EngA ENGINEERED AIR base Technical Manual page 11

Table of Contents

Advertisement

base
FbA
AI
Feedback Air
CP
AI
Condensate probe
PV1, PV2
DO
Pilot valve
SR1, SR2
DO
Safety relay
FR1, FR2
DO
Flame relay
EnH
DI
Enable heat
FbV
DI
Feedback valve
VN
Valve neutral
HL
DI
High limit
BFS
DI
Blocked flue switch
CAS
DI
Combustion air switch
Common to output set
CMd
COM
'd'
SDO
DO
Multipurpose output.
WPu
DO
Water Pump
FbD
AI
Damper Feedback
ASP
AI
Remote VFD Setpoint
RPM
AI
VFD feedback speed
Modulating heating
thermostat or control for
W+-
AI
humidification on SH
version
AA1,2
AI
Ambient air temperature
DA1,2
AI
Discharge temperature
Modulating cooling
Y+-
AI
thermostat
HiE
DI
High Speed Enable
EnC
DI
Enable cooling
OCC
DI
Occupied / Unoccupied
ENF
DI
Enable Fan
DES
DI
Damper End Switch
FbB
DI
Air Proving Switch
BYP
DI
VFD Bypass
MX1, MX2
AO
Maxitrol Valve
IOM74
Compares the combustion air actuator
feedback signal to the demand signal.
Condensate probe sensor input.
Disables the pilot flame once the main
burner has been established.
Secondary safety lockout contacts
Flame relay enable contacts.
24V must be applied to allow heating
function.
Feedback signal from the safety shut off
valve (SSOV). Wired directly to valve.
Neutral feedback signal from the safety shut
off valve (SSOV) and High Limit.
Normally closed, opens on high temperature.
Normally closed, opens on blocked flue.
Optional proof of combustion air flow.
Common power relays 'd', above.
HE dual flame sensing switchover and
Combustion blower start output for DG.
Enable evaporative 'swamp' cooler water
pump.
Modulating damper actuator feedback.
VFD speed input demand signal.
VFD output speed feedback
Independent heating demand or SH humidity
signal.
10k Type 2 thermistor
10k Type 2 thermistor
Independent cooling demand signal.
Initiate high speed operation.
Enable / disable mechanical cooling.
Enable occupied mode when powered.
Occupied mode start
Mechanical damper end switch input
Supply blower air proving switch
VFD bypass input.
DC current output to the Maxitrol modulating
valve.
11
A
0-10 Vdc
Ohms (Ω)
24/120 Vac
24/120 Vac
24/120 Vac
24 Vac
24/120 Vac
24 Vac
24 Vac
24 Vac
24/120 Vac
24/120 Vac
0-10 Vdc
0-10 Vdc
0-10 Vdc
0-10 Vdc
Ohms (Ω)
Ohms (Ω)
0-10 Vdc
24 Vac
24 Vac
24 Vac
24 Vac
24 Vac
24 Vac
24 Vac
mAdc
November 2020 R105