Temperature switch for hygienic applications
monitoring of temperatures
in gases, vapors, liquids and dust (32 pages)
Summary of Contents for ACS GWA-250
Page 1
Technical manual BA 0509 Signal converter GWA – 250 / GWAP-250 Limit value switch for limit value supervision of electrical signals Evaluable Signals Standard signals 0...10V / 0...20mA resp. 4...20mA Temperature resistor Pt100 from –50°C...+650°C Two limit value relays with different operation modes Safety function with minimum or maximum safety Double limit value function –...
GWA – 250 Application The limit value switch GWA – 250 is used for supervising electrical standard signals 0...10V / 0...20mA resp. 4...20mA or temperature resistors Pt100 regarding transgression resp. underrun of limit values. The device allows it, additionally to continuous measurements, to set up to two switching limits without the need for additional measurement devices.
Page 4
GWA – 250 Safety function The safety function defines the operation principle of the output relays. Maximum safety: The relay switches off, if the switching level is transgressed, or the power supply fails. Minimum safety: The relay switches off, if the switching level is underrun, or the power supply fails.
GWA – 250 Safety notes Each person that is engaged with inauguration and operation of this device, must have read and understood this technical manual and especially the safety notes. Installation, electrical connection, inauguration and operation of the device must be made by a qualified employee according to the informations in this technical manual and the relevant standards and rules.
GWA – 250 Electrical connection The electrical connection of the device must be carried out according to the respective country specific standards. Incorrect installation or adjustment could cause applicationally conditioned risks. Power supply input, measuring input and relay output channels are safe galvanically isolated from each other. This is also valid for both relay output channels among each other.
GWA – 250 Operation and display elements Limit value channel A 2-digit key coding switch Configuration switch Function indicator inside the housing 3 LED’s for indication of operating states Limit value channel B 2-digit key coding switch Function indicator green LED ready status, power supply voltage on red LED output relay A switched on...
GWA – 250 Technical data Auxiliary power supply Permitted supply voltage: 20 V to 253 V AC / DC 48...62 Hz, reverse polarity protected ≤ 2,5 VA / 1,75 W Power consumption: Overvoltage category: acc. to DIN EN 61010-1 Protection classification: double or reinforced insulation Isolation voltage: 4kV~...