permitted torque strength (» chapter Technical Data) __________________________________________________________________________________________________________________ Page 5 of 20 ACS Control-System GmbH | www.acs-controlsystem.de | info@acs-controlsystem.de | Eggenfelden | Germany...
Page 6
After shortening the electrode rod remove at least 10 mm of the isolation. At shortening the electrode may not be stressed mechanically to avoid damaging of the isolation. __________________________________________________________________________________________________________________ Page 6 of 20 ACS Control-System GmbH | www.acs-controlsystem.de | info@acs-controlsystem.de | Eggenfelden | Germany...
1 and channel 2 (CH1 and CH2) must be set identically Function indicator ▪ LED yellow ➔ output relay S1 switched on ▪ LED yellow ➔ output relay S2 switched on __________________________________________________________________________________________________________________ Page 8 of 20 ACS Control-System GmbH | www.acs-controlsystem.de | info@acs-controlsystem.de | Eggenfelden | Germany...
Page 9
The relay switches off, if the switching level is overrun, (Liquid connection between measuring electrode CH1/CH2 and reference electrode REF) or at power supply fail. __________________________________________________________________________________________________________________ Page 9 of 20 ACS Control-System GmbH | www.acs-controlsystem.de | info@acs-controlsystem.de | Eggenfelden | Germany...
Page 10
The output relay S2 continues operation in limit value mode. The safety function is selected by one jumper per channel, inside the housing of the device. __________________________________________________________________________________________________________________ Page 10 of 20 ACS Control-System GmbH | www.acs-controlsystem.de | info@acs-controlsystem.de | Eggenfelden | Germany...
Page 11
Configuration jumper (B) Safety function ▪ Minimum safety = no ▪ Maximum safety = nc Function indicator (C) ▪ LED yellow ➔ PNP switching output active __________________________________________________________________________________________________________________ Page 11 of 20 ACS Control-System GmbH | www.acs-controlsystem.de | info@acs-controlsystem.de | Eggenfelden | Germany...
Page 12
The output signal switches off, if the switching level is overrun, (Liquid connection between measuring electrode CH1 and reference electrode REF) or at power supply fail. __________________________________________________________________________________________________________________ Page 12 of 20 ACS Control-System GmbH | www.acs-controlsystem.de | info@acs-controlsystem.de | Eggenfelden | Germany...
Page 13
Two-position-control s version GA – PNP switching output The two-position-control function is always active. The safety function is selected by a jumper inside the housing of the device. __________________________________________________________________________________________________________________ Page 13 of 20 ACS Control-System GmbH | www.acs-controlsystem.de | info@acs-controlsystem.de | Eggenfelden | Germany...
As required by the Directive 2012/19/EU on waste electrical and electronic equipment (WEEE), products of ACS are marked with the depicted symbol in order to minimize the disposal of WEEE as unsorted municipal waste. Such products may not be disposed of as unsorted municipal waste and can be returned to ACS for disposal.
4 mm W 8 mm Length L1/L2/L3 electrode rod in mm, max. 2500 mm KAK resp. KLK _ _ _ _ _ _ _ _ _ _ __________________________________________________________________________________________________________________ Page 20 of 20 ACS Control-System GmbH | www.acs-controlsystem.de | info@acs-controlsystem.de | Eggenfelden | Germany...