GWA – 250 / GWAP-250
Limit value switch
for limit value supervision of
electrical signals
Evaluable Signals
Standard signals 0...10V / 0...20mA resp. 4...20mA
Temperature resistor Pt100 from –50°C...+650°C
Two limit value relays with different operation modes
Safety function with minimum or maximum safety
Double limit value function – two separated limit values
Two-position-control function – a limit value with hysteresis
Configurable switching delay
Simple operation per key coding switch for adjusting the
limit values from 0...99% of the signal range in steps of 1%
Integrated measurand transducer supply
Version with remote control available
Wide range power supply from 20 to 253V AC and DC
L a u t e r b a c h s t r . 5 7 – 8 4 3 0 7 E g g e n f e l d e n – G e r m a n y
T e l : + 4 9 8 7 2 1 / 9 6 6 8 - 0 – F a x : + 4 9 8 7 2 1 / 9 6 6 8 - 3 0
i n f o @ a c s - c o n t r o l s y s t e m . d e
BA 0509
w w w . a c s - c o n t r o l s y s t e m . d e
Signal converter

Advertisement

Table of Contents
loading

Summary of Contents for ACS GWA-250

  • Page 1 Technical manual BA 0509 Signal converter GWA – 250 / GWAP-250 Limit value switch for limit value supervision of electrical signals Evaluable Signals Standard signals 0...10V / 0...20mA resp. 4...20mA Temperature resistor Pt100 from –50°C...+650°C Two limit value relays with different operation modes Safety function with minimum or maximum safety Double limit value function –...
  • Page 2: Table Of Contents

    GWA – 250 Index Order code ........................2 Application ........................3 Function ........................3 / 4 Safety notes ........................5 Installation ........................5 Maintenance ........................5 Repair ..........................5 Electrical connection ....................6 Operation and display elements ..................7 Technical data .......................
  • Page 3: Application

    GWA – 250 Application The limit value switch GWA – 250 is used for supervising electrical standard signals 0...10V / 0...20mA resp. 4...20mA or temperature resistors Pt100 regarding transgression resp. underrun of limit values. The device allows it, additionally to continuous measurements, to set up to two switching limits without the need for additional measurement devices.
  • Page 4 GWA – 250 Safety function The safety function defines the operation principle of the output relays. Maximum safety: The relay switches off, if the switching level is transgressed, or the power supply fails. Minimum safety: The relay switches off, if the switching level is underrun, or the power supply fails.
  • Page 5: Safety Notes

    GWA – 250 Safety notes Each person that is engaged with inauguration and operation of this device, must have read and understood this technical manual and especially the safety notes. Installation, electrical connection, inauguration and operation of the device must be made by a qualified employee according to the informations in this technical manual and the relevant standards and rules.
  • Page 6: Electrical Connection

    GWA – 250 Electrical connection The electrical connection of the device must be carried out according to the respective country specific standards. Incorrect installation or adjustment could cause applicationally conditioned risks. Power supply input, measuring input and relay output channels are safe galvanically isolated from each other. This is also valid for both relay output channels among each other.
  • Page 7: Operation And Display Elements

    GWA – 250 Operation and display elements Limit value channel A 2-digit key coding switch Configuration switch Function indicator inside the housing 3 LED’s for indication of operating states Limit value channel B 2-digit key coding switch Function indicator green LED ready status, power supply voltage on red LED output relay A switched on...
  • Page 8: Technical Data

    GWA – 250 Technical data Auxiliary power supply Permitted supply voltage: 20 V to 253 V AC / DC 48...62 Hz, reverse polarity protected ≤ 2,5 VA / 1,75 W Power consumption: Overvoltage category: acc. to DIN EN 61010-1 Protection classification: double or reinforced insulation Isolation voltage: 4kV~...